HBM SB01A User manual

A1020-4.0 en/de/fr
Safety Barriers
Zenerbarrieren
Barrières de Zener
SB01A
Mounting Instructions
Montageanleitung
Notice de montage

English Page 3 - 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Deutsch Seite 19 - 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Français Page 35 - 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3
SB01A
A1020-4.0 en/de/fr HBM
Contents Page
English
Safety instructions 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Scope of delivery 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 General 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Application 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Maintenance, service 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Fault elimination 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Insulation coordinates for units with Ex certification according
to EN 60079‐11 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Ambient conditions 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 Operating principle 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Installation notes 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Specification of the Zener barriers 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 Electrical connection 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Barrier nominal (rated) data 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 Dimensions 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SB01A
4
A1020-4.0 en/de/frHBM
Safety instructions
Appropriate use
Zener barriers are used in control and instrumentation systems for the
processing of lower voltages and currents. Zener barriers contain intrinsically
safe circuits that are used to drive intrinsically safe field devices (load cells) in
potentially explosive atmospheres.
Devices which have been operated in general electrical systems, must not be
used afterwards in electrical systems that are in connection with potentially
explosive atmospheres.
To ensure safe operation, the device may only be operated in accordance with
the information given in the Operating Manual. It is also essential to comply
with the legal and safety requirements for the application concerned during
use. The same applies to the use of accessories.
The equipment must not be attached directly to the mains.
General dangers of failing to follow the safety instructions
The Zener barriers correspond to the state of the art and are fail‐safe. The
devices may give rise to remaining dangers if they are inappropriately
installed and operated by untrained personnel.
Any person entrusted with the installation, commissioning, maintenance or
repair of the devices must have read and understood the Operating Manual
and in particular the technical safety instructions.
Conditions on site
Protect the equipment against direct contact with water (IP 20).
Maintenance and cleaning
The Zener barriers are maintenance free. Please note the following points
when cleaning the housing:
- Before cleaning, disconnect the device from the power supply.
- Clean the housing with a soft, slightly damp (not wet!) cloth. In no case
shall you use solvent.
- When cleaning, ensure that no liquid gets into the device or connections.

5
SB01A
A1020-4.0 en/de/fr HBM
Remaining dangers
The scope of performance and supply of the Zener barriers covers only part of
the range of measurement technology. In addition, equipment planners,
installers and operators should plan, implement and respond to the safety
engineering considerations of measurement technique in such a way as to
minimize remaining dangers. Prevailing regulations must be complied with at
all times. There must be reference to the remaining dangers connected with
measurement technique.
Any risk of remaining dangers when working with the Zener barriers is pointed
out in this manual by means of the following symbols:
Symbol: CAUTION
Meaning: Potentially dangerous situation
Warns of a potentially dangerous situation in which failure to comply with
safety requirements could result in damage to property or some form of
bodily injury.
Symbols pointing out notes on use and waste disposal as well as useful
information:
Symbol: NOTE
Means that important information about the product or its handling is being
given.
Symbol:
Meaning: CE mark
The CE mark enables the manufacturer to guarantee that the product com
plies with the requirements of the relevant EC directives (the declaration of
conformity is available at http://www.hbm.com/HBMdoc).

