IFM DTI600 User manual

Operating instructions
RF-identification system
DTI600
Read/write head
11476236 / 0009 / 2022
GB

DTI600
2
Contents
1 Preliminary note ............................................................. 3
1.1 Symbols used.......................................................... 3
1.2 Warnings used ......................................................... 3
1.3 Legal and copyright information ............................................ 3
2 Safety instructions............................................................ 4
3 Intended use................................................................ 5
4 Items supplied............................................................... 6
5 Function ................................................................... 7
5.1 ID tags ............................................................... 7
5.2 Detection range with E80384 .............................................. 7
5.3 Device overview........................................................ 7
5.4 IO-Link ............................................................... 8
6 Installation.................................................................. 9
6.1 Notes on the unit installation............................................... 9
6.2 Avoiding interference .................................................... 9
6.3 Mechanical design ...................................................... 9
6.4 Mounting options........................................................ 9
6.4.1 Installation with angle bracket E80335 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6.4.2 Installation with mounting device E80336 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6.4.3 Installation with fixing bars E80337 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.5 Mounting distances...................................................... 11
6.6 Positioning of the ID tags ................................................. 12
7 Electrical connection.......................................................... 13
7.1 Wiring................................................................ 13
8 Operating and display elements................................................. 14
9 Parameter setting............................................................ 15
9.1 Parameter............................................................. 15
9.1.1 Data block size..................................................... 15
9.1.2 Data alignment..................................................... 15
9.1.3 Data hold time...................................................... 15
9.1.4 Address for automatic read/write. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
9.1.5 Data length for automatic read/write . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
9.2 Status bits............................................................. 16
10 Operation .................................................................. 18
10.1 Deactivate internal antenna................................................ 18
10.2 Operating mode Read UID................................................ 18
10.3 Operating mode Auto read data ............................................ 19
10.4 Operating mode Auto write data............................................ 20
10.5 Operating mode Read data................................................ 21
10.5.1 Example successful reading of data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
10.5.2 Example unsuccessful reading of data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
10.6 Operating mode Write data................................................ 25
10.6.1 Example successful writing of data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
10.6.2 Example unsuccessful writing of data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
10.7 Error values in the process data input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
11 Maintenance, repair and disposal................................................ 30
12 Approvals/standards.......................................................... 31
Glossary................................................................... 32

DTI600
3
1 Preliminary note
You will find instructions, technical data, approvals and further information using the QR code on the
unit / packaging or at www.ifm.com.
1.1 Symbols used
Requirement
Instructions
Reaction, result
[...] Designation of keys, buttons or indications
Cross-reference
Important note
Non-compliance may result in malfunction or interference.
Information
Supplementary note
1.2 Warnings used
ATTENTION
Warning of damage to property
1.3 Legal and copyright information
© All rights reserved by ifm electronic gmbh. No part of these instructions may be reproduced and
used without the consent of ifm electronic gmbh.
All product names, pictures, companies or other brands used on our pages are the property of the
respective rights owners.

DTI600
4
2 Safety instructions
General
• The unit described is a subcomponent for integration into a system.
– The system architect is responsible for the safety of the system.
– The system architect undertakes to perform a risk assessment and to create documentation in
accordance with legal and normative requirements to be provided to the operator and user of
the system. This documentation must contain all necessary information and safety instructions
for the operator, the user and, if applicable, for any service personnel authorised by the
architect of the system.
• Read this document before setting up the product and keep it during the entire service life.
• The product must be suitable for the corresponding applications and environmental conditions
without any restrictions.
• Only use the product for its intended purpose (Ò → Intended use).
• If the operating instructions or the technical data are not adhered to, personal injury and/or damage
to property may occur.
• The manufacturer assumes no liability or warranty for any consequences caused by tampering with
the product or incorrect use by the operator.
• Installation, electrical connection, set-up, operation and maintenance of the product must be
carried out by qualified personnel authorised by the machine operator.
• Protect units and cables against damage.
Radio equipment
In general, radio equipment must not be used in the vicinity of petrol stations, fuel depots, chemical
plants or blasting operations.
uDo not transport and store any flammable gases, liquids or explosive substances near the unit.
Interference of electronic and medical devices
Operation can affect the function of electronic devices that are not correctly shielded.
uDisconnect the device in the vicinity of medical equipment.
uContact the manufacturer of the corresponding device in case of any interference.

DTI600
6
4 Items supplied
• Read/write head
The device is supplied without installation and connection accessories.
Available accessories: www.ifm.com.
The optimum function is not ensured when using components from other manufacturers.

