Haes ESENTO MARINE Guide

Installation, Commissioning &
Operating Manual
MARINE APPROVED 2 - 4 ZONE CONVENTIONAL
CONTROL PANEL
Approved Document UI-ESEN4MAR-01 Issue 6.0
MED Ref: 0832/15

IMPORTANT NOTE
PLEASE READ THIS MANUAL BEFORE HANDLING THE EQUIPMENT AND
OBSERVE ALL ADVICE GIVEN IN IT
THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID
E.S.D
The panel is safe to operate provided it has been installed in compliance with the manufacturer’s instructions
and used in accordance with this manual.
Hazardous voltages are present inside the panel—DO NOT open it unless you are qualied and authorised
to do so. There is no need to open the panel’s enclosure except to carry out commissioning, maintenance
and remedial work. This work must only be carried out by competent service personnel who are fully
conversant with the contents of the panel’s installation manual and have the necessary skills for maintaining
this equipment.
This re alarm system requires periodic checks as specied in BS 5839 Part 1 It is the responsibility of the
system user to ensure it is regularly serviced and maintained in good working order.
Disclaimer
No responsibility can be accepted by the manufacturer or distributors of this re alarm panel for any
misinterpretation of an instruction or guidance note or for the compliance of the system as a whole. The
manufacturer’s policy is one of continuous improvement and we reserve the right to make changes to
product specications at our discretion and without prior notice. E & O E.
IMPORTANT SAFETY NOTES
Haes Technologies Ltd, Unit 3, Horton Industrial Park, West Drayton, UB7 8JD
Model Number MED Ref No.
Esento Marine 2-4 zone conventional panel ESEN-2MAR/4MAR 0832-MED-1086
European Standard EN54-2 : 1997 + A1 : 2006
Control and indicating equipment for re detection and re alarm systems for buildings.
Provided Options (with requirements):
Output to re alarm devices, dependency type ‘A’, test condition
European Standard EN54-4 : 1997 + A1 : 2002 + A2 : 2006
Power supply equipment for re detection and re alarm systems for buildings.
European Standard BS IEC60092-504 : 2001
Electrical installations in ships, special features, control and instrumentation.
European Standard BS IEC60533 : 1999
Electrical and electronic installations in ships, electromagnetic compatibility.
ATTENTION

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0
1
CONTENTS
Page
ABOUT THIS PANEL 2
PRODUCT OVERVIEW 2
CABINET DETAILS 3
CIRCUIT BOARDS 4
MAIN PCB TERMINALS 5
TECHNICAL SPECIFICATION 6
POWER SUPPLY MODULE 7
DESIGN CONSIDERATIONS 8
GENERAL DETECTION CIRCUIT WIRIING SCHEMATIC 8
GENERAL SOUNDER CIRCUIT WIRIING SCHEMATIC 9
INSTALLATION 10
SAFETY 10
ESD PRECAUTIONS 11
GENERAL 11
MOUNTING THE CABINET 11
MAINS CONNECTIONS 12
CONNECTING THE BATTERIES 13
EARTH FAULT MONITORING 13
SETUP & PROGRAMMING 14
LEVEL 3 ENGINEERING OPTIONS 14
ZONE INTERFACE FUNCTION 21
OPERATING 22
PANEL CONTROLS & INDICATIONS 24
DISABLE MODE 24
TEST MODE 25
FAULT DIAGNOSIS 26
FUNCTIONALITY DURING A SYSTEM FAULT 27
USER INSTRUCTIONS 27
SERVICE & MAINTENANCE 28
THE NEED FOR MAINTENANCE 28
DUTIES OF THE RESPONSIBLE PERSON 28
ROUTINE MAINTENANCE & TESTING 28
SCHEDULE OF TESTING LOG BOOK 30
FALSE ALARMS, FAULTS & ENGINEER VISIT LOG BOOK 36

