manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. jablotron
  6. •
  7. Keypad
  8. •
  9. jablotron JA-155E User manual

jablotron JA-155E User manual

JABLOTRON ALARMS a.s.
Pod Skalkou 4567/33 46601 Jablonec n. Nisou
Czech Republic www.jablotron.com
||
|
JA-155E, JA-155E-GR, JA-155E-AN Wireless four-segment keypad with
display and RFID reader
Typ: 5KPAD2202LU
JA-155E, JA-155E-GR, JA-155E-AN 1 / 3 MLU510701
The keypad is a wireless component of the JABLOTRON system.
It serves for the controlling and displaying system status indication.
It is equipped with four segments; their descriptions are displayed on
the LCD display. The device should be installed by a trained
technician with a valid certificate issued by an authorized distributor.
The keypad is compatible with following control panels
JA-102K, JA-103K and JA-107K.
It is necessary to use this manual in combination with the
JABLOTRON 100 installation and user manuals.
The keypad comprises of 4 segments (1), LCD display (2), keypad
and RFID card/tag reader (4).
Figure 2: 6 – battery holder;
7 – serial number; 8 – tamper
contacts; 9 – locking mechanism
Figure 1: 1 – control buttons; 2 – LCD display; 3 – system indicator / button;
4 – keypad with RFID reader; 5 – cover;
Figure 3: 9 – locking mechanism; 10 – tab
Figure 4: 11 – terminals of an external power supply and an external
magnetic contact
Installation
1. Remove the mounting pad (rear part) of the keypad. If you can´t
remove it easily, open the locking mechanism, see paragraph
Alternative power supply and Installation of a magnetic contact.
2. Mount the back of the keypad to a flat wall using 4 screws.
To connect an external power supply or magnetic contact, use
the terminals on the back of the keypad, see Figure 4. See the
connection description in the paragraphs the Alternative Power
Supply and Installation of a magnetic contact.
3. For enrolling to the system, the JA-11xR radio module must be
installed in the system.
4. Insert 4x 1.5V AA alkaline batteries into the keypad, mind the
correct polarity!
5. Enrollment to the system according to the type of control panel
use the recommended software or application, see the
installation manual of the control panel.
6. First attach the bottom edge of the keypad to the mounting pad (rear
part) of housing (align the bottom sides). Then slide the keypad
downwards, until you hear the click of the tab (10). This will secure
the keypad against falling out of the installation pad. Then turn the
locking mechanism (9) clockwise 90° to the position where the
groove points to the symbol). This locks the keypad in place and
engages the tamper contact.
Notes:
−Enrollment is also possible by entering its serial number (7) in
the F-Link software or using a bar code scanner. All numbers
stated under the bar code must be entered (1400-00-0000-
0001).
−The tilting cover (5) can be removed if the user prefers permanent
access.
Keypad disassembly
On the underside of the keypad, turn the locking mechanism (9)
anticlockwise 90° until the groove points to the symbol . Then use
a screwdriver to release the tab (10) while sliding the keypad up. The
keypad can then be easily removed from the mounting pad. (If the
mounting pad is not screwed on, use the same procedure, just slide
the mounting pad downwards against the keypad).
Setting the properties
The settings are configured by the F-Link software - Devices tab.
Use the Internal settings option on the device position. A dialogue
window will appear in which all the keypad functions can be set. The
internal settings are divided into two basic tabs: Segments and
Settings.
The Segments tab:
Within the Segments tab, the required functions can be set for
individual segments (control of sections, indication of section status,
triggering of a panic alarm, control of PG output, indication of PG
output status, etc.).
The segment descriptions can be edited in F-Link directly by
clicking on the segment text.
Authorization – setting and unsetting requires user authorization.
When this parameter is disabled, the segment can be operated
without authorization. By disabling the parameter, the specific
segment can be controlled without authorization, except for the
Unset section function, for which authorization is always required.
When switching PG outputs on and off, the Authorization / No
Authorization function is enabled for both states.
Common segment – settings and description of function
One of the other functions of the segment is called Common
segment (max 1 common segment can be set per keypad). This
simulates the simultaneous pressing of several segments controlling
sections located on this keypad. The selection of sections assigned
to a common segment is done via F-Link - Devices tab, at the
module position select Internal Settings, Segments tab and select
the function called Common segment A by selecting the segment.
The overview of segments that will be controlled at once is visible in
the newly displayed Common Segment tab.
If the status of the segments controlled by the Common segment
is different, the remaining segments will be set/unset after its use.
If one of the selected segments has the Partial setting function
enabled, then the Common Segment respects this setting: 1st press
of the Set button = partial setting, 2nd press of the Set button = full
setting.
The Common segment function should not be combined with the
Section / Common section function.
Common segment indications:
Green = all sections are unset fully
Yellow = sections are in various states or all of them are
set partially
Red = all sections are set fully
In the Settings tab, you can adjust the remaining keypad
parameters such as acoustic indication, backlight intensity, RFID
reader function, optical indication and display settings. Details of the
settings can also be found in the F-Link SW mouseover help bubble.
Automatic stand-by mode