SB01A
6
A1020-4.0 en/de/frHBM
Qualified personnel
This instrument may only be installed and used by qualified personnel, strictly
in accordance with the technical data and the safety requirements and
regulations listed below. It is also essential to comply with the legal and safety
requirements for the application concerned during use. The same applies to
the use of accessories.
Qualified personnel means persons entrusted with the installation, assembly,
commissioning and operation of the product who possess the appropriate
qualifications for their function. Maintenance and repair work at the open, live
device may only be performed by trained personnel who are aware of the
potential danger.
CAUTION
Start‐up and installation are to be implemented only by technical personnel
for this special‐trained.
Installation of the devices outside the potential explosive atmosphere
SThe Zener barriers are constructed to comply with protection class IP20
according to EN 60529 and must be protected accordingly from adverse
environmental conditions such as water spray or dirt exceeding the degree of
soiling 2.
SZener barriers must be installed outside the potential explosive atmosphere!
SThe intrinsically safe circuits of the devices (light blue marking at the devices)
can be - depending on the type of protection - conducted through potential
explosive atmospheres. In this connection, it is particularly important to ensure
the safe isolation of all non‐intrinsically safe circuits.
SWhen intrinsically safe field devices (load cells) are interconnected with the
intrinsically safe circuits of the related Zener barriers, the respective maximum
values for the field devices (load cells) and the Zener barriers - in the sense
of explosion protection - must be observed (proof of intrinsic safety).
EN 60079‐14 / IEC 60079‐14 has to be observed. For the Federal Republic of
Germany the national foreword of the DIN EN 60079‐14 / VDE0165 part 1 has
to be observed additionally.
SThe EC Certificates of Conformity or EC‐Type Examination Certificates have
to be observed. It is especially important to observe the ”Special conditions”
where these are contained in the certificates.
SWhen intrinsically safe circuits are used in explosive atmospheres caused by
dust (Ex‐Area 'D') only approved field devices (load cells) must be used.

7
SB01A
A1020-4.0 en/de/fr HBM
1 Scope of delivery
•2 pcs Zener barriers type Z 764
•1 pc Zener barrier type Z 763
•EC type examination certificate BAS01ATEX7005
•Certificate of Conformity BAS No. Ex 02E2186
•Mounting instructions
2 General
The SB01A Zener barrier combination comprising two pcs of type Z764 and one
pc of type Z763 was specially developed by Pepperl + Fuchs in cooperation with
HBM for the use of load cells with DC weighing indicators. It is characterized by
a low line resistance in the excitation lines.
For this circuit arrangement the BASEEFA (British Approvals Service for
Electrical Equipment in Flammable Atmospheres) has granted a system
Certificate of Conformity (BAS No. Ex 02E2186).
The complete certificates of conformity can be found on our web site:
http://www.hbm.com/HBMdoc

SB01A
8
A1020-4.0 en/de/frHBM
3 Application
3.1 Maintenance, service
The transfer characteristics of the devices remain stable, even over long periods
of time, thus eliminating the need for regular adjustment. Maintenance is there
fore not required.
3.2 Fault elimination
Units that are operated in connection with potentially explosive atmospheres
must not be modified in any way. Repairs on a unit may be carried out only by
specially trained and authorized specialist personnel.
3.3 Insulation coordinates for units with Ex certification
according to EN 60079‐11
The units are determined for use in degree of soiling 2, per EN 60664.
3.4 Ambient conditions
Ambient temperature: -20 °C ... +60 °C ( -4 °F ... +140 °F )
Storage temperature: -25 °C ... +70 °C ( -13 °F ... +158 °F )
Humidity: max. 75 % relative humidity without condensation
3.5 Operating principle
Safety barriers form the interface between intrinsically safe and
non‐intrinsically safe circuits. It is their task to limit the energy transmitted from
the non‐Ex area to the Ex area, both in normal operation and in the event of a
fault.
The barrier limits the current and voltage in the intrinsically safe circuit if the
voltage on the non‐intrinsically safe side reaches excessively high values or if
a short circuit occurs on the intrinsically safe side.
In normal operation the voltage between terminals 7 and 8 or 5 and 6 is less
than the breakdown voltage UZof the Zener diodes, and therefore there is
only a small leakage current through the diodes.

9
SB01A
A1020-4.0 en/de/fr HBM
Safe areaHazardous area
7
6
5
81
2
3
4
x3
x3
Load cell
Amplifier
R1
R1
Fig. 3.1: Schematic diagram of the internal structure of a Zener barrier
If the voltage between terminals 7 and 8 or 5 and 6 increases beyond the
breakdown voltage of the diodes, the Zener diodes become conducting. If the
current is too high, the fuse trips and protects the Zener diodes from
overloading.
If the fuse is destroyed the damage is irreparable, and the whole barrier has
to be swapped out.
In the event of a short circuit on the intrinsically safe side, the resistance R1
limits the current on terminals 1 and 4 to IK= UZ/ R1.
The data for voltage, resistance and short‐circuit current is specified on the
Zener barriers.
The Zener barrier can only limit the voltage and current in the intrinsically safe
circuit effectively if the energy stored in the intrinsically safe circuit is also
limited. Therefore the capacitance and inductance in this circuit, also taking
account of the cable properties, must not exceed defined values.
The SB01A Zener barrier set is intended for operating strain gage full‐bridge
transducers on measuring amplifiers that have a DC bridge excitation.
Grounding Zener barriers
The purpose of the dual‐channel structure of the Zener barrier is not only to
limit the voltage and current between the two channels with terminals 5 and 8,
but also to make sure they are limited relative to the ground potential.
NOTE
In order to operate the barrier safely it must always be grounded
through a potential equalization line.

