Item Part No.
IPAQ-L, isolated 70IPL00001
IPAQ-LX, isolated (ATEX) 70IPLX0001
IPAQ-LX, isolated (FM) 70IPLX1001
IPAQ-L, isolated, mA input 70IPL00003
Software and cable
IPRO-X (IPRO with cable) 70CFG00092
LIMITED WARRANTY
INOR Process AB, or any other affiliated company within the Inor Group (hereinafter
jointly referred to as ”Inor”), hereby warrants that the Product will be free from
defects in materials or workmanship for a period of five (5) years from the date of
delivery (”Limited Warranty”). This Limited Warranty is limited to repair or replacement
at Inor’s option and is effective only for the first end-user of the Product. Upon
receipt of a warranty claim, Inor shall respond within a reasonable time period as to
its decision concerning:
1 Whether Inor acknowledges its responsibility for any asserted defect in
materials or workmanship; and, if so,
2 the appropriate cause of action to be taken (i.e. whether a defective
product should be replaced or repaired by Inor).
This Limited Warranty applies only if the Product:
1 is installed according to the instructions furnished by Inor;
2 is connected to a proper power supply;
3 is not misused or abused; and
4 there is no evidence of tampering, mishandling, neglect, accidenta damage,
modification or repair without the approval of Inor or damage done to the
Product by anyone other than Inor.
This Limited Warranty is provided by Inor and contains the only express warranty
provided.
INOR SPECIFICALLY DISCLAIMS ANY EXPRESS WARRANTY NOT PROVIDED
HEREIN AND ANY IMPLIED WARRANTY, GUARANTEE OR REPRESENTA-
TION AS TO SUITABILITY FOR ANY PARTICULAR PURPOSE, PERFORMANCE,
QUALITY AND ABSENCE OF ANY HIDDEN DEFECTS, AND ANY REMEDY FOR
BREACH OF CONTRACT, WHICH BUT FOR THIS PROVISION, MIGHT ARISE
BY IMPLICATION, OPERATION OF LAW, CUSTOM OF TRADE OR COURSE
OF DEALING, INCLUDING IMPLIED WARRANTIES OF MER-CHANTABILITY
ANDFITNESSFORAPARTICULARPURPOSE. EXCEPTASPROVIDEDHEREIN,
INOR FURTHER DISCLAIMS ANY RESPONSIBILITY FOR LOSSES, EXPENSES,
INCONVENIENCES, SPECIAL, DIRECT, SECONDARY OR CONSEQUENTIAL
DAMAGES ARISING FROM OWNERSHIP OR USE OF THE PRODUCT.
Products that are covered by the Limited Warranty will either be repaired or replaced
at the option of Inor. Customer pays freight to Inor, and Inor will pay the return
freight by post or other “normal” way of transport. If any other type of return freight
is requested, customer pays the whole return cost.
DATA (shortform)
CONNECTIONS
ORDERING TABLE
IPAQ-LX EX-DATA
Approval Demko 03 ATEX 134461X
CE 0539 II (1)G [EEx ia] IIC
Output (terminals 5-6)
(current loop) Ui: 30 VDC
Ii: 100 mA
Pi: 0,9 W
Li:0mH
Ci:1nF
Input (terminal 1-2-3-4)
(Intrinsically safe sensor terminals) Uo: 30 V
Io: 27 mA
Lo: 50 mH
Co: 52 nF
The equipment must be electrically connected (terminal 5 and 6) via a certified
isolating interface/zener barrier -and shall be placed outside the hazardous area.
IPAQ-L/LX are designed to fit on a standard DIN Rail.
IPAQ-LX must be installed in safe area.
Connect input, output and power supply acc. to fig. 1-9.
INSTALLATION
Power supply: IPAQ-L 7.5 to 36 VDC
IPAQ-LX 8 to 30 VDC
Isolation in/out: 1500 VAC
Output: 4-20 mA
Operating temperature: -20 to +70 °C
T1
T2
mV
RTD
(Pt100)
T/C
RTD
100%
0%
RTD
RTD
(Pt100)
100%
0%
RTD
4-wire connection
Pt100
Diff temperature T1> T2
Potentiometer
3-wire connection
Potentiometer
4-wire connection
Voltage
mV
Thermocouple
Supply voltage U (VDC)
RTD
3-wire connection
Fig 3
Fig 4
Fig 5
Fig 6
Fig 7
Fig 8
Fig 9
IPAQ-L IPAQ-LX
!
!
Fig 1 Fig 2