
GEI-90802
Remove
the
relay
from
its
case
and
check
that
there are
no
broken
or
cracked
molded
parts
or other signs of physical
damage.
and
that
all
screws are
tight.
Check
that
the short fingers are in the
correct
location.
as indicated in Figure 7.
and
that
the
auxiliary
brushes are properly adjusted (see Figure 12).
MECHANICAL
INSPECTION
1.
Check
that
the
rotating
element
moves
without noticeable
friction.
2.
Remove
the time-dial locking screws
and
check
that
the
moving
contact
just
touches the
stationary
contact
when
the time
dial
is
set
at
zero
(0).
The
contact
wipe
should
be
approximately 1/32". Put locking screws
back
in place.
3.
Check
that
the control spring
is
not
deformed
and
that
the spring convolutions
at
the
No.
5 time-dial
setting
are reasonably concentric.
4.
Check
that
the armatures of the telephone
relays
move
freely.
Also. with the
telephone relays in the de-energized
position,
all
circuit-closing
contacts
should
have
a
gap
of 0.015"
and
all
circuit-opening contacts should
have
a
wipe
of 0.005".
Gap
may
be
checked
by
inserting
a
feeler
gage,
and
wipe
can
be
checked
by
observing the
amount
of
deflection
on
the
stationary
contact before
parting the contacts.
The
armature should then
be
operated
by
hand
and
the
gap
and
wipe
again checked as described above.
ELECTRICAL
TESTS
Connect the
relay
as
shown
in Figure
10
and
check
the following:
1.
Check
that
the relay picks
up
with approximately the time delay
shown
in
Figure
6
when
a single-phase source of
at
least
rated voltage
is
connected
to
both
operati
ng
coil
s.
2.
Check
that
the relay picks
up
at
a
200
cloSing angle (or other closing angle
if
used) within
~
30
when
connected
to
a source with rated voltages
on
both
coils.
Check
zero-displacement pickup.
which
should agree with the value
in
Figure 1
within
~
10%.
3.
With
both
coils
connected
to
a rated voltage source with zero displacement,
check
that
pickup time agrees with the values given in Figures 4
or
5
~
10%.
4.
With
an
adjustable
115
volt
source of rated frequency, check
that
the
telephone-type
units
pick
up
at
50%
or
less
of
rated
voltage
and
drop out
at
15%
or
more
of rated voltage.
To
check
the
"L"
relay,
connect the voltage
source
to
studs 5
and
6.
To
check
"B"
relay,
connect voltage
to
studs 8
and
9.
INSTALLATION
PROCEDURE
If.
after
acceptance
tests.
the
relay
is
held in storage before shipment
to
the job
site.
it
is
recommended
that
the visual
and
manual
inspections described in the
section
on
ACCEPTANCE
TESTS
be
repeated before
installation.
7