11.2 Perfomance characteristics
Opening time:
Dead time maximum 1 second.
VR434: maximum dead time <0,5 second.
The first valve (V1) opens in less than 1 second.
The second valve (V2) can be either a fast opening,
or slow opening valve with adjustable characteristic
(VR..XB and VR..XF models).
Maximum allowable leakage:
Each VR400 combination valve has been factory
tested to meet the following leakage requirements.
Outerwall, safety valve and main valve = 40 cm3/h
for up to DN 25 and 50 cm3/h for DN 32 at test
pressure of 6mbar and 1.5 x maximum operating
pressure.
High pressure test:
In the “OFF” condition, the VR400 valve will with-
stand 1,5bar (air) inlet pressure without damage.
Closing time (V1, V2):
Less than 1 second for all valves.
Maximum working frequency:
1 cycle per minute.
Duty cycle:
Coil suitable for permanent energization in coopera-
tion with ignition controller.
Operational voltage range:
The combination gas valve will function satisfactory
between 85% and 110% of the rated voltage.
11.3 Pressure regulator
Which reaches 50% of the adjustable outlet
pressure within 0,5 seconds after start flow or a
characterized opening valve which is adjustable
from 1 up to 30 seconds, at rated capacity. The
opening characteristic is factory set at approximate-
ly 6 seconds at the following conditions:
– measured at 80% of rated capacity
– 30mbar supply pressure
– nominal voltage
– 20°C
– 2,5mbar pressure drop
– no step pressure
Due to the influence of ambient temperature (-15
to +60°C) the adjusted opening time of 6 seconds
measured at 80% of adjusted flow rate can vary ± 4
seconds.
Tap sensitivity of outlet pressure set point:
For all gases the maximum deviation may be 1mbar.
Repeatability of outlet pressure set point:
For all gases the maximum deviation from set point
is ± 0,3mbar or + 3% of the set point value, which-
ever is the greatest.
Total set point shift
Pressure range
(mbar) Tolerance
3–37
6% of the set point value or
1mbar whichever is the
greatest
11.4 Hi-lo regulator
Pressure feedback connection:
The high–low regulator with an M5 thread connec-
tion for pressure feedback.
Minimum regulation capacity:
0,31m3/h
Maximum operating pressure:
The maximum pressure Pmax. indication on the
housing of the combination gas control is the maxi-
mum pressure at which it functions safely.
However, the maximum operating pressure is limited
by the pressure range of the high–low pressure reg-
ulator concerned: 50mbar for pressure range 4–37.
Electrical connection:
The high–low coil is provided with an earth terminal.
The high–low coil is provided with quick connect
terminals suitable for 6,3mm.
Connector: DIN43650 From B
Regulator output pressure range:
Pressure
range
(mbar)
Setting
low high
4–37 4 - Pmax (Pmax < Phigh) 12–37
Electrical data:
Supply
voltage
Color of
coil
Current
(mA)
Power
consump-
tion
220/240V~,
50Hz black 17,4/19 3/3,2
11.4.1 Performance hi-lo regulator
Maximum allowable leakage:
Each hi-lo regulator has been factory tested to meet
the following leakage requirements.
– outerwall: 24 cm3/h at test pressure of 150mbar.
– seat leakage: 110 cm3/h at test pressure of
9mbar.
– pressure feedback leakage: 650 cm3/h at test
pressure of 8mbar.
Total set point shift:
The total set point shift of the low and the high outlet
pressure caused by repeatability, tapping (tapping
impact 2Ncm) and life cycle shall not exceed.
Pressure range
(mbar)
Min. low
setting
(mbar)
Max high
setting
(mbar)
4–37 -2,5/+2,5 -4,0/+3,0
Repeatability:
Repeatability should checked after five power inter-
ruptions, maximum deviation in outlet pressure may
not exceed the values as indicated below.
Pressure range
(mbar)
At min. set
point (mbar)
At max. set
point (mbar)
4–37 0,5 1
Tap test:
After tapping the control (tapping impact 2Ncm
max.) the deviation of the outlet pressure may be
1mbar max.