manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Control Unit
  8. •
  9. Honeywell NOTIFIER XP6-MA User manual

Honeywell NOTIFIER XP6-MA User manual

BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The module housing should also be grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The XP6-MA Six Zone Interface Module is intended for use in an intelligent
alarm system. Each module provides an interface between the intelligent
alarm system and a conventional alarm system loop. A common SLC input is
used for all modules, and the initiating device loops share a common super-
visory supply and ground. Otherwise, each monitor operates independently
from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first module
from 01 to 154. The remaining modules are automatically assigned to the next
five higher addresses. Provisions are included for disabling a maximum of two
unused modules to release the addresses to be used elsewhere. Each mod-
ule also has panel controlled bicolor LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
A list of compatible two-wire System Sensor Smoke detectors for use with the
XP6-MA is available on the System Sensor website at www.systemsensor.com.
Included:
(5) 1 x 4 Terminal Blocks (2) 1.25" Stand offs (3) Shunts
(4) Machine Screws (2) Nuts (1) Long Power Supply Jumper
(6) 3.9k Ohm End of Line Resistors
C0202-00
Shipped on Board:
(2) Shunts in Class A/B position
(Shipped in Class B position, remove shunts for Class A)
1 I56-1806-010
7/1/2022
XP6-MA Six Zone Interface Module
SPECIFICATIONS
Normal Operating Voltage: 15-32VDC
Stand-By Current: 2.3 mA @ 24 V
Alarm Current: 40 mA (assumes all six LEDs solid on)
Temperature Range: 32ºF to 120ºF ( 0ºC to 49ºC)
Humidity: 10 to 93% Non-condensing
Dimensions: 6.8˝H x 5.8˝W x 1.25˝D
Accessories: CHS-6 Chassis; BB-25 Cabinet; BB-XP Cabinet; CAB-4 Series Cabinets; CAB-3 Series Cabinets
Wire Gauge: 12-18 AWG
Maximum IDC Wiring Resistance: 25 Ohms
External Power Supply Voltage: Regulated 24 VDC
Ripple Voltage: 0.1 volts RMS maximum
IDC (supervised and power limited)
DC Voltage: 18-28 volts power limited
Frequency: DC
Alarm Current: 90mA per circuit
Standby Current 6 circuits: 42mA Maximum @18 VDC
56mA Maximum @24 VDC
66mA Maximum @28 VDC
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Notifier system control panel (list available from Notifier).
COMPONENTS
Following are descriptions of the XP6-MA mounting frameworks. There are
two mounting options for XP6-MA modules:
• Up to six XP6-MA modules can be installed on a CHS-6 in a CAB-3
Series, CAB-4 Series or BB-25 cabinet
• One or two XP6-MA modules can be installed in a BB-XP cabinet
Chassis
The CHS-6 chassis is used to mount XP6-MA modules in a BB-25, CAB-3 or
CAB-4 Series cabinet. It accommodates up to six XP6-MA modules in a single
cabinet row three modules wide and two modules deep.
FIGURE 1. CHS-6 CHASSIS
MOUNT WITH
SELF-THREADING SCREWS
TO BACK OF CABINET
C0236-01
The BB-XP cabinet has a built-in chassis that will accommodate one or two
XP6-MA modules.
FIGURE 2. BB-XP CABINET
0
1
2
3
456789
0
78
6
5
4
3
21
910
11
12
13
14
15
BASEADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
0
1
2
3
456789
0
78
6
5
4
3
21
910
11
12
13
14
15
BASEADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
C0234-00
I56-1806-010
INSTALLATION AND MAINTENANCE INSTRUCTIONS
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203.484.7161
The steps in Figures 6A – 6C describe and illustrate module installation when
the rear chassis position and the position in front of it will be filled. Front
position installation is possible only if the rear position is filled with an XP
module.
FIGURE 6A. INSTALLATION OF XP6-MA MODULE IN A REAR CHASSIS
POSITION, METHOD TWO
1
C0225-01
Step 1: Install two long standoffs in the lower mounting holes using two 4-40
nuts as shown.
Step 2: Insert the bottom of the XP6-MA module down into a rear slot on the
chassis.
FIGURE 6B.
3
2
4
C0249-01
Step 3: Carefully swing the upper edge of the board back towards the back of
the chassis until it touches the two standoffs on the board.
Step 4: Align two 4-40 screws with the two standoffs on the chassis and
tighten.
Step 5: Address and wire the modules according to the instructions in this
manual.
FIGURE 6C. INSTALLATION OF XP6-MA MODULE IN FRONT CHASSIS
POSITION