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0
2
ABOUT THIS PANEL
PRODUCT OVERVIEW
The Esento Marine 2 or 4 zone is a conventional control panel with integral power supply & space for
standby batteries.
Esento Marine panels are fully approved to European standards EN54-2 & 4, Fire Detection and Alarm
Systems – Control & Indicating Equipment.
The control panel comprises of a sheet steel enclosure suitable for wall mounting with a hinged, lockable
front access door. It can be semi recessed, using a suitable recessing bezel. Cable entry is via 20mm
‘knockouts’ located at the top and rear of the cabinet.
An eight button keypad is used to control the system and allow access to the function options. The three
main buttons, ‘RESOUND’ (red), ‘SILENCE’ (blue) and ‘RESET’ (green) being much larger and colour
coded to assist the end users.
Two or four re zone circuits are provided plus two monitored sounder circuits. Fire & Fault VFCO relays,
Fire & Fault switched negative outputs, class change and an alert input are also included.
The panels are supplied with a 1.5 amp internal power supply module. This module complies with the
requirements of EN54-4 : 1988 and provides temperature compensated battery management charging.
Quiesecent and alarm current details for standby battery calculations
Model Standby Current Alarm Current
ESEN-2MAR 75mA 116mA
ESEN-4MAR 85mA 133mA

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0
3
ABOUT THIS PANEL
CABINET
Fire Detection System
57mm 80mm
260mm
308mm
250mm
300mm

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0
4
ABOUT THIS PANEL
CIRCUIT BOARDS
Esento Marine 2-4 zone panels comprise of two circuit boards
PSU
@ + +
- - + -
+ -
+ - + - + - + - + -
28V 0V
C NC NO C NC NO
FIRE FAULT FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
1 2 3
ON
1 2 3 4 ENTER
RESOUND SILENCE RESET
TPCA01-E2MAR/E4MAR - 2 or 4 zone Master PCB
TPCA02 - LED Display & Controls PCB

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0
5
ABOUT THIS PANEL
MAIN PCB TERMINALS
PSU
@ + +
- - + -
+ -
+ - + - + - + - + -
28V 0V
C NC NO C NC NO
FIRE FAULT FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
1 2 3
ON
28v output fused @ 500mA
28v input for power supply
Temperature compensation voltage control link
Commmon re VFCO relay
unfused. Max 3A @ 30vdc
Commmon fault VFCO relay
maintained (fail safe) unfused.
Max 3A @ 30vdc
Common re O/P
Common fault O/P
Alert (pulses sounders)
Precint/class change (activates sounders)
Switched -ve inputs
Switched -ve outputs
Max load 40mA
To 0 volts
Relay Coil
Conventional monitored
sounder circuits, fused @ 500mA
Conventional re zone circuits, fused @ 500mA

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0
6
ABOUT THIS PANEL
General Specication
Enclosure Steel IP30. Epoxy powder coated Interpon Radon, silver grey
Temperature range -5 deg C to +55 deg C max RH 95%
Vibration IEC 60068-2-6 Test F
Inclination IEC 60092-501 22.5o
Number of conventional detection circuits 2 or 4
Detector compatibility Apollo: S65, Orbis. / Hochiki CDX. / Nittan EV
TECHNICAL SPECIFICATION
Electrical Specication Inputs & Outputs - TPCA01-H2/H4
Cabling Fire resistant screened cable, minimum
size 1mm2. Max cable length 1Km (20
Ohm). FireBurn, FP200 or equivalent
(max capacitance 1uF, max inductance 1
millihenry).
Suitable cable glands must be used.
Terminal capacity 0.5mm2 to 2.5mm2solid or stranded wire.
PSU @ output Power supply voltage control line. For temperature compensation control.
PSU Input + - 28vdc supply input. Diode protected for
reversal and independent short circuit.
Max current 3 amps.
Max input current 3 amps. Input voltage
22vdc to 32vdc.
28v+, 0v- power output 28vdc supply output for re alarm
accessory relays etc. Max continuous
use = 400mA.
Fused @ 500mA. Fuse = 500mA
resettable fuse.
Common re relay Fire relay contact. Clean C/O.
Max 3A @ 30vdc
Unfused
Common fault relay Maintained fault relay contact. Clean
C/O. Max 3A @ 30vdc
Unfused
Outputs; FR, FLT Switched -ve voltage outputs for relay
control.
Overload voltage protected to 52vdc.
Current limited 680R. Max load = 40mA
Inputs; CC, PUL Switched -ve inputs, connect to 0v to
trigger. Max input voltage = 28vdc. Non
latching, max resistance 100R.
Protected via 10K Ohm impedance, 3v6
zener diode.
SNDR 1 - 2 28vdc polarity reversal monitored
sounder outputs to re alarm devices.
4K7 Ohm 5% 0.25W EOL resistor.
Monitoring current limit 28mA, fused @
500mA. Typical max load 22 devices @
18mA each per circuit. Ensure 0.9A is not
exceeded.
Zone 1 - 4 Fire alarm zone circuits. Conventionally
wired detection circuit. 4K7 Ohm 5%
0.25W EOL resistor.
Maximum detector load 3.5mA per zone,
Typical qty 40-50 Apollo marine optical
detectors, Note:- Max 32 detectors with
line continuity diode bases tted

