JADE™ ECONOMIZER MODULE
19 63-2700—01
Checkout Tests
Use the Checkout menu (Table 9) to test the damper operation
and any configured outputs. Only items that are configured are
shown in the Checkout menu.
NOTE: See “Interface Overview” on page 11. for information
about menu navigation and use of the keypad.
To perform a Checkout test:
1. Scroll to the desired test in the Checkout menu using the
and buttons.
2. Press the ↵button to select the item.
3. RUN? appears.
4. Press the ↵button to start the test.
5. The unit pauses and then displays IN PROGRESS.
6. When the test is complete, DONE appears.
7. When all parameters have been tested, press the
button (Menu up) to end the test (e.g. turn off the relay).
The checkout tests can all be performed at the time of
installation or any time during the operation of the system as a
test that the system is operable.
STATUS (continued) DA TEMP _ _._ ºF 0 to 140 ºF Displays when Discharge Air Sylk Bus sensor is
connected and displays measured discharge air
temperature.
Displays --.-°F if sensor sends invalid value, if not
connected, short or out-of-range.
OA TEMP _ _._ ºF -40 to 140 ºF Displays measured value of outdoor air temperature.
Displays --°F if sensor sends invalid value, if not
connected, short or out-of-range.
OA HUM _ _ % 0 to 100% Displays measured value of outdoor humidity from QA
Sylkbus sensor. Displays --% if not connected, short, or
out- of-range.
RA TEMP _ _._ ºF 0 to 140 ºF Displays measured value of return air temperature from
RAT sensor. Displays --°F if sensor sends invalid value, if
not connected, short or out-of-range.
RA HUM _ _ % 0 to 100% Displays measured value of return air humidity from RA
Sylkbus sensor. Displays --% if sensor sends invalid
value, if not connected, short or out-of-range.
IN CO2 _ _ _ ppm 0 to 2000 ppm Displays value of measured CO2 from CO2 sensor.
Invalid if not connected, short or out-of-range.
DCV STATUS n/a ON/OFF Displays ON if above setpoint and OFF if below setpoint,
and ONLY if a CO2 sensor is connected.
DAMPER OUT 2.0V 2.0 to 10.0 V Displays voltage output to the damper actuator.
EXH1 OUT OFF ON/OFF Output of EXH1 terminal.
ON = relay closed; OFF = relay open.
EXH2 OUT OFF ON/OFF Output of AUX terminal; displays only if AUX = EXH2
ERV OFF ON/OFF Output of AUX terminal; displays only if AUX = ERV
MECH COOL ON 0 0, 1, or 2 Displays stage of mechanical cooling that is active.
an/a = not applicable
Table 8. Status Menu. (Continued)
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment Notes
Table 9. Checkout Menu.
Checkout Item Checkout Test
DAMPER VMIN-HS Positions damper to VMIN position
DAMPER VMAX-HS Positions damper to VMAX position
DAMPER OPEN Positions damper to the full open position.
Exhaust fan contacts enable during the
DAMPER OPEN test. Make sure you pause in
this mode to allow for exhaust contacts to
energize due to the delay in the system.
DAMPER CLOSE Positions damper to the fully closed position.
CONNECT Y1-O Closes the Y1-O relay (Y1-O).
See CAUTION on this page
CONNECT Y2-O Closes the Y2-O relay (Y2-O).
See CAUTION on this page
CONNECT AUX Energizes the AUX output. If Aux setting is:
•NONE – no action taken
•ERV – 24 Vac out. Turns on or signals an
ERV that the conditions are not good for
economizing but are good for ERV
operation.a
•SYS – 24 Vac out. Issues a system alarm.