2
3
1
C0226-01
Step 1: Insert the bottom edge of the XP6-MA module down into a front slot
of the chassis.
Step 2: Carefully swing the upper edge of the board towards the back of the
chassis until it touches the 1.25" (32 mm) standoffs installed on the
rear module.
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to the instructions in this
manual.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. All wiring to the XP6-MA is done via terminal blocks. In order to prop-
erly make electrical connections strip approximately 0.25˝ of insulation
The front XP6-MA module positions of each chassis are offset below the rear
XP6-MA module positions so that all of the status indicators are visible.
Cabinets
A BB-25, CAB-3 or CAB-4 Series cabinet will house the CHS-6 chassis with up
to six XP6-MA modules installed on it. Refer to cabinet installation documents
for dimensions.
The BB-XP cabinet houses one or two XP6-MA modules on the internal chas-
sis that is part of the cabinet. Refer to cabinet installation documents for
dimensions.
INSTALLATION STEPS
1. Cabinet Mounting
In a clean, dry area, mount the backbox using the four holes provided in
the back surface of the cabinet (Figure 3).
2. Chassis Installation
The CHS-6 chassis is mounted in the BB-25, CAB-3 or CAB-4 Series cabi-
net. It is shipped with two self-threading screws, which are used to fas-
ten the chassis to the back wall of the cabinet (Figure 4).
FIGURE 3. TYPICAL MOUNTING HOLE LOCATIONS
BACKBOX
MOUNTING
HOLES
C0235-00
FIGURE 4. MOUNTING THE CHS-6 CHASSIS
MOUNT WITH
SELF-THREADING SCREWS
TO BACK OF CABINET
C0236-00
The BB-XP cabinet comes with the chassis already installed, so no mounting
is necessary.
3. Module Installation
There are two methods for installing a module in the rear position of a chas-
sis. Method one is for installation of a rear module only, when no module will
be installed in front of it. Refer to Figure 5 for instructions. Method two is for
installation of a rear module when another module will be installed in the
chassis position in front of it. Refer to Figures 6a and 6b for method two. All
necessary screws and standoffs are supplied with the modules.
FIGURE 5. INSTALLATION OF REAR MODULE ONLY, METHOD ONE
2
3
1
C0237-00
Step 1: Insert the bottom of the XP6-MA module down into a rear slot on the
chassis.
Step 2: Carefully swing the upper edge of the board back towards the back of
the chassis until it touches the two standoffs.
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to the instructions in this
manual.
2 I56-1806-010
7/1/2022
NOTE: Power must not be applied to the unit when changing functionality on
the shunts.
WIRING NOTES
• Power-limited circuits must employ type FPL, FPLR, or FPLP cable as
required by Article 760 of the NEC.
• All wiring must be in accordance with the NEC, NFPA 72 and all other
applicable codes and standards. All external power supplies must be
power limited with battery back-up. All external power supplies and
detectors must be UL listed for fire protection signaling applications.
PROGRAMMING
Connect the module to listed-compatible control panels only. Refer to panel
installation documentation to confirm compatibility.
The modules are programmed as devices in each system according to the pro-
gramming instructions in the appropriate FACP manual.
FIGURE 7.
TENS
0
78
6
5
4
3
21
910
11
12
13
14
15
C0227-00
3 I56-1806-010
7/1/2022
from the end of wire, sliding the bare end of the wire under the clamping
plate screw.
3. Set the address on the modules per the job drawing. Use the rotary code
switches to set the address of the first module (between 01 and 154).
In Class B operation, the remaining modules are automatically assigned to the
next five higher addresses. For example, if the base address switch is set to 28,
the next five modules will be addressed to 29, 30, 31, 32 and 33.
The module is shipped in Class B position, remove shunts for Class A. When
operating in Class A, alternate modules are paired together (+0/+1, +2/+3,
+4/+5), resulting in a total of three modules. For example, if the base ad-
dress switch is set to 28, then 30 and 32 will be automatically assigned to the
modules while 29, 31 and 33 are available to be used for other modules on the
SLC. For Class A and B operation, DO NOT set the lowest address above 154,
