jablotron JA-10E User manual

JABLOTRON ALARMS a.s.
Pod Skalkou 4567/33 46601 Jablonec n. Nisou
Czech Republic www.jablotron.com
||
|
JA-10E BUS keypad
JA-10E BUS keypad 1 / 2 MNX51101
The keypad is a component of the JA-10 system used to control
the control panel and display its current status. Using an external
input a door detector can be connected to the keypad.
It is necessary to use this manual in combination with
the JA-10 installation and user manuals.
The keypad contains 4 function buttons (5), an LCD display (3),
a system indicator (2), status indicators A, B, C, D (1), a keypad with
an RFID chip card/tag reader (4).
Figure 1 : 1 – status indicators; 2 – system indicator; 3 – LCD display;
4 – keypad and the RFID reader; 5 – function buttons A, B, C, D;
6 – keypad opening tab; 7 – detachable BUS terminals; 8 – tamper
contact; 9 – production number
Installation
1. Open the keypad housing by pressing the tab on the bottom
(6) using a screwdriver. The tab is also accessible from
the front after opening the keypad cover.
2. Break away a hole in the plastic base, run the cable through
and screw the plastic back on a selected place. Connect
the cable to the BUS terminals (7). For easier installation you
can detach the BUS terminals, connect the cables and
re-attach them.
3. Insert the keypad back into the plastic base. Make sure
the conductors do not touch the tamper contact spring.
4. Proceed according to the control panel installation manual.
Basic procedure:
a. When the device is switched on, the system indicator (2) will
start flashing yellow repeatedly to indicate that the keypad
has not yet been enrolled to the system.
b. Open the N-Link software, select the required position
in the Devices window, and click on the Enroll button which
will open a Device information dialogue window.
c. Click on Scan/add new BUS devices which will display a list
of connected unenrolled devices. Double-click on the device
you want to enroll – the JA-10E in this case.
d. The keypad is now enrolled and the yellow LED indicator
switches off.
Notes:
−The keypad can also by enrolled by opening the enrollment
mode (the Enroll button in the Devices tab of the N-Link SW)
and pressing the keypad’s cover or the tamper contact.
−Enrollment is also possible by entering its production code (9)
in the N-Link software or using a bar code scanner. All
numbers stated under the bar code must be entered (e.g.
1400-00-0000-0001).
Installation of a magnetic contact
The keypad supports connection of a door detector. The IN input
reacts to being disconnected from the GND contact. The control
panel’s reaction to an activated IN input is configurable in the N-Link
SW.
Figure 2: connecting a magnetic contact
Setting the properties
Go to the Devices window in the N-Link software. When you are
at the keypad position, click on the Internal settings option which will
display a dialogue window with all properties. Internal settings are
separated into 2 basic tabs: Function and Settings.
Function tab:
Day and time – displays the current time in the top-right corner of the
display
The system is not prepared to be Set – indicates an obstacle
preventing setting the control panel.
User defined text – enables showing any text, for example the
phone number of an installer company, etc.
Button function – On the left is a selection of button functions.
On the right is a selection of Sections or PG outputs to which the
functions will be assigned. A function button can be assigned with
these functions: None, Unsetting/setting, Unsetting/Partially setting,
Unsetting/Partially setting/Setting, Section indication, Panic, Fire,
Audible panic, Medical Troubles, PG ON/OFF, PG ON, PG OFF,
PG indication, PG indicates inversely, Common functional button
Authorization – Setting and Unsetting requires user authorization.
When this parameter is disabled the function buttons can be operated
without authorization, however this does not apply to Unsetting
a section which always requires authorization. Both ON and OFF
statuses of PG outputs can be configured to be operated with or without
authorization
Sections controlled by authorization – selection of sections which
can be controlled by authorization (using an RFID chip or a code)
PG Control – selection of PG outputs which can be controlled by
authorization (using an RFID chip or a code)
Logo – the keypad can display a black and white picture of 128x64
pixels (such as a company logo etc.) which stays on the screen for
25 seconds after the last keypad operation.
Import – enables copying settings from other keypads of the same
type which have already been enrolled. For example, this can be
utilized when the building has multiple entrances and it is necessary
for all keypads to have identical functions. In addition, this function
can also be used when replacing a faulty keypad with another. The
Import button provides the history of keypad settings on a position of
a particular device.
Setting tab:
Acoustic indication of selected sections:
−Higher volume – Increased volume of indication (It does not
apply to alarms).
−Alarms – Indicates alarms (sounds a siren).
−Entrance delay – continuous sound during the entrance delay
−Exit delay – slow beeping (1/sec)
−Exit delay when partially set – slow beeping (deactivated
by default)
−Button status change –beeps once when a status is changed
Function:
Optical indication setting:
1. Indicates permanently – the keypad indicates permanently.
When the mains electricity is disconnected it indicates
the same way as option 3. When mains electricity is restored
the keypad indicates permanently again.
2. Section/PG status change on keypad – The status
change of a section/PG is indicated by a specific function
button and a status indicator. Entrance delay and alarms
are indicated by all function buttons and status indicators.
3. Section/PG status change on button – The keypad indicates
after a change of the section/PG status, entrance delay and
alarm only by a particular button and a section indicator.
Always switch the power off before
connecting the keypad to the BUS.