DTI600
7
5 Function
5.1 ID tags
The ID tags are passively operated without a battery. The energy required for operation is provided by
the read/write head.
The energy is provided via an inductive coupling. The integrated antenna coil in the read/write head
generates a magnetic field which partly penetrates the antenna coil of the ID tag. A voltage is
generated by induction that supplies the data carrier with energy.
The device supports ID tags according to ISO 15693.
5.2 Detection range with E80384
0-50-150
170
220
120
20
[mm]
[mm]
-100
-200 50 100 150 200
70
1
Fig.1: Propagation field
1 Detection zone
The indications refer to static write operations and to the installation of the device and the ID tag
in a non-metal environment.
5.3 Device overview
DTI600
Article number: DTI600
Function: RFID compact device
Type designation: DTRHF HLRWIOUS03
Type: Rectangular

DTI600
8
5.4 IO-Link
This unit has an IO-Link communication interface which enables direct access to process and
diagnostic data. In addition it is possible to set the parameters of the unit while it is in operation.
Operation of the unit via the IO-Link interface requires an IO-Link master.
With a PC, suitable IO-Link software and an IO-Link adapter cable, communication is possible while
the system is not in operation.
The IODD required to configure the unit is available at www.ifm.com.

DTI600
9
6 Installation
6.1 Notes on the unit installation
When mounting several RFID units adhere to the minimum distances between the systems.
Flush mounting of a read/write head in metal reduces the read/write distance.
Device performance can be affected if positioned in the immediate vicinity of powerful HF
emission sources such as welding transformers or converters.
6.2 Avoiding interference
The device generates a modulated electrical field with a frequency of 13.56 MHz.
Avoid interference with data communication:
uDo not operate any devices in the vicinity that use the same frequency band.
wSuch devices are for example frequency converters and switched-mode power supplies.
If there are other devices in the same frequency band in the vicinity:
uThe mounting distances between the devices should be as large as possible.
uUse the devices in alternating operation.
uSwitch the HF field of the device on/off.
6.3 Mechanical design
1
2
1 Sensing face 2 Connections (can be rotated by 270°)
6.4 Mounting options
The device can be mounted without the accessories.
uFor installation, please use the threaded sleeves on the back of the device.
wThe required screws are not supplied with the device.

DTI600
10
6.4.1 Installation with angle bracket E80335
6.4.2 Installation with mounting device E80336
The mounting device is used to mount the unit on a clamp. Compatible clamps:
• E21110 with a rod diameter of 12 mm
• E20795 with a rod diameter of 14 mm
• E21109 with a rod diameter of 14 mm

DTI600
11
6.4.3 Installation with fixing bars E80337
6.5 Mounting distances
Operating mode Distance side (A) Distance front (B)
For reading and writing >0.6m >0.4m
Interference in data communication is avoided if there are no other RFID UHF devices in the
vicinity. If there are other RFID UHF devices in the vicinity:
uThe mounting distances between the devices should be as large as possible.
uUse the RSSI filter.
uUse the devices in alternating operation.
uSwitch the HF field of the device on/off.

DTI600
12
6.6 Positioning of the ID tags
D
Fig.2: Position the ID tag
uAlign the ID tag on the antenna central axis.
wThe distance “D” is indicated in the data sheet.
ID tags are also detected on the back of the device. To avoid this:
uUse the RSSI filter.

DTI600
13
7 Electrical connection
The device must be connected by a qualified electrician.
Device of protection class III (PC III).
The electrical supply must only be made via PELV/SELV circuits.
uDisconnect power before connecting the device.
ATTENTION
The IP rating indicated in the data sheet is only guaranteed if the M12 connectors are firmly
screwed. The device can be damaged by insufficiently tightened M12 connectors.
uScrew the M12 connector to the device applying 1 to 1.5 Nm.
7.1 Wiring
uConnect the device to an IO-Link master using a M12 connection cable.
wVoltage is supplied via the IO-Link master.
Pin assignment Wiring
4
1
3
L+
1
3
4
L
IO-Link

DTI600
14
8 Operating and display elements
①
②
Fig.3: Operating and display elements
1 LEDs 2 Sensing face
LED State Description
green On Operating voltage OK
Off Operating voltage missing
Flashing slowly deactivated
yellow On (permanently) ID tag detected
On (pulse) ID tag read/written successfully
Flashing quickly Error when reading/writing on ID tag
Off • no ID tag in the field
• faulty ID tag in the field
• invalid ID tag in the field
green and yellow Flashing alternately Error in communication or device fault

