AOM-2SF Supervised Control Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
AOM-2SF Supervised Control Modules are intended for use in intelligent, two-
wire systems, where the individual address of each module is selected us-
ing the built-in rotary switches. This module is used to switch an external
power supply, which can be a DC power supply or an audio amplifier (up
to 80 VRMS), to notification appliances. It also supervises the wiring to the
connected loads and reports their status to the panel as NORMAL, OPEN, or
SHORT CIRCUIT. The AOM-2SF has two pairs of output termination points
available for fault-tolerant wiring and a panel-controlled LED indicator.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Gamewell-FCI system control panels only (list available from Gamewell-FCI).
MOUNTING
The AOM-2SF mounts directly to 4-inch square electrical boxes (see Figure
2A). The box must have a minimum depth of 21/8inches. Surface mounted
electrical boxes (SMB500) are available. The module can also mount to the
DNR(W) housing.
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 6.5 mA (LED on)
Average Operating Current: 375µA (LED flashing - in Velociti Mode); 350µA (LED flashing - in CLIP mode)
Maximum NAC Line Loss: 4 VDC
External Supply Voltage (between Terminals T10 and T11)
Maximum (NAC): Regulated 24 VDC
Maximum (Speakers): 70.7 V RMs, 50W
Drain on External Supply: 1.7 mA Maximum using 24 VDC supply; 2.2 mA Maximum using 80 VRMS supply
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10% to 93% Non-condensing
Dimensions: 4.675” H x 4.275” W x 1.4” D (Mounts to a 4˝ square by 21/8˝ deep box.)
Accessories: SMB500 Electrical Box; CB500 Barrier
I56-3550-008
Velociti ®Series
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and reg-
ulations. When using control modules in nonpower limited applications, the
CB500 Module Barrier must be used to meet UL requirements for the separa-
tion of power-limited and nonpower-limited terminals and wiring. The barrier
must be inserted into a 4˝ × 4˝ × 21/8˝ junction box, and the control module
must be placed into the barrier and attached to the junction box (Figure 2A).
The power-limited wiring must be placed into the isolated quadrant of the
module barrier (Figure 2B).
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), see Figure 2A.
Wire should be stripped to the appropriate length (recommended strip length
is 1/4“ to 3/8”). Exposed conductor should be secured under the clamping plate
and should not protrude beyond the terminal block area. Caution: Do not loop
wire under terminals. Break wire run to provide supervision of connections.
IMPORTANT: When using the AOM-2SF for audio applications, remove Jumper
(J1) and discard. The Jumper is located on the back as shown in Figure 1B. J1
must be removed whenever power supply monitoring feature is not required.
NOTE: All references to power limited represent “Power Limited (Class 2)”.
All references to Class A also include Class X.
RELAY CONTACT RATINGS:
CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION
2 A 25 VAC PF = 0.35 Non-coded
3 A 30 VDC Resistive Non-coded
2 A 30 VDC Resistive Coded
0.46 A 30 VDC (L/R = 20ms) Non-coded
0.7 A 70.7 VAC PF = 0.35 Non-coded
0.9 A 125 VDC Resistive Non-coded
0.5 A 125 VAC PF = 0.75 Non-coded
0.3 A 125 VAC PF = 0.35 Non-coded
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203.484.7161;
Fax: 203.484.7118
www.gamewell-fci.com
1 I56-3550-008
06/19/2018
FIGURE 1A: FIGURE 1B. JUMPER LOCATION:
J1
C1059-00 C0910-00
FIGURE 2A. MODULE MOUNTING FIGURE 2B:
WITH BARRIER:
C1070-00
2 I56-3550-008
06/19/2018
FIGURE 3. TYPICAL NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA STYLE Y:
(+)
(+)
(+)
(+)
(+)
(+)