When the keypad is powered from batteries, it saves energy and
turns off system optical indication, backlight and RFID reader after 8
seconds without pressing a key or closing the keypad cover.
However, the keypad also maintains communication with the control
panel and can indicate, for example, entry delay. The keypad will be
completely active when the keypad cover is opened or pressed, or
any button or segment pressed.
JA-155E, JA-155E-GR, JA-155E-AN Wireless four-segment keypad with
display and RFID reader
Typ: 5KPAD2202LU
JA-155E, JA-155E-GR, JA-155E-AN 2 / 3 MLU510701
Alternative power supply
The keypad can be supplied from an external power supply with
12 V DC connected in PWR a GND terminals, see figure no. 5. You
can use the DE 06-12 Power adaptor suitable for concealed
installation. If the alternative power supply is connected, leave the
batteries inserted to ensure operation in the event of a mains power
failure or an external power supply being disconnected. The inserted
batteries are not recharged by an external power supply. If an
external power supply is connected, a permanent indication can be
switched on.
Installation of a magnetic contact
The keypad supports connection of a door detector. The IN input
reacts to being disconnected from the common GND terminal, see
figure no. 5. The control panel´s reaction to an activated IN input is
configurable in the F-Link SW. The input has a status response.
PWR – red, positive pole of an external power supply +12 V DC
GND – black, negative pole of an external power supply
IN – green, input terminal for door (magnetic) contact
GND – black, input terminal for door (magnetic) contact
Figure 5: magnetic contact connection
Changing the batteries
The keypad automatically checks the status of the batteries, and if
the battery voltage drops below the limit specified in the Technical
Parameters section, the keypad informs the system that the batteries
need to be replaced. Batteries should be replaced within 2 weeks of
the low battery report. The control panel must be switched into
Service or Maintenance mode before removing the keypad from the
back part (otherwise a tamper alarm will be triggered).
Note:In order to make sure the keypad works correctly, we recommend
using batteries supplied by the distributor or other quality brand alkaline
batteries.
The Settings tab
Acoustic indication
It is set without dependence on the optical indication. The keypad
can indicate alarms, entry and exit delays. The acoustic indication of
the entry delay is silenced for the duration of the authorization. Exit
delays and alarms are indicated until the end of the pre-set time
period unless the system indicator button (3)/keypad cover (5) is
pressed.
Volume - Adjusts the keypad volume level in three levels: Low,
*medium and high
Alarms – continuous tone
Entry delay –continuous tone
Exit delay – slow beeping
Exit delay when partially set – slow beeping (disabled from
default).
Segment status change – beeps once when a status is changed
Function:
RFID reader – In order to save energy, you can limit the reader´s
operation with the following options:
−Permanently ON – The RFID reader is always ON. This
setting is valid only if the keypad is permanently powered from
an external source, otherwise their RFID reader is always
switched off automatically.
−Activated by pressing – when the keypad is activated the
RFID reader wakes up for 3 seconds.
−Disabled – the RFID reader is permanently disabled.
−Activated by pressing or authorization request – the
keypad wakes up after pressing a button on a keypad cover or
by an authorization request.
Optical indication
System indicator / button (3) – indicates the system status,
according to the following priorities from highest to lowest:
1 – Service indication:
1) Flashes yellow twice every 2 seconds – Service mode
2) Flashes green 2x every 2 seconds – Maintenance mode
3) Slow flashing yellow – Keypad is in BOOT mode, which is
used when updating firmware
2 – Operational indications:
1) Flashing yellow – Keypad is not enrolled into system
2) Rapidly flashing red – Alarm in system
3) Flashes red 2x every 2 seconds – Alarm memory indication
4) Flashes yellow (8 Hz) – Unsuccessful setting indication
5) Permanent yellow light – Fault
6) Flashes green (2 Hz) – Authorized user
7) Permanent green light – Normal operation. Everything is OK,
no faults
3 – Combined indication:
1) Flashes alternately green / red – Authorized user and
alarm / alarm memory indication
2) Flashes alternately green / yellow – Authorized user and an
active fault indication
4 – Indication in power save mode:
1) Flashes red once every 2 seconds – Alarm memory
indication for keypad in power save (sleep) mode (only valid
for system profiles EN 50131-1 and Incert)
2) Flashes yellow once every 2 seconds – Fault indication
(only valid for system profiles EN 50131-1 and Incert).
3) No indication – Sleep mode
Segments – there is no indication if the system is in the service
mode or if the segment has no function programmed. The PG optical
indication on the segment can be inverted.
Keypad indication is adjustable in six levels:
1. Indicates permanently – the keypad indicates
permanently. When the mains power to the control panel is
disconnected it switches to a lower indication level. Then the
mains power is restored the keypad indicates permanently
again.
2. Section / PG status change on keypad – the keypad
indicates when the section / PG status changes. The change
of state is indicated only on that segment. Entry delay and
alarm is indicated by the entire keypad.
3. Section / PG status change on segment - the keypad
indicates when the section / PG status changes. Segment
status change, arrival delay and alarm are indicated only on
that segment.
4. Segment status change on keypad – the keypad indicates
when the segment status changes (setting, unsetting,
PG on, PG off). The status change is indicated only on the