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0
7
ABOUT THIS PANEL
POWER SUPPLY MODULE
Power Supply Specication
Mains supply 230vac +10% / -15% 50Hz max current
1A
Mains supply fuse 2 Amp (T2A 250V) Not accessible for servicing. Internal to
switch mode power unit
Internal power supply rating 1.5 Amps total including battery charging Maximum load shared between outputs
= 0.9A
Power supply output voltage 19.92 - 30.09vdc Tolerance +/- 0.1%
Max continuous load (ImaxA). Max
continuous load whilst battery charging
is not required (ImaxB).
ImaxA = 575mA ImaxB = ImaxA
Minimum current drawn by panel
(example)
4 Zone
I min = 85mA
2 Zone
I min = 75mA
Maximum ripple 1.0 V p-p Supply and charger fault monitored
Min/max battery size and type 2 x 3.2Ahr 12volt VRLA
Use Yuasa NP range batteries
Other equivalent batteries may be
used but have not been tested for the
purposes of EN54 approval.
Battery charging voltage 27.3 vdc nominal at 20 deg C Temperature compensated
Battery charging output current 1.5A PSU 630mA
Current limited 10 Ohms
Battery high impedance fault (Batt Hi Z) Resistance = 1 Ohm or greater 1 hour reporting time
Max current drawn from batteries 1.5 Amps with main power source
disconnected. Battery fuse 3A LBC
20mm.
V+
V-
E
N
L
24v +ve output
O/P Voltage adjust
(default setting 27v4 at 20oC)
24v -ve output
Earth
Neutral
Live
Mains input
Temperature compensation input
from @ terminal on main PCB

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0
8
DESIGN CONSIDERATIONS
TYPICAL DETECTION CIRCUIT SCHEMATIC

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0
9
DESIGN CONSIDERATIONS
TYPICAL SOUNDER CIRCUIT SCHEMATIC
4K7 OHM
END OF LINE
RESISTOR
-
+
SNDR1
MOTORISED BELL
POLARISED
MOTORISED BELL
POLARISED
ELECTRONIC SOUNDER
POLARISED
ELECTRONIC SOUNDER
POLARISED
+VE
+VE
+VE
+VE
-VE
-VE
-VE
-VE

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0
10
INSTALLATION
SAFETY
Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work Act 1974
to ensure as reasonably as is practical that the article will be safe and without risk to health when properly
used. An article is not regarded as properly used if it is used “without regard to any relevant information or
advice” relating to its use made available by the supplier.
It is assumed that the system, of which this control panel is a part, has been designed by a competent re
alarm system designer in accordance with IMO FSS Code and with regard to BS EN 54 parts 2 and 4 in
the case of control equipment and power supplies. Design drawings should be provided to clearly show
the position of any eld devices and ancillary equipment.
This product should be installed, commissioned and maintained by, or under the supervision of, competent
persons according to good engineering practice and,
(i) Codes of Practice
(ii) Statutory requirements
(iii) Any instructions specically advised by the manufacturer
According to the provisions of the Code you are therefore requested to take such steps as are necessary to
ensure that any appropriate information about this product is made available by you to anyone concerned
with its use.
This equipment is designed to be operated from 230V AC 50/60 Hz mains supplies and is of Class I
construction. As such it must be connected to a protective earthing conductor in the xed wiring of the
installation. Failure to ensure that all conductive accessible parts of this equipment are adequately bonded
to the protective earth will render the equipment unsafe.
This equipment must only be installed and maintained by a suitably skilled and technically
competent person.
THIS IS A PIECE OF CLASS 1 EQUIPMENT AND MUST BE EARTHED
These panels are designed to comply with the requirements of EN 54 part 2.
Installation of the panel should only be carried out by qualied personnel. The electronic components
within the panel can be damaged by static charge. Suitable precautions must be taken when handling
circuit boards. Never insert or remove boards or components, or connect cables, with the mains power
on or batteries connected.
Equipment Guarantee
This equipment is not guaranteed unless the complete system is installed and commissioned in accordance with the laid
down national standards by an approved and competent person or organisation.
This product has been manufactured in conformance with the requirements of all applicable EU Council
Directives

