GF Signet 8250-2 User manual

1Signet 8250-2 Level Transmitter
CAUTION!
• Remove power to unit before wiring
input and output connections.
• Follow instructions carefully to avoid
personal injury.
Signet 8250-2 Level Transmitter English
Contents
1. Description
2. Specifications
3. Panel installation
4. Electrical Connections
5. System configuration
Signet Level
Transmitter
Level
+10.00 ft
Relay 1 Relay 2
ENTER
1. Description
ProcessPro transmitters are available in two styles: panel mount and field mount. The panel mount is supplied with the necessary
hardware to install the transmitter. This manual includes complete panel mounting instructions.
Field mounting requires one of two separate mounting kits. The 3-8052 integral kit joins sensor and instrument together into a single
package. The 3-8050 Universal kit enables the transmitter to be installed virtually anywhere.
Detailed instructions for integral mounting or other field installation options are included with the 3-8052 Integral kit or the 3-8050
Universal kit.
General
Compatible Sensors: Signet 2450 Pressure Sensor (S3L)
Signet 2250 Level Sensor (S3L)
Other 3rd party sensors with 4 to 20 mA
output (via Model 8058)
Materials:
• Case: PBT
• Panel case gasket: Neoprene
• Window: Polyurethane-coated polycarbonate
• Keypad: Sealed silicone rubber, 4-button
Weight: Approx. 325 g (12 oz.)
Display:
• Alphanumeric 2 x 16 LCD
• Display update rate: 1 second
• Contrast: User selected, 5 levels
Electrical
Power supply: 12-24 VDC ±10% regulated,
250 mA max current
Sensor power: 5 VDC ±1% @ 25 ºC, regulated
2-wire system: 1.5 mA maximum current
4-wire system: 20 mA maximum current
Current output:
• 4 to 20 mA, isolated, fully adjustable and reversible
• Max loop impedance: 50 Ωmax. @ 12 V
325 Ωmax. @ 18 V
600 Ωmax. @ 24 V
• Update rate: 300 ms
• Output accuracy: ±0.03 mA
Relay outputs (2 sets mechanical SPDT contacts):
• Software supports 2 additional relays via optional external relay module
Note: When using the 8059-4 or -4AC, only relays 1 and 2 can be
utilized with the level instrument.
• Maximum voltage rating:
5 A @ 30 VDC, or 5 A @ 250 VAC, resistive load
• Programmable for High or Low setpoint or for Window range,
with adjustable hysteresis
• May be disabled if not used
• Time delay: Programmable from 0 s to 6400 s
Environmental:
• Operating temperature: -10 °C to 70 °C (14 °F to 158 °F)
• Storage temperature: -15 °C to 80 °C (5 °F to 176 °F)
• Relative humidity: 0 to 95%, non-condensing
• Maximum altitude: 2000 m (6562 ft)
• Enclosure: NEMA 4X/IP65 front
Standards and Approvals:
• CE, UL listed
• Immunity: EN50082-2
• Emissions: EN55011
• Safety: EN61010
• Manufactured under ISO 9001 for Quality, ISO 14001 for
Environmental Management and OHSAS 18001 for
Occupational Health and Safety.
China RoHS (Go to www.gfsignet.com for details)
Declaration of Conformity according to FCC Part 15
This device complies with Part 15 of the FCC rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and,
(2) This device must accept any interference received, including
interference that may cause undesired operation.
2. Specifications
Dimensions
3-8250.090-2 Rev. H 01/13 English
3-8250.090-2
6. View menu
7. Editing procedure
8. Calibrate menu
9. Options menu
10. Troubleshooting
92 mm
(3.6 in.)
97 mm
(3.8 in.)
56 mm
(2.2 in.)
41 mm
(1.6 in.)
Optional
Rear
Cover
96 mm
(3.8 in.)
96 mm
(3.8 in.)
106 mm
(4.18 in.)
