INSTALLATION AND SPECIFICATIONS

Copyright © 2020 Honeywell. All rights reserved.
All product and brand names are the service marks, trademarks, registered trademarks, or registered service marks of their
respective owners. Printed in the United States of America. Honeywell reserves the right to change any information in this
document at any time without prior notice.
Pro-Watch® is a trademark of Honeywell International, Inc.
Ordering Information
Please contact your local Honeywell representative or visit us on the web at www.honeywellintegrated.com for information
about ordering.
Feedback
Honeywell appreciates your comments about this manual. Please visit us on the web at www.honeywellintegrated.com to
post your comments.
DISCLAIMER
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device
may not cause harmful interference, and (2) this device must accept any interference received, including interference that
may cause undesired operation.

Installation Guide, Document 800-26499 i
TABLE OF CONTENTS
Chapter 1 - Installation And Specification .................................................. 1
General......................................................................................................................................... 1
PW7K1R1 Hardware............................................................................................................... 2
Reader wiring.............................................................................................................................3
Door Strike Relay Wiring ....................................................................................................... 4
Communication Wiring .........................................................................................................5
Address Baud Rate and Encryption Configuration Switch ..................................... 6
Status LEDs ............................................................................................................................... 7
Specifications............................................................................................................................ 8
Warranty ...................................................................................................................................... 9
Liability ........................................................................................................................................ 9

ii Installation Guide, Document 800-26499
(This page is intensionally left blank)

CHAPTER
1
Installation Guide, Document 1
INSTALLATION AND
SPECIFICATION
General
The PW7K1R1 reader interface provides a solution to the OEM system integrator
for interfacing to a TTL (D1/D0, Clock/Data), F/2F or RS-485 device, and door
hardware. It also provides a tri-stated LED control and buzzer control. Two Form-C
contact relay outputs may be used for strike control or alarm signaling. Two inputs
are provided that can be used for monitoring the door contact and request to exit
push button. Input circuits can be configured as unsupervised or supervised. Com-
munication to the controller is accomplished via a 2-wire RS-485 interface. The
PW7K1R1 requires 12 to 24 Vdc for power.

2 Installation Guide, Document
PW7K1R1 Hardware
The PW7K1R1 requires filtered 12 to 24 Vdc ± 10% for power. Two inputs are typi-
cally used for door contact and exit push button monitoring. End of line resistors
are required input supervision, shown below.
Note: The input power is passed through to the reader terminal strip and is available for
powering a reader. Readers that require different voltage requirements must be
powered separately. Care must be taken to insure that the input voltage is within the
voltage range of the reader. The reader power output terminal, TB4-6 (VO), is not
current limited

Installation Guide, Document 3
Reader wiring
The reader port supports a reader with TTL (D1/D0, Clock/Data), F/2F, or 2-wire
RS-485 signaling. **Refer to the reader manufacture specifications for cabling
requirements. In the 2-wire LED mode the buzzer output is used to drive the sec-
ond LED. Reader port configuration is set via the host software. Do not terminate
any RS-485 device connected to the reader port.
Caution: : D1 to LED on supervised F/2f readers

4 Installation Guide, Document
Door Strike Relay Wiring
The PW7K1R1 has two Form-C contact relays for controlling a door strike or other
devices. See specifications section for the relay contact ratings. Load switching
can cause abnormal contact wear and premature contact failure. Switching of
inductive loads (strike) also causes EMI (electromagnetic interference) which may
interfere with normal operation of other equipment. To minimize premature con-
tact failure and to increase system reliability, use the contact protection circuit
shown below. Recommend the following circuit. Locate the protection circuit as
close to the load as possible (within 12 inches [30 cm]), as the effectiveness of the
circuit will decrease if it is located far away.

Installation Guide, Document 5
Communication Wiring
The PW7K1R1 communicates to a Honeywell Security intelligent controller
(EP2500 for example) via a half-duplex multi-drop 2-wire RS-485 interface. The
total cable length is limited to 4,000 feet (1,219 meters). Shielded cable of 24 AWG
with characteristic impedance of 120 ohm is specified for the 2- wire RS-485 inter-
face. The device on each end of the communication line should have the termina-
tor installed (install jumper J1 of the PW7K1R1)
.

6 Installation Guide, Document
Address Baud Rate and Encryption Configuration Switch
Switches 1 to 5 select the device address. Switch 6 and 7 select the communication
baud rate. Switch 8 enables encrypted communication. All other configuration
settings are set via host software.
S8 S7 S6 S5 S4 S3 S2 S1 SECTION
OFF OFF OFF OFF OFF Address 0
OFF OFF OFF OFF ON Address 1
OFF OFF OFF ON OFF Address 2
OFF OFF OFF ON ON Address 3
OFF OFF ON OFF OFF Address 4
OFF OFF ON OFF ON Address 5
OFF OFF ON ON OFF Address 6
OFF OFF ON ON ON Address 7
OFF ON OFF OFF OFF Address 8
OFF ON OFF OFF ON Address 9
OFF ON OFF ON OFF Address 10
OFF ON OFF ON ON Address 11
OFF ON ON OFF OFF Address 12
OFF ON ON OFF ON Address 13
OFF ON ON ON OFF Address 14
OFF ON ON ON ON Address 15
ON OFF OFF OFF OFF Address16
ON OFF OFF OFF ON Address 17
ON OFF OFF ON OFF Address 18
ON OFF OFF ON ON Address 19
ON OFF ON OFF OFF Address 20
ON OFF ON OFF ON Address 21
ON OFF ON ON OFF Address 22
ON OFF ON ON ON Address 23
ON ON OFF OFF OFF Address 24