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0
11
INSTALLATION
ESD PRECAUTION
GENERAL
MOUNTING THE CABINET
Electronic components are vulnerable to damage by Electrostatic Discharges (ESD). An ESD wrist strap,
suitably grounded, should be worn at all times when handling pcbs. These wrist straps are designed to
prevent the build up of static charges, not only within a persons body, but on many other materials.
ESD damage is not always evident immediately, faults can manifest themselves at anytime in the future.
All pcbs should be stored in static shielded bags (silvered) for safe keeping, when not mounted in the
control panel.
Care should be taken with regards to avoiding the close proximity of high voltage cables or areas likely
to induce electrical interference. Earth links should be maintained on all system cables and grounded in
the control panel. The detection and sounder circuit cabling is classed as extra low voltage and must be
segregated away from mains voltage.
• Any junction boxes used should be clearly labelled FIRE ALARM.
• Any ancillary devices, e.g. door retaining magnets, must be powered from a separate power source.
• Any coils or solenoids used in the system must be suppressed, to avoid damage to the control
equipment.
This panel is only suitable for mounting in dry control rooms or dry accomodation spaces. The site chosen
for the location of the panel should be clean, dry and not subject to shock or vibration. Damp, salt air or
environments where water ingress or extremes of temperature may affect the panel must be avoided. The
temperature should be in the range -5° to +55°C, and the relative humidity should not exceed 95%.
Before mounting the cabinet remove the main PCB.
Remove the power supply module connecting wires from the main PCB, taking care to note where to re-
connect them. The main PCB can then be carefully pulled off it’s mounting clips.
Secure the cabinet to the wall using the four indented holes in the back box. Ensure the box is mounted
level and in a convenient location where it may be easily operated and serviced.
External cables should be glanded via preformed knockouts at the top and rear of the cabinet. Remove
any knockouts and ensure the cabinet is clear of swarf etc prior to retting the PCB. Always ensure that if
a knockout is removed, the hole is lled with a good quality cable gland. Any unused knockouts must be
securely blanked off.
Knockouts should be removed with a sharp tap at the
rim of the knockout using a at 6mm broad bladed
screwdriver.
Use of excessive force will damage the enclosure
around the knockout.

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0
12
INSTALLATION
Typical panel layout
Drawing shows typical internal layout of the panel cabinet with two 3.2Ah, 12v batteries tted
MAINS CONNECTIONS
Do not connect the mains supply to the panel
until you are fully conversant with the layout
and features of the equipment.
A rating plate is attached to the power supply
module describing the nature of the supply
permitted.
The incoming mains supply should be brought
into the panel via one of the knockouts
provided.
A suitable cable gland must be used to secure
the outer sheath of the cable used. The earth
must rst be connected to the primary earth
stud (peg) marked with a symbol, using a
suitable ring crimp.
Sufcient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the
terminal block while leaving the earth connection intact.
V+
V-
E
N
L
PSU
@ + +
- - + -
+ -
+ - + - + - + - + -
28V 0V
C NC NO C NC NO
FIRE FAULT FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
1 2 3
ON
Low voltage detection and sounder circuit wiringIncoming mains wiring
12V 3.2Ah VRLA BATTERY
12V 3.2Ah VRLA BATTERY
Filter
Battery
Clamp