47K EOL
RESIST
OR
ELR-47K
UL LISTED EOL
RELAY SHOWN
ENERGIZED
24 VDC COIL
EOLR-1
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
TO NEXT CONTROL MODULE OR
END-OF-LINE RELAY. ONE RELAY
REQUIRED FOR EACH CIRCUIT. SOME
CONTROL PANELS HAVE RELAY BUILT
IN AND DO NOT REQUIRE EXTERNAL
WIRING. REFER TO PANEL MANUAL.
24 VDC POWER SUPPLY
ISOLATED, REGULATED, POWER
LIMITED PER NFPA 70. LISTED
FOR FIRE PROTECTION WITH
BATTERY BACKUP.
MODULE POLARITIES
ARE SHOWN IN ALARM
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
CONTROL
MODULE
FROM
PANEL OR
PREVIOUS
DEVICE
TO NEXT
DEVICE
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
(–) (–)
(–)
(–)
(–)
(–)
C1017-00
FIGURE 4. TYPICAL FAULT TOLERANT NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA STYLE Z:
(+)
(–)
(+)
(–)
(+)
(–)
(–)
(+)
(–)
(+)
(+)
(–)
ALL WIRING SHOWN IS
SUPERVISED AND POWER LIMITED
MODULE POLARITIES
ARE SHOWN IN ALARM
EOL
RESIST
OR IS
INTERNAL
AT
TERMINALS
8 & 9
UL LISTED EOL
RELAY SHOWN
ENERGIZED
24 VDC COIL
EOLR-1
TO NEXT CONTROL MODULE OR
END-OF-LINE RELAY. ONE RELAY
REQUIRED FOR EACH CIRCUIT. SOME
CONTROL PANELS HAVE RELAY BUILT
IN AND DO NOT REQUIRE EXTERNAL
WIRING. REFER TO PANEL MANUAL.
CONTROL
MODULE
TO NEXT
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
CONNECT MODULES TO
LISTED COMPATIBLE
CONTROL PANELS ONLY
FROM
PANEL OR
PREVIOUS
DEVICE
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER
NFPA 70. LISTED FOR
FIRE PROTECTION WITH
BATTERY BACKUP.
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C1018-00
3 I56-3550-008
06/19/2018
FIGURE 5. TYPICAL WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE Y:
(+)
(–)
(+)
(–)
(+)
(–)
(–)
(+)
(–)
(+)
(+)
(–)
AUDIO CIRCUIT
DO NOT LOOP WIRE AROUND TERMINALS 10 &
11. BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
WIRES MUST BE SUPERVISED PER NFPA
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY
FROM
PANEL OR
PREVIOUS
DEVICE
CONTROL
MODULE
47K EOL
RESISTOR
ELR-47K
SPEAKERS MUST BE LISTED
FOR FIRE PROTECTION.
TO NEXT
DEVICE
MODULE POLARITIES ARE
SHOWN IN ALARM
TO NEXT CONTROL MODULE
LAST MODULE MUST RETURN
WIRES FOR SUPERVISION
SUPERVISION
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.
SEE INSTALLATION MANUAL FOR DETAILED INFORMATION.
AUDIO AMPLIFIER, 70.7 Vrms MAX.
USE ONLY MODELS AM-50, AM-50-70, AA100
OR AA-120. AMPLIFIER MUST PROVIDE
WIRING SUPERVISION PER NFPA.
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C1016-01
FIGURE 6. TYPICAL FAULT TOLERANT WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE Z:
(+)
(–)
(+)
(–)
(+)
(–) (+)
(–)
(–)
(+)
(–)
(+)
ALL WIRING SHOWN IS SUPER
VISED
AND POWER LIMITED
TO NEXT
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
WIRES MUST BE SUPERVISED PER NFPA
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY
FROM
PANEL OR
PREVIOUS
DEVICE
CONTROL
MODULE
SPEAKERS MUST BE LISTED
FOR FIRE PROTECTION.
47K EOL RESISTOR
IS INTERNAL AT
TERMINALS 8 & 9
MODULE POLARITIES ARE
SHOWN IN ALARM
TO NEXT CONTROL MODULE
LAST MODULE MUST RETURN
WIRES FOR SUPERVISION
SUPERVISION
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.
SEE YOUR PANEL’S SLC WIRING DOCUMENTAT ION FOR DETA ILS.
AUDIO AMPLIFIER, 70.7 Vrms MAX.
USE ONLY MODELS AM-50, AM-50-70, AA100
OR AA-120. AMPLIFIER MUST PROVIDE
WIRING SUPERVISION PER NFPA .
AUDIO CIRCUIT
DO NOT LOOP WIRE AROUND TERMINALS 10 & 11. BREAK WIRE TO
ENSURE SUPERVISION OF CONNECTIONS.
BYPASS CAPACITORS: 100µ
A2143-20 NONPOLARIZED
<10µA LEAKAGE
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C1024-02
WARNING
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
4 I56-3550-008
©2018 Honeywell. 06/19/2018
Velociti®, Gamewell-FCI®, System Sensor®, and Honeywell®are registered trademarks of Honeywell International, Inc.