SB01A
10
A1020-4.0 en/de/frHBM
The cross‐section of the ground connection in the case of a copper conductor
must be at least 4mm2(for further requirements see EN60079-14, section
12.2.4).
CAUTION
Double grounding of intrinsically safe circuits is not prohibited.
The isolation voltage of lines and field devices (load cells), measured against
ground, must be greater than 500 VAC.
CAUTION
In the case of cable lengths over 50 meters the shield must not be put
on on both sides.

11
SB01A
A1020-4.0 en/de/fr HBM
4 Installation notes
The Zener barriers can be installed in three different ways by snapping onto a
support rail according to EN 60715.
Label carrier
Insertion strip
35 mm support rail
to EN 60715
Clamp
Fig. 4.1 Potential compensation via the support rail
Mounting
block
Fig. 4.2 Insulated assembly (group grounding)

SB01A
12
A1020-4.0 en/de/frHBM
Spacing roller
Ground rail feed
N‐Combined rail
Mounting block
Connector for ground lead
Connector
Single socket
Fig. 4.3 Insulated assembly (single grounding)
Type of construction: modular terminal housing made of Makrolon,
flammability class UL 94: V‐0
Mounting: snap‐on type onto 35 mm standard rail
according to EN 60715
Connection options: self‐opening unit terminals,
max. wire cross‐section: 2 x 2.5 mm2
Usually, barriers are used in racks or switching cabinets. They can be fitted in
housings under production conditions, provided that the housing offers
sufficient protection. They can also be used in potentially explosive
atmospheres if it is ensured that the surrounding housing has been certified
for such use.
The installation must be carried out such that the intrinsic safety is not
adversely affected by the following factors:
SRisk of mechanical damage
SUnauthorized modifications or manipulation by third party personnel
SHumidity, dust, foreign matter
SExceeding the permissible ambient temperature
SConnection of non intrinsically safe electrical circuits to intrinsically safe
circuits
Grounding of the mounting rail
The assembly rail is usually grounded by connecting both ends to the
intrinsically safe ground. This also simplifies any testing of the ground
connection.

13
SB01A
A1020-4.0 en/de/fr HBM
5 Specification of the Zener barriers
5.1 Electrical connection
1
Sense +
Excitation +
Excitation -
Sense -
Signal -
Signal +
6
1
4
8
5
Z763
Z764
Z764
1
4
8
5
1
4
8
5
Amplifier
(WE2108, WE2110
or AED...)
Junction box Zener barriers
SB01A
1 ... 6 Load cells
Excitation
Signal
Sense
+
-
+
-
-
+
Hazardous area Safe area
2
D
D
D
CAUTION
Observe max. permissible cable length and nominal (rated)
values of the barriers. Please see tables on next pages!