82 mm
(3.23 in.)
SIDE VIEW
Field Mount w/
8052 Integral kit
107 mm
(4.2 in.)
96 mm
(3.8 in.)
Panel Mount
SIDE VIEW
FRONT VIEW
Field Mount &
Panel Mount
SIDE VIEW
Field Mount w/
8050 Universal base

2 Signet 8250-2 Level Transmitter
Terminals 5-10: Relay Outputs
Two sets mechanical SPDT contacts programmable as:
• High or Low setpoint with adjustable hysteresis
• "Window" limits with adjustable hysteresis
• Time delay up to 6400 seconds.
• May be disabled (Off) if not used.
• Auxiliary power (terminals 1-2) MUST be connected
for relay operation
Terminals 1 and 2: AUXILIARY power
Required for all systems that include relay
operation.
4
3
2
1
13
12
11
10
9
8
7
6
5
AUX
Power +
Sensr Gnd
(SHIELD)
Sensr IN
(RED)
Sensr V+
(BLACK)
Relay 2
(NO)
Relay 2
(COM)
Relay 2
(NC)
Relay 1
(NO)
Relay 1
(COM)
Relay 1
(NC)
System Pwr
Loop -
System Pwr
Loop +
AUX
Power -
3. Panel Installation
1. The panel mount transmitter is designed for installation using a 1/4 DIN Punch. For
manual panel cutout, an adhesive template is provided as an installation guide. The
cutout must be 92 mm x 92 mm. Recommended clearance on all sides between
instruments is 25 mm (1 in.)
2. Slide the instrument into the cutout from the front of the panel.
3. Slide the mounting bracket over back of instrument until quick-clips snap into latches on
side of instrument.
4. To remove, secure instrument temporarily with tape from front or grip from rear of
instrument. DO NOT RELEASE.
5. Press quick-clips outward and remove.
2
1
Terminals 11-13: Digital (S3L)
The 2450 sensor and External Relay
Module connect here.
System Pwr
Loop -
System Pwr
Loop +
2
1
Sensr Gnd
(SHIELD)
Sensr IN
(RED)
Sensr V+
(BLACK)
7
6
5
4
3
AUX
Power -
AUX
Power +
13
12
11
Relay 2
(NO)
Relay 2
(NC)
10
9
8
Relay 2
(COM)
Relay 1
(NO)
Relay 1
(NC)
Relay 1
(COM)
quick-clips
gasket panel
terminals mounting
bracket
latch
Panel Mount
Installation Detail
4. Electrical Connections
CAUTION: Failure to fully open terminal jaws before removing wire may permanently damage instrument.
Wiring Procedure
1. Remove 13 mm - 16 mm (0.5 in. - 0.625 in.) of insulation from wire end.
2. Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
3. Insert exposed (non-insulated) wire end in terminal hole until it bottoms out.
4. Release orange terminal lever to secure wire in place. Gently pull on each wire to ensure a good connection.
Wiring Removal Procedure
1. Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
2. When fully open, remove wire from terminal.
Terminals 3 and 4: Loop Power
12-24 VDC ±10% system power
and current loop output.
Max. loop impedance:
50 Ωmax. @ 12 V
325 Ωmax. @ 18 V
600 Ωmax. @ 24 V

3Signet 8250-2 Level Transmitter
4.2 Serial Data Connections
• The Input/Output terminals on the 8250 carry S3L serial data from the 2450 Pressure Sensor or from the 2250 Level Sensor and
from the External Relay Module.
• You MUST reset sensor configuration (see Calibrate menu) for all new systems and after connecting a new sensor or relay module
to the I/O terminals.
• Do not route sensor or output cables in conduit containing AC power wiring. Electrical noise may interfere with sensor signal.
• Routing cable in grounded metal conduit will help prevent electrical noise and mechanical damage.
• Seal cable entry points to prevent moisture damage.
