manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Control Unit
  8. •
  9. Honeywell Notifier FCM-1 User manual

Honeywell Notifier FCM-1 User manual

NO-460-004 4 I56-3500-008
©2013 Notifier
NO-460-004 1 I56-3500-008
FCM-1 Supervised Control Module
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
FCM-1 Supervised Control Modules are intended for use in intelligent, two-
wire systems, where the individual address of each module is selected us-
ing the built-in rotary switches. This module is used to switch an external
power supply, which can be a DC power supply or an audio amplifier (up
to 80 VRMS), to notification appliances. It also supervises the wiring to the
connected loads and reports their status to the panel as NORMAL, OPEN,
or SHORT CIRCUIT. The FCM-1 has two pairs of output termination points
available for fault-tolerant wiring and a panel-controlled LED indicator. This
module can be used to replace a CMX-2 module that has been configured for
supervised wiring operation.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Notifier system control panels only (list available from Notifier).
MOUNTING
The FCM-1 mounts directly to 4-inch square electrical boxes (see Figure 2A).
The box must have a minimum depth of 21/8inches. Surface mounted electri-
cal boxes (SMB500) are available. The module can also mount to the DNR(W)
duct housing.
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 6.5 mA (LED on)
Average Operating Current: 375µA (LED flashing - in group poll mode) 350µA (LED flashing - in direct poll mode); 485µA Max. (LED flashing, NAC shorted)
Maximum NAC Line Loss: 4 VDC
External Supply Voltage (between Terminals T10 and T11)
Maximum (NAC): Regulated 24 VDC
Maximum (Speakers): 70.7 V RMS, 50 W
Drain on External Supply: 1.7 mA Maximum using 24 VDC supply; 2.2 mA Maximum using 80 VRMS supply
Max NAC Current Ratings: For class B wiring system, the current rating is 3A; For class A wiring system, the current rating is 2A
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10% to 93% Non-condensing
Dimensions: 4.675˝ H x 4.275˝ W x 1.4˝ D (Mounts to a 4˝ square by 21
/8˝ deep box.)
Accessories: SMB500 Electrical Box; CB500 Barrier
I56-3500-008
INSTALLATION AND MAINTENANCE INSTRUCTIONS
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and reg-
ulations. When using control modules in nonpower limited applications, the
CB500 Module Barrier must be used to meet UL requirements for the separa-
tion of power-limited and nonpower-limited terminals and wiring. The barrier
must be inserted into a 4˝ × 4˝ × 21/8˝ junction box, and the control module
must be placed into the barrier and attached to the junction box (Figure 2A).
The power-limited wiring must be placed into the isolated quadrant of the
module barrier (Figure 2B).
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), see Figure 2A.
Wire should be stripped to the appropriate length (recommended strip length
is 1/4“ to 3/8”). Exposed conductor should be secured under the clamping plate
and should not protrude beyond the terminal block area.
CAUTION: Do not loop wire under terminals. Break wire run to provide su-
pervision of connections.
IMPORTANT: When using the FCM-1 for audio applications, remove Jumper
(J1) and discard. The Jumper is located on the back as shown in Figure 1B.
J1 must be removed whenever power supply monitoring feature is not required.
NOTE: All references to power limited represent “Power Limited (Class 2)”.
All references to Class A also include Class X.
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203.484.7161
RELAY CONTACT RATINGS:
CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION
2 A 25 VAC PF = 0.35 Non-coded
3 A 30 VDC Resistive Non-coded
2 A 30 VDC Resistive Coded
0.46 A 30 VDC (L/R = 20ms) Non-coded
0.7 A 70.7 VAC PF = 0.35 Non-coded
0.9 A 125 VDC Resistive Non-coded
0.5 A 125 VAC PF = 0.75 Non-coded
0.3 A 125 VAC PF = 0.35 Non-coded