segment.
5. Entry delay / Alarm on segment – the keypad indicates the
entry delay and alarm on a specific segment.
6. Wake-up by pressing – the keypad optically indicates only
after opening the front cover (5), pressing a key or segment.
Other optional functions:
−Indicates PG status changes
−Indicates Unset status
−Indicates Set status
−External input – enables the input for an external magnetic
contact
Unset a section by authorization only during entry delay -
using an access code or an RFID tag/card will unset a section where
an entrance delay has been triggered (if the user has access to the
section).
WARNING: This function is not recommended when the control
panel is configured to use a Common section. Unwanted unsetting
may occur to all sections assigned to the Common section or it may
even occur to the whole system (when pressing the Unsetting button
is followed by authorization).
JABLOTRON ALARMS a.s.
Pod Skalkou 4567/33 46601 Jablonec n. Nisou
Czech Republic www.jablotron.com
||
|
JA-155E, JA-155E-GR, JA-155E-AN Wireless four-segment keypad with
display and RFID reader
Typ: 5KPAD2202LU
JA-155E, JA-155E-GR, JA-155E-AN 3 / 3 MLU510701
Periodical communication with CP once every 8 s – Enabling
the parameter to extend the battery lifetime. However, this setting
will increase the response time of the keypad in response to system
states (entry and exit delay, alarms, segment status change).
Delayed panic –this function triggers a panic alarm (silent or loud)
with an adjustable delay during which the alarm can be cancelled.
Activation and deactivation are done by a segment button configured
to Silent panic or Audible panic. Pressing the red segment button
(right) starts the timing and pressing the green segment button
cancels the timing. When authorization is enabled then it is required
for activation and deactivation. The delay is adjustable from 1 to 255
seconds.
Keypad light intensity in DAY / NIGHT mode.
Segment – segment button light intensity setting
Keypad – numeric keypad backlight setting
Display – LCD backlight setting
*Mute – in the NIGHT mode, the keypad will be without
any acoustic indication. It will not indicate exit
delay, alarm, key press, etc. In the DAY mode,
it will indicate according to the setting "Acoustic
indication of selected sections“
* - the option is available only in NIGHT mode
A keypad configuration which complies with
certification requirements must be selected
from the list of System profiles in the
Parameters tab of the F-Link SW.
Date and time – the current date and time is automatically
displayed on the bottom line of the LCD display (2) of the keypad if
this segment is without function.
Temperature – displays the measured temperature of the selected
detector on the bottom line of the LCD display (2) of the keypad if
this segment is without function.
Import – the import button allows you to copy keypad settings to
another keypad in the system of the same type. This can be used,
for example, if an object has multiple entrances and it is necessary
to set all keypads in the same way. The Import button provides
a history of the last keypad settings at a given device position. This
function can also be used when replacing a faulty keypad with a new
one.
Keypad FW update
1. Updates can only be done by a Service technician with the
F-Link SW.
2. Start the F-Link SW and open the appropriate database.
3. Enter the service mode
4. In a toolbar click to: Control panel → Update firmware
5. In the devices menu table, select the required device; if
Automatic Update is disabled, select the FW package file
(included in the F-Link installation or can be published for
download separately, file type *.fwp).
6. Press OK to upgrade the selected device.
7. When the update is complete, check the keypad setting in the
F-Link, Devices / Internal settings. Depending on the changes
made during the update, the previous settings of the module may
be retained or reset to factory defaults. If a reset has been
performed, the Import button can be used to select from the
previous settings and restore them without breaking the new
firmware.
Technical specifications
Power supply 4 x alkaline batteries, type: AA (LR6) 1.5 V
Please note: Batteries are not included.
Typical lifetime of batteries 1–2 Years
LowBatt state <4.5 V
Quiescent current consumption (6 V) 245 μA
Maximum current consumption (6 V) 115 mA
External power supply 12 V +/-1 V typ. 45 mA, max. 100 mA
Maximum cable length 3 m
Communication band 868.1 MHz, JABLOTRON protocol
Maximum radio-frequency power (ERP) <25 mW
Communication range approx 200 m (open area)
RFID frequency 125 kHz
Maximum RFID magnetic field strength -5.4 dBμA/m
(measured at 10 m)
Dimensions 110 x 136 x 33 mm
Weight (w/o batteries) 285 g
Classification
Security grade 2/Environmental class II (according to EN 50131-1)
Environment indoor general
Operating temperature range -10 °C to +40 °C
Average operating humidity 75% RH, w/o condensation
Certification body Trezor Test s.r.o. (no. 3025)
In compliance with ETSI EN 300 220-1,-2, ETSI EN 300 330,
EN 50130-4, EN 55032, EN 62368-1,
EN 50131-1, EN 50131-3, EN 50131-5-3, EN 50131-6,
Operating conditions according to general authorization
ERC REC 70-03
Recommended screw 4 x ø 3.5 x 40 mm (half-round head)
JABLOTRON ALARMS a.s. hereby declares that the
1KPAD2201LU is in a compliance with the relevant
Union harmonisation legislation: Directives No:
2014/53/EU, 2014/35/EU, 2014/30/EU, 2011/65/EU.
The original of the conformity assessment can be
found at www.jablotron.com – Section Downloads
Note: Disposing of this product correctly will help save
valuable resources and prevent any potential negative
effects on human health and the environment, which
could otherwise arise from inappropriate waste
handling. Please return the product to the dealer or
contact your local authority for further details of your
nearest designated collection point.