JA-10E BUS keypad
JA-10E BUS keypad 2 / 2 MNX51101
4. Button status change on keypad – The keypad indicates
after a change of the section/PG status by a particular button
and a section indicator. Entrance delay and alarms are
indicated acoustically only.
5. Entrance delay/Alarms on button – The keypad indicates
entrance delays and alarms with a function button and a
status indicator. Change of section/PG status is not
indicated visually or acoustically.
6. Wake-up by pressing –The keypad starts to optically and
acoustically indicate after the front cover has been opened
and also when a key or a function button has been pressed.
RFID reader: In order to save energy we limit the RFID reader to
function for 3 seconds after pressing the keypad cover. The
reader can be also completely disabled. This setting applies to
wireless keypads and access modules as long as they are
supplied permanently by an external power supply, otherwise
their RFID readers will always turn off automatically.
Permanently ON – the RFID reader is always active. A BUS
keypad ignores wake up settings.
Activated by pressing – When the keypad is activated the
RFID wakes up for 3 seconds.
Disabled – RFID is permanently disabled.
Activated by pressing or authorization requirement –
the keypad wakes up after pressing a button on a keypad cover
or by an authorization request, for example during the entrance
delay.
Unset a section by authorization only during an entrance
delay – using an access code or an RFID tag will unset a section
where an entrance delay has been triggered (if the user has
access to the section). This authorization can be used with
wireless keypads only when they declare an entrance delay.
WARNING: This function is not recommended when the control
panel is configured to use a Common section. Unwanted
unsetting may occur to all sections assigned to the Common
section or it may even occur to the whole control panel (when
pressing the Unsetting button is followed by authorization).
Delayed panic – this function triggers a panic alarm (silent
or loud) with an adjustable delay during which the alarm can
be cancelled. Activation and deactivation is done by a function
button configured to Panic or Silent panic functions. The button
pressed once triggers the delay. Press twice to cancel the delay.
When authorization is enabled then it is required for activation
and deactivation. The delay is adjustable from 1 to 255 seconds.
Backlight intensity
−Indicators – backlight intensity of indicators
−Functional buttons – backlight intensity of the function
buttons
−Keypad – backlight intensity of the keypad
−Display – backlight intensity of the LCD display
−Contrast – LCD display contrast
Acoustic indication for sections: list of allowed sections for
acoustic indication.
A keypad configuration which complies with
certification requirements must be selected
from the list of System profiles in the
Parameters tab of the N-Link SW.
Optical indication
System indicator:
Continuous green light - Normal operation. Sections controlled
by the keypad are OK, no faults.
Continuous yellow light - Normal operation, reported faults
in some of the controlled sections. You can get more detailed
information via the LCD keypad menu after user authorization
depending on the user access rights.
If the optical indication is followed by a rotating Jablotron logo
on the LCD keypad then it represents a radio communication fault
between the control panel and the keypad
Continuous red light – The keypad is in BOOT mode, used
while upgrading firmware.
Flashes green (2Hz) – Ongoing authorization during which
the user can change the statuses of the function buttons
or browse the keypad menu. Authorization times out after
8 seconds from the last time any of the buttons had been pressed
or it can be cancelled by pressing ESC.
Flashes yellow (8Hz) - Unsuccessful setting warning indication
Flashes red (8Hz) - Indication of a currently triggered alarm
in one of the sections controlled by the keypad. The type of alarm,
