manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Switch
  8. •
  9. Honeywell KSL Series Operation manual

Honeywell KSL Series Operation manual

® U.S. Registered Trademark EN0B-0757GE51 R0617
Copyright © 2017 Honeywell Inc. ▪All Rights Reserved
KSL
Compact Electronic Air Flow Switch
PRODUCT DATA
GENERAL
These highly reliable compact electronic flow switches are
designed for detecting air flow in ducts or pipes.
The device's sensitivity is adjusted using a potentiometer.
When the air flow speed reaches a customer-preselected
threshold value (switchpoint), the device switches an
electronic circuit. The switching state is indicated by an LED.
FEATURES
▪PG7 connection for easy mounting directly to ducts.
▪No moveable parts in the detection zone.
▪Temperature-compensated operating range.
▪Highly resistant to contamination and corrosion.
DIMENSIONS
56
10
15
140
82
47
Ø 10
21.5
47
PG7
TIGHTENING
SCREW
DEPRESSION
INDICATING
DIRECTION OF
FLOW
CIRCULAR
MOUNTING
BRACKET
Ø 4 mm
M16x1.5
LATERAL
HOLE
CENTRIC
HOLE
Fig. 1. KSL, dimensions (mm)
SPECIFICATIONS
Type KSL-230 KSL-24
Media air air
Power supply 230/240 VAC ±10% 24 VAC/DC ±10%
Power indication green "voltage" LED green "voltage" LED
Power consump. 4 VA 4 VA
Ambient temp. -20 ... +60 °C -20 ... +60 °C
Medium temp. -10 ... +80 °C -10 ... +80 °C
Relay contact SPDT SPDT
Contact load 250 VAC, 10(2) A 250 VAC, 10(2) A
Switch indication yellow "air flow" LED yellow "air flow" LED
60-sec electrical
outage protection ON/OFF (jumper) ON/OFF (jumper)
Outage prot. ind. Yellow "time" LED Yellow "time" LED
Setpt. adjustment potentiometer potentiometer
Range 0.1 … 30 m/sec 0.1 … 30 m/sec
Response time 1…10 sec 1…10 sec
Immersion depth 130 mm 130 mm
Max. pressure 10 bar 10 bar
Process connec-
tion
PG7 + circular
mounting bracket
PG7 + circular
mounting bracket
Housing IP IP 65 IP 65
Sensor IP IP 67 IP 67
Protection class II II
Wiring terminals 5 x 2.5 mm25 x 2.5 mm2
Probe material MS58 nickel-plated MS58 nickel-plated
Weight 400 g 400 g
MOUNTING
▪Select a mounting location in an area of calm flow.
Specifically, the device should not be mounted
immediately upstream or downstream from bends
(upstream calming distance = approx. 5X the duct
diameter; downstream calming distance = approx. 3X the
duct diameter). Vertical and horizontal mounting possible.
▪After selecting an appropriate mounting location, securely
fix the circular mounting bracket into place on the duct
using at least two screws.
▪Now slide the probe through the 10-mm centric hole in the
circular mounting bracket until the tip of the probe is at the
proper depth (in the middle of the duct).
▪Rotate the device to ensure that the air flows through the
lateral opening at the tip of the probe. Specifically, the
small depression (see Fig. 1) should face towards the
oncoming air.
▪Finally, securely fix the device in place using the
tightening screw (see Fig. 1).
▪Maintenance: The sensor should be cleaned regularly by
immersion in soapy warm water for about 10 minutes
under warm water flow using a clean rag. Do not use
screwdrivers or other hard tools to clean the sensor!
KSL COMPACT ELECTRONIC AIR FLOW SWITCH – PRODUCT DATA
Manufactured for and on behalf of the Environmental & Energy Solution Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Home and Building Technologies
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich, Germany
Phone: (49) 7031 63701
Fax: (49) 7031 637493
http://ecc.emea.honeywell.com
Subject to change without notice. Printed in Germany
EN0B-0757GE51 R0617
FIELD WIRING
In the case of 230 VAC or 24 VAC power supply, connect the
power supply to terminals L (+) and N (-).
In the case of 24 VDC power supply, connect common 15,