• Only one wire should be inserted into a terminal. Splice double wires outside the terminal.
• The TOTAL cable length from I/O devices to the transmitter must not exceed 122 m (400 ft.).
• For best performance, ground the sensor SHIELD wire to a local earth ground at a point near the sensor.
• Consult the sensor manual for additional wiring information.
4.1 System Power/Loop Connections
-
+
4
3
2
1
4
3
2
1
-
+
4
3
2
1
+
-
+
-
-
+
4
3
2
1
4
3
2
1
4
3
2
1
+
-
-
+
-
+
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
Channel 1
4 to 20 mA in
Channel 2
4 to 20 mA in
System Pwr Loop -
System Pwr Loop +
AUX Power -
AUX Power +
System Pwr Loop -
System Pwr Loop +
AUX Power -
AUX Power +
Loop Input
4 to 20 mA
System Pwr Loop -
System Pwr Loop +
AUX Power -
AUX Power +
Loop Input
4 to 20 mA
System Pwr Loop -
System Pwr Loop +
AUX Power -
AUX Power +
System Pwr Loop -
System Pwr Loop +
AUX Power -
AUX Power +
Example: Two transmitters connected to PLC/Recorder with separate power supply
PLC or Recorder
Transmitter 1
Terminals Transmitter 2
Terminals
Power
Supply
12 to 24 VDC
* See AUX POWER Note
Connection to a PLC with built-in power supply
Internal
PLC
Connection
Power
Supply
12 to 24 VDC
PLC Terminals
Transmitter
Terminals
* See AUX POWER Note
Connection to a PLC/Recorder, separate supply
PLC or Recorder
Transmitter
Terminals
Power
Supply
12 to 24 VDC
* See AUX POWER Note
Stand-alone application, no current loop used
Transmitter
Terminals
Power
Supply
12 to 24 VDC
* See AUX POWER Note
Note:
AUXILIARY power is required to operate the relays.
13
12
11
8059 External
Relay Module
2450 Pressure Sensor
8250 I/O
TerminalsShield (Gnd)
Red (I/O)
Black (V+)
The TOTAL cable length connected to the 8250
input/output terminals must not exceed 122 m (400 ft)
The External Relay Module provides
“Pass-Thru” terminals to connect the
sensor in series via S
3
L.
2250 Level Sensor
OR

4 Signet 8250-2 Level Transmitter
Zero reference point (Z):
The point in the vessel where you want the 8250 to display zero
(0 ft., 0 gal. etc).
• If Z is located below the fluid surface, the 8250 will display
a positive level measurement.
• If Z is located above the fluid surface, the 8250 will display
a negative level measurement.
Sensor Location point (SLoc):
The point on the level sensor where the measurement is taken.
• The 2450 Pressure sensor measures from the centerline of
the diaphragm.
Offset (O):
The distance from Z to SLoc.
• Enter a positive value in the Calibrate menu if the sensor is
located above Z.
• Enter a negative value in the Calibrate menu if the sensor
is located below Z.
• Enter 0 in the Calibrate menu if the sensor is located at Z.
Level (L):
The distance from Z to surface of fluid (displayed as "Level"
by transmitter).
L> 0
O> 0
Z
SLOC
L> 0
O< 0 Z
SLOC
L < 0
SLOC
O< 0
Z
2450 Pressure Sensor Location and Offset
Z
Z
For horizontal cylinders only, the
zero reference point MUST be
the lowest point in the vessel.
For most vessels, the zero
reference point may be
designated as any height
in the vessel.
5. System Configuration
The 8250 Level Transmitter must be programmed using the following system configuration procedure.
1. Determine where you want the level measurement to start. This is the Zero reference point (Z).
Review the diagram to help select the best option.
2. Determine where you will mount the sensor. This is SLoc.
Consult the Sensor manual for information regarding the best location for the sensor.