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0
13
INSTALLATION
CONNECTING THE BATTERIES
BATTERY CHARGING VOLTAGE CHECKS
EARTH FAULT MONITORING
Batteries of even very small capacity are capable of delivering very high currents which can cause re or
injury, therefore battery connections should be done with caution.
The panel is supplied with battery leads already connected to the battery terminals on the main PCB.
These leads are coloured red for +ve and black for -ve.
2 x 12v batteries should be connected in series using the
white jumper lead provided. See diagram.
To optimise the service life of the batteries, the battery
charger output voltage varies with temperature.
N.B.
In the event of mains failure, the battery charger circuit will
protect the batteries from full discharge by disconnecting
them when they reach below 19v. When the mains supply
is restored the batteries will be automatically reconnected.
+ve-ve
12v SLA Battery 12v SLA Battery
+ -
BATTERY
1 2 3
ON
NOTE:
If the mains is connected before the batteries, the panel will show a Power Supply fault for up to 1 minute
until the monitoring cylce has nished polling. This is normal. If the fault doesn’t clear after 1 minute, check
connections.
For on ship use:- battery retaining clamps must be tted.
The battery charging voltage is factory calibrated to 27.3vdc +/- 0.2v @ 20oC. This should not normally
require adjustment. Where battery problems are experienced, the following information should be
considered.
a) If a battery is disconnected from the charger, no voltage will appear on the output leads or terminals,
due to intelligent battery controls.
b) Check the power supply voltage at the 28v & 0v supply output terminals. With the batteries
disconnected the voltage should be 27.6vdc +/- 0.2v @ between 11oC - 40oC.
c) To test the batteries, turn off the mains and see if the system will run on the batteries. Check the
battery voltage, should be 26.8v for a good battery or 22v for a at battery.
d) The power supply voltage can be adjusted using the potentiometer on the power supply module (see
page 7), checking at the 28v & 0v output terminals with a calibrated volt meter. Batteries should be
disconnected and the Access Level 3 DIL switch should be set to ‘ON’ (see page 17), which will over
ride the temperature compensation controls. Carefully adjust the voltage to 27.6vdc +/- 0.2v. When
completed, switch off Access Level 3 DIL switch and re-connect the batteries.
e) When the panel is re-charging a low battery, it should be possible to see the voltage across the
batteries increase gradually. If this is not occurring, the batteries or the panel may be faulty.
The Marine panels are equipped with earth fault monitoring to the 28v supply rails. Any cable connected
to earth will cause an earth fault to be indicated. The earth fault LED is located internally next to the
program options switch on the main circuit board. If an earth fault exists a PSU Fault (and General Fault)
will be indicated externally. The internal LED will show continuously for earth faults on the -ve polarity
cables and pulse for +ve polarity cables. (Be aware sounder cables monitor in reverse). Identifying the
source of the earth fault requires systematically removing cables until the fault clears. There is a 30
second delay to the earth fault signal to avoid spurious faults due to noise.