DTI600
15
9 Parameter setting
The parameters of the device are set using a software via IO-Link (for example ifm moneo configure
SA).
More information can be found in the IODD of the unit: www.ifm.com
9.1 Parameter
9.1.1 Data block size
The memory area of an ID tag is organised in data blocks. The parameter specifies the size of a data
block. The set value must correspond with the value of the ID tag indicated in the data sheet.
The following values are permissible:
4,8,16 and 32 bytes per block.
The data block size is only required for the internal data processing in the device. The user can
access the process data images byte by byte on the memory area of the ID tag.
9.1.2 Data alignment
The parameter sets the order of the data in a data block of the ID tag.
Example
For an ID tag with block size 4 bytes the data can be ordered as in the tables:
Data block 0 Data block 1
Byte 3 Byte 2 Byte 1 Byte 0 Byte 3 ...
Tab.1: Normal order
Data block 0 Data block 1
Byte 0 Byte 1 Byte 2 Byte 3 Byte 0 ...
Tab.2: Reversed order
9.1.3 Data hold time
The data hold time indicates the time during which the data of the process data input image can be
held constant. Depending on the operating mode, this concerns
• the UID,
• the "Tag present" bit,
• the data in Auto read and Auto write mode.
The parameter “Data hold time” does not influence data transfer in the operating modes "Read data"
and "Write data".
Example
When the data hold time is set to 500 ms, the UID and the "Tag present" bit are transferred for min.
500 ms via IO-Link.
This also applies if the ID tag is no longer within the range of the device.

DTI600
16
9.1.4 Address for automatic read/write
The parameter "Address for automatic read/write" sets the start address of the memory area that is
accessed in the operating modes "Auto read" and "Auto write".
The address is provided in bytes.
In the operating modes “Auto read" and "Auto write" the device reads and writes a specified number of
data of the ID tag automatically.
The addressed memory area must be within the available memory area of the ID tag:
Auto Read and Write Address +
Auto Read and Write Data Length ≤
Number of available bytes on the ID tag
The number of available bytes is indicated in the data sheet of the ID tag.
9.1.5 Data length for automatic read/write
The parameter "Data length for automatic read/write" sets the length of the memory area that is read
and written.
The length is indicated in bytes. The minimum length is 1 byte and the maximum length is 29 bytes.
In the operating modes “Auto read" and "Auto write" the device reads and writes a specified number of
data of the ID tag automatically.
The addressed memory area must be within the available memory area of the ID tag:
Auto Read and Write Address +
Auto Read and Write Data Length ≤
Number of available bytes on the ID tag
The number of available bytes is indicated in the data sheet of the ID tag.
9.2 Status bits
Process data input
Bit 7 6 5 4 3 2 1 0
Name Antenna de-
activated
Tag present Cmd End Cmd Start
Acknowl-
edge
Process data output
Bit 7 6 5 4 3 2 1 0
Name Cmd Anten-
na deacti-
vate
Cmd Start
Status bit Value Description
Antenna deactivated 0 Antenna activated, device ready to receive
1 Antenna deactivated, device not ready to receive
Tag present 0 No ID tag in the range of the device
1 ID tag detected
Cmd End 0 Read or write operation not yet started or active

DTI600
17
Status bit Value Description
Cmd End 1 Read or write operation terminated
Cmd Start Acknowledge 0 Start of a read or write operation not acknowledged
1 Start of a read or write operation acknowledged
Cmd Antenna deactivate 0 Activate antenna
1 Deactivate antenna
Cmd Start 0 Reset trigger for read or write operation
1 Set trigger for read or write operation
The following status bits cannot be used in the "Read UID" operating mode:
uCmd Start
uCmd Start Acknowledge
uCmd End