3. Measure the distance between Z and SLoc. This is O(ffset).
4. Enter the Offset into the Calibrate menu.

5Signet 8250-2 Level Transmitter
Custom point #10 3000 gal.
Custom point #1 0 gal.
Custom point #2 45 gal.
Custom point #3 118 gal.
Custom point #4 160 gal.
Custom point #5 250 gal.
Custom point #9 1300 gal.
Custom point #6 380 gal.
Custom point #7 700 gal.
Custom point #8 1000 gal.
If Custom Shape is selected in the Options menu, you can define
from two to ten Custom Points to establish the relationship of
level to volume in the vessel.
• Select Manual level Measurement mode to edit both level and
volume data (dry configuration).
• Select Automatic level Measurement mode to accept the
sensor measurement of the Level, while you assign a
volumetric value to each custom point (wet configuration).
• Enter from 3 to 10 custom points to link level and volume
values.
• The first custom point must be the lowest fluid level in the
vessel. Each successive point must be greater than the
preceding point.
• The last point must be equal to or greater than the highest
fluid level in the vessel.
• A custom point should be located at each transition point in
the vessel shape (for example, at custom point #9, where the
shape changes from a cylinder to a cone).
• The more complex sections should be defined with more
points. Notice that the conical section of the illustration has
been defined by custom points 1 through 9.
• Simpler sections require fewer defining points. Note that the
cylinder requires only custom points 9 and 10.
r
h
A
Length
5.2 Reference
5.1 Level and Volume Conversion in Custom Shaped Vessels
Pressure to level conversion:
Level = P ÷ (SG × D)
where P = Pressure
SG = Specific Gravity of fluid
D
= Density of water
With pressure in psi:
Level (meters) = 0.703069 × (P/SG)
With pressure in bar:
Level (meters) = 1.019715 × (P/SG)
Mass Conversion
m = D × SG × V
where m = mass of fluid
D = density of water = 1000 kg/m3
SG = Specific Gravity of fluid
V = Volume of fluid (m3)
m (kg) = 1000 × SG × V
Horizontal cylinder:
V = A × L
where A = area of segment
L = length of vessel
Level, volume and mass calculations performed by the 8250
include:
Vertical cylinder:
V = π× r2 × h
where r = radius of cylinder
h = height of fluid
Rectangular vessel:
V = w × L × h
where w = width
L = length
h = height
Volume Calculations
where r = radius of vessel
h = height of segment
()
⎥
⎦
⎤
⎢
⎣
⎡−×
⎟
⎟
⎠
⎞
⎜
⎜
⎝
⎛−−
⎟
⎠
⎞
⎜
⎝
⎛−
××= −2cos 12 hrhhr
r
hr
rA 2

6 Signet 8250-2 Level Transmitter
5.3 Relay Operation
Relay outputs can be used as switches that respond when the
process variables move above or below setpoints, or when the
process variables move outside of a window.
• The relays may be turned Off if not in use.
• Response can be delayed up to 6400 s ( see Calibrate menu).
Low:
Relay is energized when process variable is less than the
setpoint. The relay de-energizes when the process variable
moves above the setpoint plus the hysteresis value.
High:
Relay is energized when process variable is greater than the
setpoint. The relay de-energizes when the process variable
moves below the setpoint plus the hysteresis value.
Window:
Relay is energized when the process variable moves above or
below a fixed window of values. The relay de-energizes when
the process variable moves inside the window by more than the
hysteresis value.
Note: Relays will operate in reverse if miswired. Observe relay
logic appropriate to the application.
6. VIEW Menu
• During normal operation, the ProcessPro displays the VIEW menu.
• To select a display, press the UP or DOWN arrow keys. The display selections scroll in a continuous loop.
• Changing the display selection does not interrupt system operations.
• No keycode is necessary to change display selection.
• Output settings cannot be edited from the VIEW menu.
• When using the CALIBRATE or OPTIONS menus, the ProcessPro will return to the VIEW menu if no key
is pressed for 10 minutes.