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0
14
SETUP & PROGRAMMING
LEVEL 3 ENGINEERING OPTIONS
- + - + - + - + - + -
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
1 2 3
ON
1 2 3
ON
A series of programmable engineering options are available. These
programming modes are initiated by entering a four digit code using
buttons 1 - 4 on the keypad followed by the ENTER button.
1 2 3
ON
1234567
1 1 1 3 Reset all disablements, test modes and parameters back to factory settings.
Options
Enter the above code and press the ENTER button.
Then press the ENTER button again and hold for 3 seconds.
Any disablements or test mode settings will now clear and all
engineering option parameters will revert back to factory settings.
The panel will bleep to acknowledge the reset.
RESOUND SILENCE RESET
ENTER
1 2 3 4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND SILENCE RESET
ENTER
1 2 3 4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
To access Level 3 options, rst set switch 3 on the 3 way DIL switch located on the main PCB to the
‘ON’ position. Then activate the controls by entering the four digit code (see Activate Controls in the
OPERATING section).
The ‘Access Level’ indicator will pulse
rapidly to signify that Level 3 access is
active.
2 2 2 4 Set fault buzzer volume.
RESOUND SILENCE RESET
ENTER
1 2 3 4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
There are two levels of volume for the internal fault buzzer, high and low.
Enter the above code and press the ENTER button to increase or decrease
the fault buzzer tone from the previous level.
Setting will change when ENTER button is pressed.
When nished, enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0
15
SETUP & PROGRAMMING
1 2 2 2 Muster Alarm Signal.
This option is used to select zones for activation of a muster alarm signal. A muster alarm is dened as 7 short
blasts of the sounders, followed by 1 long blast. This is repeated until silenced. The activated muster alarm
zone will show a re indication at the panel but no common re LED. The panels outputs can be programmed
to respond to a muster alarm using seperate option codes.
A second setting is provided to enable the panels ‘RESOUND’ button to activate the muster alarm signal.
Note: With panel software V4.1 and above, muster alarm will have priority over any new re alarms by default.
It is possible to make re a higher priority using
option 3.
Enter the above code and press the ENTER button.
The zone 1 re LED will be on steady. Use button
1 to toggle between steady re LEDs 1, for setting
muster alam zones, 2, for setting RESOUND button
to activate muster alarm, 3, for changing muster
alarm priority.or
4, Set presence of VDR card.
LED 1 LED 2 LED 3 LED 4
Select
muster
alarm zones
Set
RESOUND
button
Set muster
alarm
priority
OFF
Set VDR
Card
Present
Set Muster Alarm Zones [LED 1]
With the zone 1 re LED lit press the ENTER button and the LED will pulse to indicate setting zone 1 to muster
alarm. Use button 1 to move the pulsing re LED to the required zone and then use button 2 to change the
setting, indicated by the amber fault LED ON or OFF. Any or all zones may be set for muster alarm.
ON = muster alarm zone, OFF = standard.
Set RESOUND Button Operation For Muster Alarm [LED 2]
With the zone 2 re LED lit press the ENTER button. Fire LED 2 will now pulse to indicate editing mode.
Use button 2 to toggle the option on or off, indicated by zone 1 amber fault LED ON or OFF.
ON = RESOUND button activates muster alarm, OFF = RESOUND button activates evacuate (default).
Set Fire As Priority Over Muster Alarm [LED 3]
With the zone 3 re LED lit press the ENTER button. Fire LED 3 will now pulse to indicate editing mode.
Use button 2 to toggle the option on or off, indicated by zone 1 amber fault LED ON or OFF.
OFF = muster alarm has priority, ON = re has priority.
When nished, press and hold button 1 to store settings and exit programming mode. Then enter next
programming code or return DIL switch 3 to ‘OFF’ position and disable controls.
Set presence of VDR card [LED 4]
When a VDR (Voyage data recorder) communications output card is to be used the setting must be made to
allow the panel to monitor the integrity of the communications path.
With the zone 4 re LED lit press the ENTER button. Fire LED 4 will now pulse to indicate editing mode. Use
button 2 to toggle the option on or off, indicated by zone 1 amber fault LED ON or OFF.
OFF = VDR card is not present, ON = VDR card is tted.