This manual suits for next models

2

Other jablotron Keypad manuals

jablotron JA-10E User manual

jablotron

jablotron JA-10E User manual

jablotron KB-2051 User manual

jablotron

jablotron KB-2051 User manual

jablotron 100 User manual

jablotron

jablotron 100 User manual

jablotron JA-60F User manual

jablotron

jablotron JA-60F User manual

jablotron JA-15E User manual

jablotron

jablotron JA-15E User manual

jablotron JA-150E User manual

jablotron

jablotron JA-150E User manual

jablotron JA-114E User manual

jablotron

jablotron JA-114E User manual

jablotron KB-1051 User manual

jablotron

jablotron KB-1051 User manual

jablotron JA-80E User manual

jablotron

jablotron JA-80E User manual

jablotron JA-115E User manual

jablotron

jablotron JA-115E User manual

jablotron JA-63F User manual

jablotron

jablotron JA-63F User manual

Popular Keypad manuals by other brands

Aritech ATS1110 Instruction

Aritech

Aritech ATS1110 Instruction

Rockwell Automation Allen-Bradley 2711E-NK5 Installation datasheet

Rockwell Automation

Rockwell Automation Allen-Bradley 2711E-NK5 Installation datasheet

Samsung OfficeServ 7200 user guide

Samsung

Samsung OfficeServ 7200 user guide

Nice MV00297 installation guide

Nice

Nice MV00297 installation guide

Johnson Controls IQ KEYPAD user guide

Johnson Controls

Johnson Controls IQ KEYPAD user guide

DMP Electronics ePAD 5.0 Programming guide

DMP Electronics

DMP Electronics ePAD 5.0 Programming guide

URC Total Control TDC-7100 owner's manual

URC

URC Total Control TDC-7100 owner's manual

Crestron CNX-B12 Operations & installation guide

Crestron

Crestron CNX-B12 Operations & installation guide

fortessa FTK5 instructions

fortessa

fortessa FTK5 instructions

First Alert FA260KP-OM installation instructions

First Alert

First Alert FA260KP-OM installation instructions

Fort ECSPKY manual

Fort

Fort ECSPKY manual

Comelit 3348B User programming manual

Comelit

Comelit 3348B User programming manual

Richmond GTR066 manual

Richmond

Richmond GTR066 manual

Genie Universal Keypad instructions

Genie

Genie Universal Keypad instructions

Manhattan 176354 instructions

Manhattan

Manhattan 176354 instructions

Climax Technology KP-23EL-ZBS-ACE manual

Climax Technology

Climax Technology KP-23EL-ZBS-ACE manual

tau TCODE installation guide

tau

tau TCODE installation guide

AMX PLK-IMS Dimensional drawing

AMX

AMX PLK-IMS Dimensional drawing

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.