View Menu
Signet Level
Transmitter
Level
+10.00 ft
Relay 1 Relay 2
ENTER
Window
High Limit Hysteresis
Hysteresis
Time
Low Limit
Process
Hysteresis
Time
Low Setpoint
Process
Relay energized
Relay de-energized
Hysteresis
Time
High Setpoint
Process
Display Description
Level
+10.00 ft
Displays the Level value.
Permanent display when "Level" is the display selection in OPTIONS menu.
Volume
+30.00 gal
Displays the Volume value.
Permanent display when "Volume" is the display selection in OPTIONS menu.
LVL +10.00 ft
VOL +300.00 gal
Displays the Level and Volume simultaneously.
Permanent display when "Both" is the display selection in OPTIONS menu.
All of the displays below are temporary. After 10 minutes the display returns to the permanent display.
Loop Output:
12.00 mA Monitor the 4 to 20 mA Loop output.
Relay A: On
Relay B: Off
Displays the status of Relays A and B.
Appears only when external relay module is detected.
No Relay Module
Detected
Displayed if the relay module is not detected at Sensor Configuration (see
calibrate menu)
Note: When using the 8059-4 or -4AC, only relays 1 and 2 can be utilized with the level instrument.
Last CAL:
02-10-09
Monitor date for scheduled maintenance or date of last calibration.
(See description in Calibrate Menu.)

7Signet 8250-2 Level Transmitter
Relay 1 Setpnt:
+10.000 ft
Relay 1 Setpnt:
+00.000 ft
ENTER
Relay 1 Setpnt:
+00.000 ft
Relay 1 Setpnt:
+09.000 ft
Relay 1 Setpnt:
Saving
Relay 1 Setpnt:
+9.0000 ft >
Notes on Steps 5 and 6:
• All output functions remain active during editing.
• Only the flashing element can be edited.
• RIGHT ARROW key advances the flashing element in a continuous loop.
• Edited value is effective immediately after pressing ENTER key.
• If no key is pressed for 10 minutes unit will restore the last saved value and return to step 3.
• Step 6 (pressing ENTER key) always returns you to Step 3.
• Repeat steps 3-6 until all editing is completed.
Notes on Step 2:
If no key is pressed for 5 minutes while display is showing "Enter
Key Code", the display will return to the VIEW menu.
Notes on Steps 3 and 4:
• Refer to pages 8-10 for complete listing of menu items and their use.
• From the Step 3 display, pressing the UP and DOWN keys simultaneously will
return the display to the VIEW menu.
• If no key is pressed for 10 minutes, display will also return to the VIEW menu.
7. ProcessPro Editing Procedure:
Step 1. Press and hold ENTER key:
• 2 seconds to select the CALIBRATE menu
• 5 seconds to select the OPTIONS menu.
Step 2. The Key Code is UP-UP-UP-DOWN keys in sequence.
• After entering the Key Code, the display will show the first item in the selected menu.
Step 3. Scroll menu with UP or DOWN arrow keys.
Step 4. Press RIGHT ARROW key to select menu item to be edited.
• The first display element will begin flashing.
Step 5. Press UP or DOWN keys to edit the flashing element.
• RIGHT ARROW key advances the flashing element.
Step 6. Press ENTER key to save the new setting and return to Step 3.
2s 5s
ENTER
OPTIONS
CALIBRATE
VIEW
Press &
hold for
access:
Step 5
Step 6
Notes on Step 1:
• The View Menu is normally displayed.
• The CALIBRATE and OPTIONS menus require a KEY CODE.
Step 4
First item in CALI-
BRATE menu
Step 3
Step 3: Finished Editing?
Press the UP and DOWN keys simultaneously after
saving the last setting to return to normal operation.
Press the UP and DOWN keys simultaneously
while any element is flashing. This will recall the
last saved value of the item being edited and
return you to Step 3.