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0
16
SETUP & PROGRAMMING
2 1 2 3 Panel Wide Settings
OPTION 1. Change / Remove Keypad Access Code
There are 4 general, panel wide, settings available.
Enter the above code and press the ENTER button. The 4 programmable
options are represented by re zone LEDs 1 - 4.
Use button 1 to move to option required as per table;
RESOUND SILENCE RESET
ENTER
1 2 3 4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND SILENCE RESET
ENTER
1 2 3 4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
Fire LED Programming Option
1 Change / remove keypad access code
2 Set presence of output card
3 Inhibit muted tone beeps
4 UPS Mode / Disable battery monitoring
The keypad can be used to activate the panel controls instead of using the key switch. The default code
is 1-2-3-4, however, this can be changed. It is also possible to disable the use of a code entry to enable
controls, forcing the use of the key switch only.
With the zone 1 re LED lit, press the ENTER button. Zone 1 re LED will pulse to indicate ‘edit mode’ and
the amber, fault LEDs will start to rapidly pulse in sequence to show the currently set code.
Enter the new code slowly and deliberately, one number at a time using buttons 1 - 4
Note: Enable Controls codes must always start with a 1 or 2.
When nished entering the new four digit code, press the ENTER button. The panel will then conrm the
new code with rapidly pulsing LEDs in sequence and zone 1 re LED will return to steady ‘view mode’.
Changing the keypad code to 1 - 1 - 1 - 1 will disable the use of a keypad to enable controls.
Press button 1 to move to next option or hold button 1 for 3
seconds to exit programming mode 2-1-2-3. (The panel will
conrm the new access code one more time before exiting the
programming mode).
RESOUND SILENCE RESET
ENTER
1 2 3 4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0
17
SETUP & PROGRAMMING
OPTION 3. Inhibit Muted Tone Beeps
With the zone 3 re LED lit press the ENTER button. The zone 1 re LED will pulse to indicate ‘edit mode’.
Press button 1 to light the zone 1 amber fault LED. - Beeps are now silenced.
OPTION 2. Set Presence of Output Card
An output/relay card may be added to each control panel to provide additional common or zonal outputs.
The presence of the card must be setup to enable operation.
With the zone 2 re LED lit, the amber, fault LED (zone 1) will show the current setting.
Zone 1 amber fault LED ON = Output Card present.
Press the ENTER button, zone 1 re LED will pulse to indicate adding or removing the card.
Then use button 2 to add or remove the card, indicated by the amber fault LED ON (added) or OFF
(removed).
When nished press the ENTER button again and the zone 2 re LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
OPTION 4. UPS Mode / Disable Battery Monitoring (EN54!) & Disable Battery Hi Z Monitoring (EN54!)
The battery monitoring may be disabled for applications where this is appropriate such as non re alarm
use or where no battery backup is required. Note: There is no remote PSU fault input available on the
panel. This is also known as ‘UPS Mode’ where the panel is supplied from a local 24v supply rather than
mains and intenal batteries.
With the zone 4 re LED lit, the amber, fault LEDs will show the current setting.
Press the ENTER button, zone 1 re LED will pulse to indicate ‘edit mode’ for std battery monitoring.
Use button 1 to toggle between pulsing re LEDs 1 & 2 for editing std or Hi Z battery monitoring as per
above.
Now use button 2 to change the setting indicated by the amber fault LED as per above.
When nished press the ENTER button again and the zone 4 re LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
Note: When batteries are unmonitored the input 24v dc voltage may vary between 20v dc & 32v dc.
FAULT LED 1 FAULT LED 2 SETTINGS
OFF ON Battery & Hi Z monitoring normal (default)
ON ON Battery & Hi Z monitoring both ‘OFF’ (UPS mode)
ON OFF Battery & Hi Z monitoring both ‘OFF’ (UPS mode)
OFF OFF Battery monitoring ‘ON’, Hi Z monitoring ‘OFF’

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0
18
SETUP & PROGRAMMING
1 1 1 4 Select sounder resound options for zones.
By default, after an initial re condition and the (blue) Silence Alarms button has been activated, any new
re condition in a different zone will cause the alarms to resound.
It is possible to change this on a zonal basis so that any new alarm in a different zone will not resound the
alarms.
Enter the above code and press the ENTER button. The Sounder Status LED will pulse slowly. Zone Fault
LEDs will show their current status (see below) with Zone 1 pulsing to indicate it is under selection.
Use Button 1 (Disable Mode) to move to the zone for programming (indicated by a pulsing LED) and press
the ENTER button to change the status. Pressing the ENTER button again will toggle the status, indicated
by a rapid or slow pulsing LED (see below). Then use Button 1 to move to the next zone. If the zone has
been set to not resound alarms, the LED will be off. If kept as default, new re condition will resound
alarms, then the LED will be on steady.
Rapid Pulse = Zone is under selection and is set to have alarms resound (default).
Slow Pulse = Zone is under selection and has been set to not resound alarms on new re condition.
LED Off = Zone has been set to not resound alarms on new re condition.
LED On = Zone is set to have alarms resound (default).
RESOUND SILENCE RESET
ENTER
1 2 3 4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND SILENCE RESET
ENTER
1 2 3 4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
When nished, press and hold Button 1 (Disable Mode) for 3 seconds or alternatively wait approx 10
seconds and the panel will save the settings and revert back to Level 3 access mode.
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
This manual suits for next models
2
Table of contents
Other Haes Control Panel manuals
Popular Control Panel manuals by other brands

Xylem
Xylem Lowara Q-smart Installation, operation & maintenance manual

Lippert Components
Lippert Components LCI Level-Up owner's manual

CAME BPT
CAME BPT TH/PLUS Installation and commissioning manual

Danfoss
Danfoss ECL Comfort 210 user guide

mr. steam
mr. steam TEMPO/PLUS owner's manual

Pro-face
Pro-face GC4000 Series Hardware manual