name of the section where an alarm has been triggered and
the source of the triggered alarm is visible on the LCD keypad
Flashes alternately red/yellow - Triggered alarm with an
active fault
Flashes alternately green/red – Ongoing authorization
with an alarm memory
Flashes alternately green/yellow – Ongoing authorization with
an active fault
Flashes yellow 2x every 2 seconds - Programming / Service
mode. All control button indication is disabled, function keys along
with the keypad menu are unavailable for users and the
Administrator. The keypad menu is only available for a service
technician unless a PC is connected to the control panel.
Flashes red 2x every 2 seconds - Alarm memory indication
Flashes yellow 1x every 2 seconds - Fault indication on a
keypad which is in sleep mode (only valid for the EN50131-1 profile)
Flashes red 1x every 2 seconds - Alarm memory indication on
a keypad which is in sleep mode (only valid for the EN50131-1
profile)
No indication – The keypad is in sleep mode.
Function buttons and status indicators – the status of the
function buttons is simultaneously indicated by the status
indicators A, B, C, D
Continuous green light - Section status is Unset or a PG
output is OFF.
Flashes green (4Hz) – Ongoing entrance delay and the system
waits to be Unset by authorization.
Continuous yellow light - Section status is Partially set
Continuous red light - Section status is Set or a PG output
is ON
Flashes yellow (4Hz) - System expects authorization when
partially set or it reports a fault during partial setting.
Flashes yellow (8Hz) - Unsuccessful setting warning indication.
Flashes red (4Hz) – The control panel waits for authorization
during setting or it reports a problem during setting
Flashes red (8Hz) - Alarm memory indication. It is indicated
until it is cancelled
No light - Service mode or a blocked section after an alarm
(after blocking and cancelling alarm memory indication)
Acoustic indication
It can be set regardless of the keypad’s optical indication and
sleep mode. The keypad can indicate entrance/exit delays
or alarms. During valid authorization (by a user code or RFID
card), the acoustic indication of exit delays is suppressed.
By pressing the indication button, the keypad is muted
permanently. Entrance delays and alarms are indicated until their
times expire, unless the activation button is pressed.
Technical specifications
Power from control panel digital bus (9…15 V)
Nominal current consumption to calculate back up 30 mA
Current consumption for cable selection 110 mA
Connection type data BUS – not shared
RFID frequency 125 kHz
Size 120x130x30 mm
Weight 217 g
Operating temperature range -10 to +40 °C
Average operational humidity 75% RH
Operational environment according to EN 50131-1 II. Indoor general
Classification Grade 2 (if selected in the N-Link SW)
according to EN 50131-1, EN 50131-3,
Certification body Trezor Test
Also complies with ETSI EN 300 330, EN 50130-4,
EN 50581, EN 55032, EN 62368-1,
Can be operated according to ERC REC 70-03
JABLOTRON ALARMS a.s. hereby declares that the JA-10E
is in a compliance with the relevant European Union harmo-
nization
legislation: Directives No: 2014/53/EU, 2014/35/EU,
2014/30/EU, 2011/65/EU. The original of the conformity assess-
ment can be found at www.jablotron.com - Section Downloads.
Note:
Although this product does not contain any harmful
materials we suggest you return the product to the dealer
or directly to the producer after use. For more detailed information
visit www.jablotron.com.
Other jablotron Keypad manuals

jablotron
jablotron JA-115E User manual

jablotron
jablotron KB-2051 User manual

jablotron
jablotron JA-155E User manual

jablotron
jablotron JA-114E User manual

jablotron
jablotron JA-63F User manual

jablotron
jablotron 100 User manual

jablotron
jablotron JA-15E User manual

jablotron
jablotron JA-150E User manual

jablotron
jablotron KB-1051 User manual

jablotron
jablotron JA-60F User manual