Step 5: Made an Error?
CALIBRATE: ----
Enter Key Code
CALIBRATE: *---
Enter Key Code
CALIBRATE: **--
Enter Key Code
CALIBRATE: ***-
Enter Key Code
ft >
LVL Units:
ft >
LVL Units:
Relay 1 Setpnt:
+10.000 ft >

8 Signet 8250-2 Level Transmitter
8. Calibrate Menu
Display
(Factory settings shown) Description
LVL Units:
ft > Select the units of measure: ft, in, m,cm.
Show LVL in %:
No >
Yes: Level will be displayed as a percentage of the full scale.
No: Level will be displayed as engineering units.
LVL 100%:
+0.0000 ft >
If "Show LVL in %" is YES, enter the full scale value. The units are the same as LVL Units.
Sensor Offset:
+0.0000 ft >
Enter the distance from SLOC to Z in the vessel.
Enter +if the sensor is located above Z.
Enter -if the sensor is located below Z.
VOL Units:
gal > Select the units of measure for Volume: gal, ft3, in3, m3, kg, lb, or lit (liters)
Show VOL in %:
No >
Yes: Volume will be displayed as a percentage of the full scale.
No: Volume will be displayed as engineering units.
VOL 100%:
+0.0000 gal > If "Show VOL in %" is YES, enter the full scale value. The units are the same as VOL Units
Spec Gravity:
1.0000 >
Enter the specific gravity of the fluid. Factory setting is 1 (water)
This setting is required only if the level measurement is made by a pressure sensor
(Signet 2450), or if volume units are selected ( kg or lb )
Set LVL:
>
Single-point calibration for Level.
Reset LVL
to Factory Cal: >
Yes: Reset Level to original factory calibration. ("Set LVL" entry is erased.)
No: Return to menu, do not reset Level.
Loop Source:
LVL > Select the source for the 4-20 mA Loop: LVL or VOL.
Loop Rng: ft
+0.0000 →+10.000 > Select the minimum and maximum values for the 4-20 mA Current loop output.
Relay 1 Mode:
Off >
Select the mode of operation for Relay Output: Low, High, or Window.
The relay may be disabled (Off) if not in use.
Reset Sensor
Configuration: >
Use this function during initial startup of a new system, and whenever a new sensor is added
to the system. It enables the 8250 to scan the sensor input terminals and determine the type
and specific serial numbers of the sensors connected to the sensor input.
Technical Note
If you see this error The most likely cause is Remedy
Too Much Error
Check Sensor
A new sensor was connected to the 8250
but the "Sensor Reset Configuration" has
not been executed.
Perform the sensor configuration.
*
*
IMPORTANT TECHNICAL ADVICE. DO THIS FIRST!
Before proceeding with the calibration, press the UP key twice, then press the RIGHT key to restore the function of the configuration of
the sensor (sensor configuration RESET). This procedure is part of the sensor 8250 and provides for many calibration functions.

9Signet 8250-2 Level Transmitter
8. Calibrate Menu (continued)
Display
(Factory settings shown) Description
The Relay settings below will not appear if the Relay mode is OFF.
Relay 1 Source:
LVL > Select the source for Relay: LVL or VOL.
Relay 1 Setpnt:
+0.0000 ft >
If Relay is in Low or High mode, the relay will be energized when the level or volume reaches
this value.
Relay 1 Rng: ft
+0.0000 →+10.000 >
If Relay is in Window mode, the relay will be energized when the level or volume is less than
(low limit) or greater than (hig limit) the range. You must enter the low limit into the first field,
and the high limit into the second field.
Relay 1 Hys:
0.00 ft >
Relay will be de-energized at Setpoint ± Hysteresis.
The Hysteresis value is in Level units or % of full scale.
Relay 1 Delay:
0.0 secs >
Set up to 6400 seconds delay time for relay response.