DTI600
18
10 Operation
The device supports several operation modes selected with the command value in the process data
output image:
Operating mode Command value Description
Read UID 0x00 Operating mode Read UID (Ò/18)
Auto read data 0x01 Operating mode Auto read data
(Ò/19)
Auto write data 0x02 Operating mode Auto write data
(Ò/20)
Read data 0x03 Operating mode Read data (Ò/21)
Write data 0x04 Operating mode Write data (Ò/25)
For all operating modes, the same status bits and error values in the process images apply.
10.1 Deactivate internal antenna
The internal antenna of the unit can be deactivated at any time. With antenna deactivated
• the device can still be accessed via IO-Link,
• no high-frequency magnetic field is generated by the unit,
• the unit does not recognise ID tags.
Interference between units mounted next to each other is reduced by deactivating the antenna.
Deactivate the internal antenna:
uSet the "Cmd Antenna deactivate" bit in the process data output.
The status of the internal antenna is queried via the bit “Antenna deactivated“ in the process
data input image.
10.2 Operating mode Read UID
In the operating mode "Read UID" the UID of an ID tag is read. Then the UID is available in the
process data input. If no ID tag is in the range of the device, the 8 bytes of the UID get the value
"0x00".
As soon as an ID tag is detected by the device, the UID is transferred. The transfer is continued for the
min. length of the data hold time. If a new ID tag appears in the detection range during the data hold
time, the UID of the new ID tag is transferred.
The default operating mode after the unit is started is "Read UID".
Byte Process data output Process data input
0 Command value = 0x00 Command value = 0x00
1 Status Status
2 ignored UID 0
3 ignored UID 1
4 ignored UID 2
5 ignored UID 3
6 ignored UID 4
7 ignored UID 5

DTI600
19
Byte Process data output Process data input
8 ignored UID 6
9 ignored UID 7
10 ignored 0x00
11 ignored 0x00
12 ignored 0x00
13 ignored 0x00
14 ignored 0x00
15 ignored 0x00
16 ignored 0x00
17 ignored 0x00
18 ignored 0x00
19 ignored 0x00
20 ignored 0x00
21 ignored 0x00
22 ignored 0x00
23 ignored 0x00
24 ignored 0x00
25 ignored 0x00
26 ignored 0x00
27 ignored 0x00
28 ignored 0x00
29 ignored 0x00
30 ignored 0x00
31 ignored Error value
10.3 Operating mode Auto read data
In the operating mode "Auto read data" the bytes 0 to 28 represent the data in the memory area of the
ID tag. The memory area is set by the parameters "Address for Auto Read/Write" and "Data Length for
Auto-Read/Write".
For memory areas with a data length of < 29 bytes the data remaining in the process image is filled
with the value 0x00.
The data in the process image is updated as soon as an ID tag enters the detection range. The data in
the process image is valid as soon as the status bit "Cmd End" is set.
If the ID tag leaves the detection range, the data is held in the process image according to the data
hold time. If the data hold time is exceeded and there is no ID tag in the detection range, the data is
filled with the value 0x00.
If the ID tag remains in the detection range, the data can be read with the status bit "Cmd Start". If
reading was unsuccessful, the error value is shown in the process image.
The smaller the "Length for Auto Read/Write" is set, the less time is needed for reading. That
means that the dwell time of the ID tag in the detection range can be shorter.
Byte Process data output Process data input
0 Command value = 0x01 Command value = 0x01
1 Status Status

DTI600
20
Byte Process data output Process data input
2 ignored Data 0
3 ignored Data 1
4 ignored Data 2
5 ignored Data 3
6 ignored Data 4
7 ignored Data 5
8 ignored Data 6
9 ignored Data 7
10 ignored Data 8
11 ignored Data 9
12 ignored Data 10
13 ignored Data 11
14 ignored Data 12
15 ignored Data 13
16 ignored Data 14
17 ignored Data 15
18 ignored Data 16
19 ignored Data 17
20 ignored Data 18
21 ignored Data 19
22 ignored Data 20
23 ignored Data 21
24 ignored Data 22
25 ignored Data 23
26 ignored Data 24
27 ignored Data 25
28 ignored Data 26
29 ignored Data 27
30 ignored Data 28
31 ignored Error value
10.4 Operating mode Auto write data
In the operating mode "Auto-write data" the data to be written is defined by the process data output
image. The data is set with the parameters "Address for Auto Read/Write" and "Data Length for Auto
Read/Write".
The data is written with the address and length to an ID tag as soon as the ID tag enters the detection
range.
Max. 29 bytes become defined in the process data output image (bytes 0 to 28). For memory areas
with a data length of < 29 bytes the remaining data is ignored and not written to the ID tag.
If writing was successful, the written data is copied to the process data input image and the status bit
"Cmd End" is set.
If the ID tag leaves the detection range, the data is held in the process image according to the data
hold time. If the data hold time is exceeded and there is no ID tag in the detection range, the data is
filled with the value 0x00.
Other manuals for DTI600
1
Table of contents
Other IFM RFID System manuals