as the other modules will be assigned to nonexistent addresses.
NOTE: The XP6-MA must have power cycled for shunt changes to take effect.
NOTE: Some panels support extended addressing. In order to set the module
above address 99 on compatible systems, carefully remove the stop on the
upper rotary switch (see Figure 7). If the panel does not support extended ad-
dressing, do not set the lowest address above 94.
4. A shunt is provided to disable a maximum of two unused modules in
Class B operation and Class A operation. Modules are disabled from the
highest address and work downward. If two modules are disabled, the
lowest four addresses will be functional, while the highest two will be
disabled. For example, in Class B operation, if the shunt for Address Dis-
able is placed on “two” and the base switch is set to 28, the modules will
be assigned to 28, 29, 30 and 31 while disabling the highest two positions.
NOTE: Place unused shunts on single pin to store on board for future use.
0
1
2
3
456789
BASE ADDRESS
TO NEXT DEVICE
–
STATUS
INDICATORS
—
+
—
+
+0
+1
IDC
ADDRESS
—
+
—
+
+2
+3
IDC
ADDRESS
—
+
—
+
+4
+5
IDC
ADDRESS
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
3.9K EOL
RESISTOR
(INCLUDED)
CONNECT MODULES TO
LISTED COMPATIBLE
NOTIFIER CONTROL
PANELS ONLY
SIGNAL LINE CIRCUIT 32 VDC MAX.
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
CLASS B IDC (TYPICAL)
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
+
–
+
–
T6 T5
DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE.
INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
(–)
(+)
IN
OUT
—
+
—
+
EXTERNAL SUPPLY
0
1
2
3
456789
POWER-LIMITED
AND SUPERVISED
POWER TO THE NEXT INTERFACE
MODULE MUST BE EXTERNALLY
SWITCHED TO RESET THE DETECTORS.
AN FRM-1 RELAY CONTROL MODULE CAN BE
USED TO SWITCH POWER FROM A
STANDARD POWER SUPPLY. SEE FIGUR 10.
1. To use a common power supply between multiple XP6-MA modules, connect a long power supply jumper from T5 or T6 to T5 or
T6 on the adjacent XP6-MA module.
FIGURE 8. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS B
C0154-02
FIGURE 9. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS A
0
1
2
3
456789
BASE ADDRESS
TO NEXT DEVICE
–
STATUS
INDICATORS
—
+
—
+
+0
+1
IDC
ADDRESS
—
+
—
+
+2
+3
IDC
ADDRESS
—
+
—
+
+4
+5
IDC
ADDRESS
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO LISTED COMPATIBLE
NOTIFIER CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT 32 VDC MAX.
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
CLASS A IDC (TYPICAL)
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
0
1
2
3
45678910
11
12
13
14
15
++
IDC 2
IDC 3
(–)
(+)
POWER TO THE NEXT INTERFACE
MODULE MUST BE EXTERNALLY
SWITCHED TO RESET THE DETECTORS.
AN FRM-1 RELAY CONTROL MODULE CAN BE
USED TO SWITCH POWER FROM A
STANDARD POWER SUPPLY. SEE FIGURE 10.
T6 T5
IN
OUT
—
+
—
+
EXTERNAL SUPPLY
POWER-LIMITED
AND SUPERVISED
––
Detectors must be UL Listed compatible with the module. Install detectors
per manufacturer’s installation instructions.
C0160-01
1. To select Class A, remove the
two shunts from the “A/B se-
lect” positions.
2. To use a common power
supply between multiple
XP6-MA modules, connect
a long power supply jumper
from T5 or T6 to T5 or T6 on
the adjacent XP6-MA mod-
ule.
FIGURE 10. RELAY CONTROL MODULE USED TO DISCONNECT A POWER SUPPLY
C0248-00
FIGURE 11. EXAMPLE OF MULTIPLE BOARDS SHARING SAME EXTERNAL SUPPLY
Refer to figures 8 and 9 for typical wiring. Make certain lip on long power supply jumper engages retaining tab on T5 or T6 as shown in View A-A:
C0142-00
4 I56-1806-010
©2022 Notifier. 7/1/2022
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
FCC STATEMENT
DEVICE AND SYSTEM SECURITY
Before installing this product ensure that the tamper seal on the packaging is present and unbroken and the product has not been tampered with since leaving the factory.
Do not install this product if there are any indications of tampering. If there are any signs of tampering the product should be returned to the point of purchase.
It is the responsibility of the system owner to ensure that all system components, i.e. devices, panels, wiring etc., are adequately protected to avoid tampering of the system
that could result in information disclosure, spoofing, and integrity violation.
NOTIFIER®is a registered trademark of Honeywell International, Inc.