Relay will be activated only if the source value exceeds the setpoint for this time period.
• Relay settings will repeat for Relay #2 and for External Relays.
• External Relays require the optional External Relay Module (model number 3-8059-4 or 3-8059-4AC).
• Note: When using the 8059-4 or -4AC, only relays 1 and 2 can be utilized with the flow instrument.
Reset Sensor
Configuration: >
Use this function during initial startup of a new system, and whenever a new sensor is added
to the system. It enables the 8250 to scan the sensor input terminals and determine the type
and specific serial numbers of the sensors connected to the sensor input.
Last CAL:
2-10-09
Use this “note pad” to record important dates, such as annual recertification or scheduled
maintenance.
Technical Note
If you see this error
during normal operation The most likely cause is Remedy
CHK SENSOR A new sensor was connected to the 8250
but the "Sensor Reset Configuration" has
not been executed.
Perform the sensor configuration.
*

10 Signet 8250-2 Level Transmitter
9. Options Menu
• The following entries are used by the 8250 to convert the level into volumetric and mass measurements. The accuracy of
the entries entered will determine the accuracy of the volumetric and mass calculation. Refer to section 5 for additional
information.
Display
(Factory settings shown) Description
Contrast:
3 >
Adjust the LCD contrast for best viewing. A setting of 1 is lowest contrast, 5 is highest. Select
lower contrast if the display is in warmer ambient surroundings.
Display Option:
Level >
Select Level, Volume or Both.
This setting will determine the permanent display selection.
Averaging
Off >
OFF provides the quickest output response to changes in level or volume. Longer averaging
period produces more stable display and output response.
Decimal
*****. >
Set the decimal to the best resolution for your application. The display will automatically scale
up to this resolution. Select *****., ****.*, ***.**, **.*** or *.****
Loop Adjust
4.00 mA >
Adjust the minimum and maximum current output. Use this setting to match the system output
to any external device. The display value represents the precise current output.
Adjustment limits:
• 3.80 mA < 4.00 mA > 5.00 mA
• 19.00 mA < 20.00 mA > 21.00 mA
Loop Adjust
20.00 mA >
Test Loop:
>
Press UP or DOWN keys to manually order any output current value from 3.6 mA to
21.00 mA to test current loop output.
Test Relay 1:
>
Press UP or DOWN keys to manually toggle the state of Relay 1.
Display
(Factory settings shown) Description
VOL Shape:
Vert Cylinder >
Select the shape of the vessel where Sensor is located:
Vert Cylinder, Horiz Cylinder, Rectangular or Custom shape.
VOL Diameter:
0.0000 ft >
If Vert Cylinder or Horiz Cylinder is selected: Set the diameter of the cylinder.
The unit of measure is set by "LVL Units" in Calibrate menu.
VOL Length:
0.0000 ft >
If Horizontal Cylinder or Rectangular shape is selected: Set the length of the vessel.
The unit of measure is set by "LVL Units" in Calibrate menu.
VOL Width:
0.0000 ft >
If Rectangular shape is selected: Set the width of the vessel.
The unit of measure is set by "LVL Units" in Calibrate menu.
Number of Custom
Points: 10 >
If Custom shape is selected: enter the number of measurement points to be used to define
the vessel shape. Minimum 3 points, maximum 10 points.
LVL Measurement:
Manual >
If Custom shape is selected: select Manual or Automatic level measurement.
Manual allows you to edit both the Level measurement and the Volume measurement.
Automatic allows you to edit only the Volume measurement (while displaying Level value)
P01: +0.0000 ft
V: +0.0000 gal >
Set the Volume (and Level if manual measurement is selected) at each custom point in your
vessel.
• Relay settings will repeat for Relay #2 and for External Relays.
• External Relays require the optional External Relay Module (model number 3-8059-4 or 3-8059-4AC).
• Note: When using the 8059-4 or -4AC, only relays 1 and 2 can be utilized with the flow instrument.