SB01A
14
A1020-4.0 en/de/frHBM
5.2 Barrier nominal (rated) data
Type Un[V] Rmin
[Ω]Rnom
[Ω]Rmax
[Ω]Uznom
[V] U0[V] Ikor I0
[mA] Pmax
[W]
Z763Supply 10.0
0.7
31.35
31.35
33.0
33.0
39.8
38.8
12.0
1.5
11.6
1.6
370
51
1.07
0.02
Z764Sense 10.0
10.0
980
980
1k
1k
1033
1033
12.0
12.0
11.6
11.6
12.0
12.0
0.04
0.04
Z764Signal 10.0
10.0
980
980
1k
1k
1033
1033
12.0
12.0
11.6
11.6
12.0
12.0
0.04
0.04
469 1.25
These values refer to the maximum voltage, the minimum value of the fitted
resistance and the resulting maximum current.
Maximum voltage U0
The maximum voltage does not refer to the working range but to the value
that can be maximally reached in the event of a fault, until the fuse is
triggered. The resistance value is not identical with the maximum longitudinal
resistance. These values only provide an indication of the values that can be
maximally reached in the event of a fault.
Longitudinal resistance
The resistance that can be measured between both ends of a barrier channel.
It is determined by the sum of resistance R and the resistance value of the
fuse at an ambient temperature of 20 °C (68 °F).
Polarity
When connecting, note the specified polarity.
Maximum current in an intrinsically safe electrical circuit (IK)
The maximum current value which can flow in the intrinsically safe circuit in
the event of a fault occurring.
Maximum input voltage (Un)
The maximum voltage (of correct polarity), which can be applied between the
contacts inside the safe area and the ground without the fuse being triggered.
This value is determined with an open intrinsically safe power circuit and at an
ambient temperature of 20 °C (68 °F). This means, that the max. bridge
excitation voltage of the amplifier may be up to 10 V on terminal 8 of barrier Z
763. At terminal 5, 0 V should be applied (max. 0.7 V due to the voltage drop
across the lines). At the terminals of Z 764 (filter and signal ) there will then be

15
SB01A
A1020-4.0 en/de/fr HBM
a voltage applied, coming from the hazardous area, which corresponds to
approx. half the bridge excitation voltage.
Maximum external capacity Cmax that may be connected
The maximum capacity value which may be connected to the terminals of the
intrinsically safe circuit of the barrier. This value results from the sum of line
capacity and input capacity of the field unit (load cell).
Maximum inductivity Lmax that may be connected
The maximum inductivity value which may be connected to the terminals of
the intrinsically safe circuit of the barrier. This value results from the sum of
line inductivity and input inductivity of the field unit (load cell).
The max. permissible capacity and inductivity results from the following
tables:
Load cells tested to PTB 01 Atex 2208, gas group IIC
(HBM types C16..., C2..., U2..., PW...):
Gas group Capacity (μF) Inductivity (μH) L/R ratio (μH/Ω)Cable length 1)
IIC 0.92 137 28
300 m
IIB 5.78 622 116
IIA 20.98 1269 233
Load cells tested to PTB 01 Atex 2209, gas group IIC
(HBM types HLC..., RSC..., PWS..., Z6..., PW15...):
Gas group Capacity (μF) Inductivity (μH) L/R ratio (μH/Ω)Cable length 1)
IIC 0.92 149 28
300 m
IIB 5.78 634 116
IIA 20.98 1281 23
Load cells tested to PTB 01 Atex 2211, gas group IIC
(HBM types RTN...):
Gas Capacity (μF) Inductivity (μH) L/R ratio (μH/Ω)Cable length 1)
IIC 0.85 61 25
100 m
IIB 5.71 546 113
IIA 20.91 1193 230
1) Max. permissible cable length between SB01A and junction box with HBM
cable type KAB7.5/00‐2/2/2 (blue)

SB01A
16
A1020-4.0 en/de/frHBM
CAUTION
With cable lengths over 50 m the cable shield must not be supported on
both sides!
Specifications for HBM cable KAB7.5/00‐2/2/2 (blue)
HBM part no.: - 4‐3301.0082 (sold by the length)
- 1‐CABE2/20 (cable roll, 20 m cable)
- 1‐CABE2/100 (cable roll, 100 m cable)
Cable type LF‐2YAECVY 3x2x0.14 (0.10)
Diameter 7.5 "0.3 mm
Use Connection cable
from junction box (hazardous area)
to Zener barrier (safe area)
Cable structure 6 wires, shielded, in pairs with parallel
stranded wire
Conductor material Cu wire, tinned
Wire structure / stranded wire 18 single wires, ∅0.10 mm
Cross section 0.14 mm2
Insulation of the wires PE‐A (different colors)
Wire colors/pair white/red; black/blue; grey/green
Shield Cu, ∅0.15 mm, 95 % degree of coverage
Sheath PVC/PUR/SIL etc. available
blue, RAL 5015
Temperature ranges with movement: -5 °C...+50 °C
(23 °F...+122 °F)
without movement: -30 °C...+70 °C
(-22 °F...+158 °F)
Bending radius >75 mm
Insulation resistance 10 GΩx km
Loop resistance 282 Ω/ km
Loop inductivity, max. 0.44 mH / km
Capacity wire/wire 2 x 75 nF / km
Capacity wire/shield 130 nF / km