FIGURE 6. TYPICAL FAULT TOLERANT WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE Z:
(+)
(–)
(+)
(–)
(+)
(–) (+)
(–)
(–)
(+)
(–)
(+)
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
TO NEXT
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
WIRES MUST BE SUPERVISED PER NFPA
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
FROM
PANEL OR
PREVIOUS
DEVICE
CONTROL
MODULE
SPEAKERS MUST BE LISTED FOR
FIRE PROTECTION.
47K EOL RESISTOR
IS INTERNAL AT
TERMINALS 8 & 9
MODULE POLARITIES ARE SHOWN IN ALARM
TO NEXT CONTROL
MODULE LAST MODULE
MUST RETURN WIRES FOR
SUPERVISION
SUPERVISION
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.
SEE NOTIFIER INST
ALLATION MANUAL FOR DETAILED INFORMATION.
AUDIO AMPLIFIER, 70.7 Vrms MAX.
USE ONLY MODELS AA-30, AA100 OR
AA-120. AMPLIFIER MUST PROVIDE
WIRING SUPERVISION PER NFPA.
AUDIO CIRCUIT
DO NOT LOOP WIRE AROUND TERMINALS 10 & 11.
BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
BYPASS CAPACITORS: 100µ
A2143-20 NONPOLARIZED
<10µA LEAKAGE
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C0950-02
WARNING
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
NO-460-004 3 I56-3500-008NO-460-004 2 I56-3500-008
FIGURE 4. TYPICAL FAULT TOLERANT NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA STYLE Z:
(+)
(–)
(+)
(–)
(+)
(–)
(–)
(+)
(–)
(+)
(+)
(–)
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
MODULE POLARITIES ARE
SHOWN IN ALARM
EOL RESISTOR
IS INTERNAL
AT TERMINALS
8 AND 9
UL LISTED EOL
RELAY SHOWN
ENERGIZED
24 VDC COIL
EOLR-1
TO NEXT CONTROL MODULE OR
END-OF-LINE RELAY. ONE RELAY
REQUIRED FOR EACH CIRCUIT. SOME
CONTROL PANELS HAVE RELAY BUILT
IN AND DO NOT REQUIRE EXTERNAL
WIRING. REFER TO PANEL MANUAL.
CONTROL
MODULE
TO NEXT
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL
PANELS ONLY
FROM PANEL
OR PREVIOUS
DEVICE
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10
& 11. BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER
NFPA 70. LISTED FOR
FIRE PROTECTION WITH
BATTERY BACKUP.
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C0948-00
FIGURE 3. TYPICAL NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA STYLE Y:
(+)
(+)
(+)
(+)
(+)
(+)
47K EOL
RESIST
OR
ELR-47K
UL LISTED EOL
RELAY SHOWN
ENERGIZED
24 VDC COIL
EOLR-1
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
TO NEXT CONTROL MODULE OR
END-OF-LINE RELAY. ONE RELAY
REQUIRED FOR EACH CIRCUIT. SOME
CONTROL PANELS HAVE RELAY BUILT
IN AND DO NOT REQUIRE EXTERNAL
WIRING. REFER TO PANEL MANUAL.
24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER NFPA 70.
LISTED FOR FIRE PROTECTION
WITH BATTERY BACKUP.
MODULE POLARITIES ARE
SHOWN IN ALARM
CONNECT MODULES TO
LISTED COMPATIBLE CONTROL
PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
CONTROL
MODULE
FROM PANEL
OR PREVIOUS
DEVICE
TO NEXT
DEVICE
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
(–) (–)
(–) (–)
(–)
(–)
C0947-00
FIGURE 5. TYPICAL WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE Y:
(+)
(–)
(+)
(–)
(+)
(–)
(–)
(+)
(–)
(+)
(+)
(–)
AUDIO CIRCUIT
DO NOT LOOP WIRE AROUND TERMINALS 10 & 11.
BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS
SUPERVISED AND POWER LIMITED
WIRES MUST BE SUPERVISED PER NFPA
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
FROM
PANEL OR
PREVIOUS
DEVICE
CONTROL
MODULE
47K EOL
RESISTOR
ELR-47K
SPEAKERS MUST
BE LISTED FOR FIRE PROTECTION.
TO NEXT
DEVICE
MODULE POLARITIES ARE
SHOWN IN ALARM
TO NEXT CONTROL MODULE
LAST MODULE MUST RETURN
WIRES FOR SUPERVISION
SUPERVISION
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.
SEE NOTIFIER INSTALLATION MANUAL FOR DETAILED INFORMATION.
AUDIO AMPLIFIER, 70.7 Vrms MAX.
USE ONLY MODELS AA-30, AA100 OR
AA-120. AMPLIFIER MUST PROVIDE
WIRING SUPERVISION PER NFPA.
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C0949-02
C1070-00
FIGURE 2A. MODULE MOUNTING FIGURE 2B:
WITH BARRIER:
FIGURE 1A: FIGURE 1B. JUMPER LOCATION:
J1
C1059-00 C0910-00