normally-closed 16, and normally-open 18, accordingly.
16 15 18
L(+) N(-)
Fig. 2. Wiring diagram
NOTE: To ensure IP rating, use only cables having diameters of
6…9 mm.
MEASURING PRINCIPLE
The KSL operates according to the principle of the hot-wire
anemometer, and consists of two identical resistive sensors
located inside a probe. One sensor measures the tempera-
ture of the air. The second sensor, located in the lateral
opening and so directly exposed to the air flow, heats up to a
controlled permanent temperature.
When there is no air flow, the temperature of this second,
heated sensor remains stable, but as soon as air flows, its
temperature drops. The resultant change is registered by the
built-in electronics, which attempt to re-establish its original
temperature by increasing the electrical current. The extra
current required to do this is proportional to the air speed.
COMMISSIONING
1. If Electrical Outage Protection (see section "60-Second
Electrical Outage Protection") is desired, insert the jumper
(see Fig. 3). Otherwise, remove the jumper.
2. Next, set the potentiometer (marked "Sensitivity" – see
Fig. 3) to the lowest sensitivity (i.e., to the left limit stop).
3. Now connect mains voltage; the green "Voltage" LED will
light up.
NOTE: If the jumper was set, Electrical Outage Protection will now
be in effect (see section "60-Second Electrical Outage
Protection"), and for the next 60 seconds, besides the
green "Voltage" LED, both yellow LEDs ("Time" and "Air
Flow") will also light up, and the device's relay will behave
as though the blower were running and minimum air flow
were present. You must therefore now wait until the 60
seconds have elapsed and the two yellow LEDS have gone
dark before continuing adjustment.
4. Now switch on the blower and provide for nominal air flow.
5. Setpoint adjustment: Slowly turn the potentiometer CW
until the yellow "Air Flow" LED lights up.
6. To achieve a stable switch point, turn the potentiometer
slightly past the switching point.
7. To verify function, reduce or completely cut off the air flow.
The yellow "Air Flow" LED should go dark and the internal
relay should switch.
GREEN "VOLTAGE" LED
Y
ELLOW "TIME" LED
Y
ELLOW "AIR FLOW" LED
JUMPER - OUTAGE PROT.
"SENSITIVITY" POTI
Fig. 3. KSL 24 (cover removed)
60-Second Electrical Outage Protection
The following description of relay behavior assumes that one
wishes to monitor the minimum flow (the usual case). During
normal operation, when the air flow exceeds the setpoint, the
device's relay contact will then close.
To avoid malfunctioning when power is restored after a
system-wide outage (affecting both the blower and the
sensor), select Electrical Outage Protection by setting the
jumper. When restoring power after an outage (or when
starting up; see section "Commissioning"), the relay will then
remain closed for an additional 60 seconds, as though
minimum air flow were still present.
After the 60-sec period has elapsed, normal operation and
relay behavior will resume: Thus, if the air flow has returned
to above the setpoint, the relay will remain closed; if the air
flow has dropped to below the setpoint, the relay will open.
This function can be disabled by removing the jumper.
TROUBLESHOOTING
Problem Possible cause Correction
Device does not
function at all.
No or wrong mains
voltage connected.
Check mains voltage
and connection.
Device does not
detect air flow.
Sensor installed
incorrectly.
Check installation con-
ditions.
Switching behavior
changes.
Sensor heavily
soiled by medium.
Carefully clean sensor
with water.
Device switches at
rapid temperature
increase.
Temp. range is out-
side technical speci-
fications.
Turn poti slightly far-
ther CW. Check temp.
range of system.