This manual suits for next models

1

Other Honeywell Control Unit manuals

Honeywell CR7075 Operation manual

Honeywell

Honeywell CR7075 Operation manual

Honeywell Exi-/MaxLED T2 User manual

Honeywell

Honeywell Exi-/MaxLED T2 User manual

Honeywell Esser 2 Series User manual

Honeywell

Honeywell Esser 2 Series User manual

Honeywell V5004TF User manual

Honeywell

Honeywell V5004TF User manual

Honeywell JADE W7220 Operation manual

Honeywell

Honeywell JADE W7220 Operation manual

Honeywell FF-SRM200P2 User manual

Honeywell

Honeywell FF-SRM200P2 User manual

Honeywell DS06D Operation manual

Honeywell

Honeywell DS06D Operation manual

Honeywell NOTIFIER FTM-1 User manual

Honeywell

Honeywell NOTIFIER FTM-1 User manual

Honeywell RF CM61NG User manual

Honeywell

Honeywell RF CM61NG User manual

Honeywell UCIP-GPRS User manual

Honeywell

Honeywell UCIP-GPRS User manual

Honeywell NK295C User manual

Honeywell

Honeywell NK295C User manual

Honeywell FF-SRS5988 User manual

Honeywell

Honeywell FF-SRS5988 User manual

Honeywell S7800A1001 User manual

Honeywell

Honeywell S7800A1001 User manual

Honeywell V5197A1011 Operation manual

Honeywell

Honeywell V5197A1011 Operation manual

Honeywell Silent Knight IDP-Monitor-2 User manual

Honeywell

Honeywell Silent Knight IDP-Monitor-2 User manual

Honeywell 7800 SERIES User manual

Honeywell

Honeywell 7800 SERIES User manual

Honeywell VC7900 Series Operation manual

Honeywell

Honeywell VC7900 Series Operation manual

Honeywell 7800 SERIES Operation manual

Honeywell

Honeywell 7800 SERIES Operation manual

Honeywell IntelliDoX User manual

Honeywell

Honeywell IntelliDoX User manual

Honeywell Notifier NFG-8 User manual

Honeywell

Honeywell Notifier NFG-8 User manual

Honeywell MCV2000AA Installation instructions

Honeywell

Honeywell MCV2000AA Installation instructions

Honeywell VRW2 User manual

Honeywell

Honeywell VRW2 User manual

Honeywell satronic DMG 971 Instructions for use

Honeywell

Honeywell satronic DMG 971 Instructions for use

Honeywell PRO3200 User manual

Honeywell

Honeywell PRO3200 User manual

Popular Control Unit manuals by other brands

Victaulic 867-4UF Installation, operation and maintenance manual

Victaulic

Victaulic 867-4UF Installation, operation and maintenance manual

iNels RFATV-2 manual

iNels

iNels RFATV-2 manual

Siemens SIMATIC ET 200SP manual

Siemens

Siemens SIMATIC ET 200SP manual

Burkert 6038 quick start guide

Burkert

Burkert 6038 quick start guide

NewMar BMS-19/23 Installation & operation manual

NewMar

NewMar BMS-19/23 Installation & operation manual

Hasco H1281-6 operating instructions

Hasco

Hasco H1281-6 operating instructions

Infineon TLE9262-3BQX manual

Infineon

Infineon TLE9262-3BQX manual

claber Hydro 4 Use and installation  manual

claber

claber Hydro 4 Use and installation manual

YASKAWA SLIO CP 042-1IO00 manual

YASKAWA

YASKAWA SLIO CP 042-1IO00 manual

Siemens SIMATIC ET 200SP manual

Siemens

Siemens SIMATIC ET 200SP manual

Burkert AirLINE 8652 Series operating instructions

Burkert

Burkert AirLINE 8652 Series operating instructions

HID ACW2-XN Quick install guide

HID

HID ACW2-XN Quick install guide

Bosch MP 100 Installation instruction

Bosch

Bosch MP 100 Installation instruction

Xilica Audio Design XTouch Series: XTouch50 user manual

Xilica Audio Design

Xilica Audio Design XTouch Series: XTouch50 user manual

Ross HBB Series operating instructions

Ross

Ross HBB Series operating instructions

Siemens SIMATIC IM 151/CPU manual

Siemens

Siemens SIMATIC IM 151/CPU manual

Texas Instruments BIOSUSB user guide

Texas Instruments

Texas Instruments BIOSUSB user guide

IBA ibaMS8xAI-110VAC manual

IBA

IBA ibaMS8xAI-110VAC manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.