Other Honeywell Control Unit manuals

Honeywell RM7824A Operation manual

Honeywell

Honeywell RM7824A Operation manual

Honeywell IDENT KEY 3 User manual

Honeywell

Honeywell IDENT KEY 3 User manual

Honeywell DCCC6500 User manual

Honeywell

Honeywell DCCC6500 User manual

Honeywell NOTIFIER FCM-1A User manual

Honeywell

Honeywell NOTIFIER FCM-1A User manual

Honeywell ADEMCO 4204 User manual

Honeywell

Honeywell ADEMCO 4204 User manual

Honeywell S7800A1001 User manual

Honeywell

Honeywell S7800A1001 User manual

Honeywell PS300 User manual

Honeywell

Honeywell PS300 User manual

Honeywell TrueZONE ARD Series User manual

Honeywell

Honeywell TrueZONE ARD Series User manual

Honeywell VRN Series User manual

Honeywell

Honeywell VRN Series User manual

Honeywell V4730B User manual

Honeywell

Honeywell V4730B User manual

Honeywell NOTIFIER ASY-01-044-NIM User manual

Honeywell

Honeywell NOTIFIER ASY-01-044-NIM User manual

Honeywell 7800 SERIES User manual

Honeywell

Honeywell 7800 SERIES User manual

Honeywell D05FS User manual

Honeywell

Honeywell D05FS User manual

Honeywell Notifier NFG-8 User manual

Honeywell

Honeywell Notifier NFG-8 User manual

Honeywell SmartPAC 2 User manual

Honeywell

Honeywell SmartPAC 2 User manual

Honeywell SILENT KNIGHT SK-FML User manual

Honeywell

Honeywell SILENT KNIGHT SK-FML User manual

Honeywell T7560A User manual

Honeywell

Honeywell T7560A User manual

Honeywell RV284 User manual

Honeywell

Honeywell RV284 User manual

Honeywell M6410A Operation manual

Honeywell

Honeywell M6410A Operation manual

Honeywell 7800 SERIES User manual

Honeywell

Honeywell 7800 SERIES User manual

Honeywell 5800WAVE - Ademco Wireless Siren Assembly instructions

Honeywell

Honeywell 5800WAVE - Ademco Wireless Siren Assembly instructions

Honeywell RK-MCU Instruction sheet

Honeywell

Honeywell RK-MCU Instruction sheet

Honeywell VQ400 Series User manual

Honeywell

Honeywell VQ400 Series User manual

Honeywell Esser IQ8TAL User manual

Honeywell

Honeywell Esser IQ8TAL User manual

Popular Control Unit manuals by other brands

damixa 48408 Installation instruction

damixa

damixa 48408 Installation instruction

Humandata XP68-03 Series user manual

Humandata

Humandata XP68-03 Series user manual

Teletype 33 General description and operation

Teletype

Teletype 33 General description and operation

ADLINK Technology NuDAM-6017 user guide

ADLINK Technology

ADLINK Technology NuDAM-6017 user guide

Spitronics TCU Standard manual

Spitronics

Spitronics TCU Standard manual

INOXPA OVERFLOW VALVE Installation, service and maintenance instructions

INOXPA

INOXPA OVERFLOW VALVE Installation, service and maintenance instructions

Puls YR40.242 installation manual

Puls

Puls YR40.242 installation manual

Metso E2 Series Installation maintenance and operating instructions

Metso

Metso E2 Series Installation maintenance and operating instructions

Harman DBX 500 Series owner's manual

Harman

Harman DBX 500 Series owner's manual

Viega 8127.3 Instructions for use

Viega

Viega 8127.3 Instructions for use

Burkert 0406 operating instructions

Burkert

Burkert 0406 operating instructions

CodeMate 94008 manual

CodeMate

CodeMate 94008 manual

Teac ER-VRRC owner's manual

Teac

Teac ER-VRRC owner's manual

Penn System 450 Series installation guide

Penn

Penn System 450 Series installation guide

NXP Semiconductors TWR-PROTO quick start guide

NXP Semiconductors

NXP Semiconductors TWR-PROTO quick start guide

Idex Warren Rupp Sandpiper HDF3-M Service and operating manual

Idex

Idex Warren Rupp Sandpiper HDF3-M Service and operating manual

Microhard Systems HP900 operating manual

Microhard Systems

Microhard Systems HP900 operating manual

Lenze SM302 manual

Lenze

Lenze SM302 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.