Installation Guide, Document 7
Status LEDs
Power-up: All LED’s OFF
Initialization:
Once power is applied, initialization of the module begins
The D1 LED is turned ON at the beginning of initialization
Run time:
After a successful initialization, the LEDs have the following meanings
D1 LED:
Heartbeat and On-Line Status
Off-line:
1 second rate, 20% ON, 80% OFF
ON ON OFF OFF ON Address 25
ON ON OFF ON OFF Address 26
ON ON OFF ON ON Address 27
ON ON ON OFF OFF Address 28
ON ON ON OFF ON Address 29
ON ON ON ON OFF Address 30
ON ON ON ON ON Address 31
OFF OFF 115,200 BPS
OFF ON 9,600 BPS
ON OFF 19,200 BPS
ON ON 38,400 BPS
OFF Encrypted communication not required
ON Encrypted communication required
S8 S7 S6 S5 S4 S3 S2 S1 SECTION

8 Installation Guide, Document
On-line:
Non-encrypted communication: 1 second rate, 80% ON, 20% OFF
Encrypted communication:
.1 S ON,.1 S OFF,.1 S ON,.1 S OFF,.1 S ON,.1 S OFF,.1 sec ON,.3 S OFF
D1 LED Error Indication:
Waiting for the downloaded of the application firmware:.1 S ON,.1 S OFF
D2 LED: SIO Communication Port Status:
Indicates communication activity on the SIO communication port
Specifications
Revision E assembly
The Interface is for use in low voltage, class 2 circuits only
Reader Interface
Cable Requirements
Primary Power 12 to 24 Vdc ± 10%, 150 mA maximum (plus reader current)
Outputs: Two Form-C contact relays:
K1: Normally open contact (NO) contact: 5 A @ 30 Vdc resistive Normally
closed contact (NC) contact: 3 A @ 30 Vdc resistive K2: 1 A @ 30 Vdc resistive
Inputs: Two unsupervised/supervised, standard EOL, 1k/1k ohm, 1%, ¼ watt
One unsupervised, dedicated for cabinet tamper
Reader power 12 to 24 Vdc ± 10% (input voltage passed through)
Reader LED output: TTL compatible, , high > 3 V, low < 0.5 V, 5 mA source/sink maximum
Buzzer output: Open collector, 12 Vdc open circuit maximum, 40 mA
sink maximum
Data Inputs TTL compatible, F/2F or 2-wire RS-485
Communication: 2-wire RS-485: 9600, 19200, 38400 or 115200 bps
Power: 1 twisted pair, 18 AWG
RS-485 I/O devices: 1 shielded twisted pair, 24 AWG, 120 ohm impedance, 4,000 ft.
(1,219 m) maximum
Alarm Inputs: 1 twisted pair per input, 30 ohms maximum
Outputs: As required for the load
Reader data (TTL): 6-conductor, 18 AWG, 500 ft. (150 m) maximum
Reader data (F/2F): 4-conductor, 18 AWG, 500 ft. (150 m) maximum

Installation Guide, Document 9
Mechanical
Environment
Warranty
Honeywell Security warrants the product is free from defects in material and work-
manship under normal use and service with proper maintenance for one year from
the date of factory shipment. Honeywell Security assumes no responsibility for
products damaged by improper handling or installation. This warranty is limited to
the repair or replacement of the defective unit.
There are no expressed warranties other than set forth herein. Honeywell Security
does not make, nor intends, nor does it authorize any agent or representative to
make any other warranties, or implied warranties, and expressly excludes and dis-
claims all implied warranties of merchantability or fitness for a particular purpose.
Returns must be accompanied by a Return Material Authorization (RMA) number
obtained from customer service, and prepaid postage and insurance.
Liability
The Interface should only be used to control exits from areas where an alternative
method for exit is available. This product is not intended for, nor is rated for opera-
tion in life-critical control applications. Honeywell Security is not liable under any
circumstances for loss or damage caused by or partially caused by the misapplica-
tion or malfunction of the product. Honeywell Security’s liability does not extend
beyond the purchase price of the product.
Dimension: 4.25 in. (108 mm) W x 2.75 in. (70 mm) L x 1 in. (25.4 mm) H
Weigh 4 oz. (120 g) nominal
Temperature: -55 to +85 °C, storage,
-40 to +75 °C, operating
Humidity: 5 to 95 % RHNC

10 Installation Guide, Document
(This page is intentionally left blank)

Table of contents
Other Honeywell Computer Hardware manuals

Honeywell
Honeywell 66 User manual

Honeywell
Honeywell NX series User manual

Honeywell
Honeywell PW7K1R1E Operator's manual

Honeywell
Honeywell RS-485 User manual

Honeywell
Honeywell GENT VSINTM-PCB-UPG User manual

Honeywell
Honeywell PX4ie User manual

Honeywell
Honeywell WEB-O3022H Operation manual

Honeywell
Honeywell HX3 User manual

Honeywell
Honeywell RM7838B Series User manual

Honeywell
Honeywell ALERTON AXM User manual