Other Honeywell Control Unit manuals

Honeywell TM300 User manual

Honeywell

Honeywell TM300 User manual

Honeywell VP522A User manual

Honeywell

Honeywell VP522A User manual

Honeywell NOTIFIER M701E User manual

Honeywell

Honeywell NOTIFIER M701E User manual

Honeywell 7800 SERIES Operation manual

Honeywell

Honeywell 7800 SERIES Operation manual

Honeywell V1810 Alwa-Kombi-4 User manual

Honeywell

Honeywell V1810 Alwa-Kombi-4 User manual

Honeywell EXCEL 5000 OPEN T7460A User manual

Honeywell

Honeywell EXCEL 5000 OPEN T7460A User manual

Honeywell V48F User manual

Honeywell

Honeywell V48F User manual

Honeywell RV181 User manual

Honeywell

Honeywell RV181 User manual

Honeywell CR7075 Operation manual

Honeywell

Honeywell CR7075 Operation manual

Honeywell Aquatrol W964F Owner's manual

Honeywell

Honeywell Aquatrol W964F Owner's manual

Honeywell Maxon SMA11 User manual

Honeywell

Honeywell Maxon SMA11 User manual

Honeywell PW6K1R1E Operator's manual

Honeywell

Honeywell PW6K1R1E Operator's manual

Honeywell Y8610U Operation manual

Honeywell

Honeywell Y8610U Operation manual

Honeywell VHL120 Guide

Honeywell

Honeywell VHL120 Guide

Honeywell CA295 User manual

Honeywell

Honeywell CA295 User manual

Honeywell CentraLine CLCM1T User manual

Honeywell

Honeywell CentraLine CLCM1T User manual

Honeywell EXCEL CARE 5000 User manual

Honeywell

Honeywell EXCEL CARE 5000 User manual

Honeywell LYNXDM-GSM Assembly instructions

Honeywell

Honeywell LYNXDM-GSM Assembly instructions

Honeywell W8735ER User manual

Honeywell

Honeywell W8735ER User manual

Honeywell Fire-lite FFT User manual

Honeywell

Honeywell Fire-lite FFT User manual

Honeywell VR8200A User manual

Honeywell

Honeywell VR8200A User manual

Honeywell S8910U Original instructions

Honeywell

Honeywell S8910U Original instructions

Honeywell Braukmann BV300 User manual

Honeywell

Honeywell Braukmann BV300 User manual

Honeywell MAXON 8730 Series User manual

Honeywell

Honeywell MAXON 8730 Series User manual

Popular Control Unit manuals by other brands

AAON RSMVQ Technical guide

AAON

AAON RSMVQ Technical guide

ADC HiGain H2TU-R-402 List 6 Quick installation

ADC

ADC HiGain H2TU-R-402 List 6 Quick installation

Emerson Anderson Greenwood 500 Series Installation and maintenance instructions

Emerson

Emerson Anderson Greenwood 500 Series Installation and maintenance instructions

BENDIX E-7 DUAL BRAKE VALVE manual

BENDIX

BENDIX E-7 DUAL BRAKE VALVE manual

Analog Devices ADP5520 manual

Analog Devices

Analog Devices ADP5520 manual

WAGO 753-646 manual

WAGO

WAGO 753-646 manual

ATI Technologies SC29 manual

ATI Technologies

ATI Technologies SC29 manual

Texas Instruments DRV10964 user guide

Texas Instruments

Texas Instruments DRV10964 user guide

Tecomat Foxtrot CP-1000 manual

Tecomat

Tecomat Foxtrot CP-1000 manual

Tadao Musashi 3 Upgrade

Tadao

Tadao Musashi 3 Upgrade

Belden GRASS VALLEY AMX-1901 Guide to installation and operation

Belden

Belden GRASS VALLEY AMX-1901 Guide to installation and operation

Festo Pneumatic MPZ-1-24 operating instructions

Festo Pneumatic

Festo Pneumatic MPZ-1-24 operating instructions

Nice UST1K Instructions and information for installation and use

Nice

Nice UST1K Instructions and information for installation and use

ARAG IBX100 4679004 Installation, use and maintenance

ARAG

ARAG IBX100 4679004 Installation, use and maintenance

DUSKWORK VCO V2 Build guide

DUSKWORK

DUSKWORK VCO V2 Build guide

HAWE Hydraulik CDK Series Product documentation

HAWE Hydraulik

HAWE Hydraulik CDK Series Product documentation

Flowserve Valtek Mark Six Installation, operation & maintenance instructions

Flowserve

Flowserve Valtek Mark Six Installation, operation & maintenance instructions

Flowserve NAF-Setball Maintenance and installation instructions

Flowserve

Flowserve NAF-Setball Maintenance and installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.