01 02
1 Safety and warning
There is a risk of injury due to
improperly handle the device.
Component of product can be
recycled
Danger of high voltage and electric
shock.
This surface is upward, and it should
not be tilted and upended.
Danger of hot surface! Do not touch
the hot surface when the device is
running.
No more than four (4) identical
packages be stacked on each other
CE mark.
The package/product should be
handled carefully and never be
tipped over or slung.
Product should not be posed as
normal house hold waste.
Keep Dry
This symbol indicates that you
should wait at least 5mins after
disconnecting
the utility grid and from the PV
panel before touching any
the inverter from
inner live parts.
This manual contains important instructions for MT series inverter that shall be followed during installation and
maintenance of the inverter.
The MT series for Four-MPPT, Three-Phase solar inverter without transformer, which consists of GW50K-MT, GW60K-MT,
and GW75KHV-MT model type.
MT Series have been designed and tested strictly according to the international safety regulation. As electrical and
electronic equipment, safety instructions related to them must be complied with during installation, commissioning,
operation and maintenance. Incorrect or work may result in damage to:
1. The life and well-being of the operator or a third party.
2. The inverter and other properties that belong to the operator or a third party, Therefore the flowing safety instructions
must be read and always kept in mind prior to any work. All detailed work-related safety warnings and notes will be
specified at the critical points in corresponding chapter.
All installation and electrical work must only be performed by qualified personnel. They have:
• Been trained specially;
• Already completely read through and understood the manual and related documents.
• Be familiar with safety requirements for electrical systems.
The inverter must be installed and maintained by professionals in compliance with local electrical standards regulations
and the requirements of local power authorities or companies.
• There is a risk of injury due to improperly handing device.
• Always follow the instructions contained in the manual when moving or positioning the inverter.
• The weight of the equipment can cause injuries, serious wounds or bruise if improperly handled.
• Please install it in the place beyond children’s reach.
• Prior to installing and maintaining the inverter, it is crucial to make certain that the inverter in not electrically connected.
4
•
disconnect the connection between the DC input and the inverter, you should wait at least 5mins after these disconnection
in case of electric shock.
• All cables must be firmly attached, undamaged, properly insulated, and adequately dimensioned.
• The temperature of some parts of the inverter may exceed 60℃ during operation. To avoid being burnt, do not touch the
inverter during operation. Let it cool before touching it.
• Without permission, It is not allowed to open the front cover of the inverter. Users should not touch/replace any
components of the inverter except the DC/AC connectors. GOODWE will not bear any consequences caused by
unauthorized actions which will lead to potential injury to people and damage to inverters.
• Static electricity may damage electronic components. Appropriate method must be adopted to prevent such damage to
the inverter; otherwise the inverter may be damaged and the warranty will be annulled.
• Ensure that the output voltage of the proposed PV array is lower than the maximum rated input voltage of the inverter;
otherwise the inverter may be damaged and the warranty will be annulled.
• If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
• When exposed to sunlight, the PV array will generate very high voltage which can cause electrical shock hazard. Please
strictly follow the instruction we provided.
• PV modules should have an IEC61730 class A rating.
• Prohibit inserting or pulling the AC or DC terminals when the inverter is working. Or the inverter will be destroyed.
Only DC connectors provided by GoodWe are permitted to use, otherwise the inverter may be damaged and the warranty
will be annulled.
Before maintaining the inverter, disconnect the connection between the AC grid and the inverter firstly, and then
2.1 Intended usage
2 Product introduction
The MT series which is a Four MPPT, three phase transformer-less grid-connected inverter is a crucial unit between the PV
string and the utility grid in the PV power system.
Inverter is dedicated to converting directing current generated by the PV modular into alternating current, which
conforms to parameters to local utility grid and fed it into the utility grid. The intended usage of inverter is illustrated in
figure .2.1-1
kW.H
Figure 2.1-1
A B C D
Refer to the operating instructions
● The inverter can exclude the possibility of DC residual currents to 6mA in the system,Where an external RCD is required in addition
to the built-in RCMU, type A RCD must be used to avoid tripping。
● The default photovoltaic module is not grounded.
● If there are more than 3 PV strings on input side, an additional fuse installing will be suggested.