This manual suits for next models

2

Other Honeywell Switch manuals

Honeywell Q640 User manual

Honeywell

Honeywell Q640 User manual

Honeywell MICRO SWITCH GSX User manual

Honeywell

Honeywell MICRO SWITCH GSX User manual

Honeywell krom schroder DL K Series User manual

Honeywell

Honeywell krom schroder DL K Series User manual

Honeywell 272630D User manual

Honeywell

Honeywell 272630D User manual

Honeywell ZW4203 User manual

Honeywell

Honeywell ZW4203 User manual

Honeywell Limitless WGLA Series User manual

Honeywell

Honeywell Limitless WGLA Series User manual

Honeywell 39348 User manual

Honeywell

Honeywell 39348 User manual

Honeywell ZW4201 User manual

Honeywell

Honeywell ZW4201 User manual

Honeywell kromshroeder DL H Series User manual

Honeywell

Honeywell kromshroeder DL H Series User manual

Honeywell ZW4009 User manual

Honeywell

Honeywell ZW4009 User manual

Honeywell Micro Switch 91SE Series User manual

Honeywell

Honeywell Micro Switch 91SE Series User manual

Honeywell CENTRAL HUB User manual

Honeywell

Honeywell CENTRAL HUB User manual

Honeywell PLS531A User manual

Honeywell

Honeywell PLS531A User manual

Honeywell IDENT-KEY 3 User manual

Honeywell

Honeywell IDENT-KEY 3 User manual

Honeywell WBX Series User manual

Honeywell

Honeywell WBX Series User manual

Honeywell 43191680-001 User manual

Honeywell

Honeywell 43191680-001 User manual

Honeywell RXSW100A3CULH User manual

Honeywell

Honeywell RXSW100A3CULH User manual

Honeywell 39351 User manual

Honeywell

Honeywell 39351 User manual

Honeywell nfs2-3030 User manual

Honeywell

Honeywell nfs2-3030 User manual

Honeywell VC Series User manual

Honeywell

Honeywell VC Series User manual

Honeywell C6097A User manual

Honeywell

Honeywell C6097A User manual

Honeywell Krom Schroder DL A Series User manual

Honeywell

Honeywell Krom Schroder DL A Series User manual

Honeywell CX Series Quick guide

Honeywell

Honeywell CX Series Quick guide

Honeywell ADEMCO 270R Assembly instructions

Honeywell

Honeywell ADEMCO 270R Assembly instructions

Popular Switch manuals by other brands

Ihse L484-8VHSWR user manual

Ihse

Ihse L484-8VHSWR user manual

Schartec FW1 manual

Schartec

Schartec FW1 manual

socomec SIRCOVER 100A instruction sheet

socomec

socomec SIRCOVER 100A instruction sheet

GeoVision GV-APOE0400 installation guide

GeoVision

GeoVision GV-APOE0400 installation guide

Altronix NetWay5P Series installation guide

Altronix

Altronix NetWay5P Series installation guide

Siemens RUGGEDCOM RSG2200NC installation guide

Siemens

Siemens RUGGEDCOM RSG2200NC installation guide

Dungs GGW A4/2 X Series manual

Dungs

Dungs GGW A4/2 X Series manual

Intek Rheotherm 100CS manual

Intek

Intek Rheotherm 100CS manual

Hewlett Packard Enterprise Aruba 8360 Series Installation and getting started guide

Hewlett Packard Enterprise

Hewlett Packard Enterprise Aruba 8360 Series Installation and getting started guide

Audio Authority 1177A Specifications

Audio Authority

Audio Authority 1177A Specifications

Yokis 5454495 quick start guide

Yokis

Yokis 5454495 quick start guide

CyberPower CyberSwitch CSW8RU user guide

CyberPower

CyberPower CyberSwitch CSW8RU user guide

GW Security GWSW1602G user manual

GW Security

GW Security GWSW1602G user manual

Louroe Electronics SA-1A Installation and operating instructions

Louroe Electronics

Louroe Electronics SA-1A Installation and operating instructions

ATEN Altusen KL1508Ai quick start guide

ATEN

ATEN Altusen KL1508Ai quick start guide

No Wires Needed Pelican 1100 user manual

No Wires Needed

No Wires Needed Pelican 1100 user manual

schmersal AZM300B-I1-ST-1P2P Instructions for operation

schmersal

schmersal AZM300B-I1-ST-1P2P Instructions for operation

Avocent DSR Series DSR1021 supplementary guide

Avocent

Avocent DSR Series DSR1021 supplementary guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.