11Signet 8250-2 Level Transmitter
10. Troubleshooting
Display Condition Possible Causes Suggested Solutions
Value must be 6400 or less Time delay cannot be greater than 6400 s. Set time delay to 6400 s or less.
Value must be more than zero Specific gravity value set to 0.0000 Set specific gravity to a value greater than 0.
Must have more than 1 point
Must have 10 or less points
Custom Shape requires from 3 to 10
custom points. Enter 3 to 10 custom points.
Must be > than previous point
A custom point has been entered that is not
greater than the previous point.
(Custom points must be in ascending
order.)
Reset the custom point to a value greater
than the preceding point.
CustomTable Error
Number of custom points increased without
setting new values so all custom points are
not sequential.
Review all custom points and reset values
so each point is greater than the preceding
point.
CHK SENSOR Problem with the sensor during different
modes of operation:
1. Wiring problem:
• AUXILIARY POWER was not
connected when LOOP power started.
• The sensor is not connected properly.
• The sensor cable is detached.
2. The sensor has not been configured.
3. The sensor is defective.
1. Start AUX power, then LOOP power.
2. Check sensor wiring.
3. Perform SENSOR CONFIGURATION in
CALIBRATE menu.
4. Replace the sensor, then perform
SENSOR CONFIGURATION.
Too Much Error
Check Sensor
0 SENR(S) FOUND: SAVE ?
No Relay Module Found
• External Relay Module wiring is loose.
• Relay module has been disconnected.
• Relay module has been replaced.
• Relay module is defective.
1. Check wiring
2. Reset SENSOR CONFIGURATION
3. Replace External Relay Module.
• External Relays require the optional External Relay Module (model number 3-8059-4 or 3-8059-4AC).
• Note: When using the 8059-4 or -4AC, only relays 1 and 2 can be utilized with the flow instrument.

Georg Fischer Signet LLC, 3401 Aero Jet Avenue, El Monte, CA 91731-2882 U.S.A. • Tel. (626) 571-2770 • Fax (626) 573-2057
For Worldwide Sales and Service, visit our website: www.gfsignet.com • or call (in the U.S.): (800) 854-4090
For the most up-to-date information, please refer to our website at www.gfsignet.com
3-8250.090-2 Rev. H 01/13 English © Georg Fischer Signet LLC 2013
Ordering Information
Mfr. Part No. Code Description
3-8250-2 159 000 766 Level Transmitter, Field Mount
3-8250-2P 159 000 767 Level Transmitter, Panel Mount
3-8059-4 159 000 772 External 4-Relay Module
3-8059-4AC 159 000 773 External 4-Relay Module with Power Supply
Note: When using the 8059-4 or 8059-4AC, only relays 1 and 2 can be utilized with the flow instrument.
Accessories
Mfr. Part No. Code Description
3-8050 159 000 184 Universal mounting kit
3-8050.395 159 000 186 NEMA 4X Back Cover
3-8052 159 000 188 3/4” Integral mounting kit
3-8050.396 159 000 617 RC Filter Kit (for relay use), 2 per kit
3-0000.596 159 000 641 Heavy Duty Wall Mount Bracket
3-9000.392 159 000 368 Liquid-tight connector kit, 3 sets, 1/2 in. NPT5
3-9000.392-1 159 000 839 Liquid-tight connector kit, 1 set, 1/2 in. NPT5
3-9000.392-2 159 000 841 Liquid-tight connector kit, 1 set, PG 13.5
7300-7524 159 000 687 7.5W 24V Power Supply
7300-1524 159 000 688 15W 24V Power Supply
7300-3024 159 000 689 30W 24V Power Supply
7300-5024 159 000 690 50W 24V Power Supply
7300-1024 159 000 691 100W 24V Power Supply
This manual suits for next models
2
Table of contents
Other GF Transmitter manuals