17
SB01A
A1020-4.0 en/de/fr HBM
6 Dimensions
Dimensions of one Zener barrier (in mm, 1 mm = 0.03937 inches)
11012.5
115
1 Set = 3 pcs.
(2 x Zener barriers Z764 type, 1 x Zener barriere Z763 type)

SB01A
18
A1020-4.0 en/de/frHBM

19
SB01A
A1020-4.0 en/de/fr HBM
Inhalt Seite
Deutsch
Sicherheitshinweise 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Lieferumfang 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Allgemeines 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Anwendung 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Instandhaltung, Wartung 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Störungsbeseitigung 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Isolationskoordinaten für Geräte mit Ex‐Zertifikat nach
EN 60079‐11 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Umgebungsbedingungen 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 Funktionsprinzip 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Installationshinweise 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Spezifikation der Zenerbarrieren 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 Elektrische Verschaltung 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Barrieren‐Nenndaten 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 Abmessungen 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SB01A
20
A1020-4.0 en/de/frHBM
Sicherheitshinweise
Bestimmungsgemäße Verwendung
Der Einsatz der Zenerbarrieren erfolgt in der MSR‐Technik zur Verarbeitung
von kleineren Spannungen und Strömen. Die Zenerbarrieren beinhalten
eigensichere Stromkreise, die dazu dienen, eigensichere Feldgeräte
(Wägezellen) innerhalb explosionsgefährdeter Bereiche zu betreiben.
Geräte, die in allgemeinen elektrischen Anlagen betrieben wurden, dürfen
danach nicht mehr in elektrischen Anlagen eingesetzt werden, die in
Verbindung mit explosionsgefährdeten Bereichen stehen.
Zur Gewährleistung eines sicheren Betriebes darf das Gerät nur nach den
Angaben in der Bedienungsanleitung betrieben werden. Bei der Verwendung
sind zusätzlich die für den jeweiligen Anwendungsfall erforderlichen Rechts‐
und Sicherheitsvorschriften zu beachten. Sinngemäß gilt dies auch bei
Verwendung von Zubehör.
Das Gerät darf nicht unmittelbar ans Netz angeschlossen werden.
Allgemeine Gefahren bei Nichtbeachten der Sicherheitshinweise
Die Zenerbarrieren entsprechen dem Stand der Technik und sind betriebssi
cher. Von den Geräten können Restgefahren ausgehen, wenn sie von unge
schultem Personal unsachgemäß eingesetzt und bedient werden.
Jede Person, die mit Aufstellung, Inbetriebnahme, Wartung oder Reparatur
der Geräte beauftragt ist, muss die Bedienungsanleitung und insbesondere
die sicherheitstechnischen Hinweise gelesen und verstanden haben.
Bedingungen am Aufstellungsort
Schützen Sie die Zenerbarrieren vor direktem Kontakt mit Wasser (IP20).
Wartung und Reinigung
Die Zenerbarrieren sind wartungsfrei. Beachten Sie bei der Reinigung des
Gehäuses folgende Punkte:
- Trennen Sie vor der Reinigung die Verbindung zur Stromversorgung.
- Reinigen Sie das Gehäuse mit einem weichen und leicht angefeuchteten
(nicht nassen!) Tuch. Verwenden Sie auf keinen Fall Lösungsmittel.
- Achten Sie beim Reinigen darauf, dass keine Flüssigkeit in das Gerät oder
an die Anschlüsse gelangt.
Table of contents
Languages:
Other HBM Accessories manuals