manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. jablotron
  6. •
  7. Keypad
  8. •
  9. jablotron JA-15E User manual

jablotron JA-15E User manual

JABLOTRON ALARMS a.s.
Pod Skalkou 4567/33 46601 Jablonec n. Nisou
Czech Republic www.jablotron.com
||
|
JA-15E Wireless keypad
JA-15E Wireless keypad 1 / 3 MNX53101
The keypad is a component of the JA-10 system used
to control the control panel and display its current status. Using an
external input a door detector can be connected to the keypad.
It is necessary to use this manual in combination with
the JA-10 installation and user manuals.
The keypad contains 4 function buttons (5), an LCD display (3),
a system indicator (2), status indicators A, B, C, D (1), a keypad with
an RFID chip card/tag reader (4).
Figure 1: 1 – status indicators A,B,C,D; 2 – system indicator; 3 – LCD
display; 4 – keypad and the RFID reader; 5 – function buttons A, B, C, D;
6 – keypad opening tab; 7 – batteries; 8 – detachable BUS terminals;
9 – tamper contact; 10 – mini USB connector; 11 – production number.
Installation
1. Open the keypad housing by pressing the tab on the bottom (6)
using a screwdriver which will release the keypad from its back
part.
2. Screw the back part on a selected place.
3. Insert two CR123A lithium batteries in the keypad.
4. Insert the keypad back into the back part.
5. Proceed according to the control panel installation manual.
Basic procedure:
a. The JA-111R radio module must be installed in the control
panel. The keypad must be in its communication range.
b. When the device is switched on, the system indicator (2)
will start showing yellow light to indicate that the keypad
has not yet been enrolled to the system.
c. Open the N-Link software, select the required position in
the Devices window, and click on the Enroll button which
will open the enrollment mode.
d. Press the keypad cover which will enroll the keypad and
the yellow LED indicator will switch off, which may take
afew seconds. The enrollment signal can be sent by
inserting the batteries in the keypad or pressing the tamper
contact.
Notes:
−Enrollment is also possible by entering its production code
(11)in the N-Link software or using a bar code scanner. All
numbers stated under the bar code must be entered (e.g.
1400-00-0000-0001).
Installation of a magnetic contact
The keypad supports connection of a door detector. The IN
input reacts to being disconnected from the common GND
contact. The control panel’s reaction to an activated IN input is
configurable in the N-Link SW.
Figure 2: connecting a magnetic contact
Setting the properties
Go to the Devices window in the N-Link software. When you are
at the keypad position, click on the Internal settings option which will
display a dialogue window to configure its settings and function
buttons. Internal settings are separated into 2 basic tabs: Function
and Settings.
The Function tab:
Date and time – Displays the current time in the top-right corner of
the display
The system is not prepared to be Set – Indicates an obstacle
preventing setting the control panel.
User defined text – Enables showing any text, for example the
phone number of an installer company, etc.
Buttons Function – On the left is a selection of button functions.
On the right is a selection of Sections or PG outputs to which the
functions will be assigned. A function button can be assigned with
these functions: None, Unsetting/setting, Unsetting/partial setting,
Unsetting/partially setting/setting, Section indication, Panic, Fire,
Audible panic, Medical Troubles, PG ON/OFF, PGON, PG OFF, PG
indication, PG indicates inversely, Common functional button.
Authorization – Setting and Unsetting requires user authorization.
When this parameter is disabled the function buttons can be operated
without authorization, however this does not apply to Unsetting
a section which always requires authorization. Both ON and OFF
statuses of PG outputs can be configured to be operated with or
without authorization.
Section controlled by authorization – Selection of sections which
can be controlled by authorization (using an RFID chip or a code)
PG control – Selection of PG outputs which can be controlled
by authorization (using an RFID chip or a code)
Import – Enables copying settings from other keypads of the same
type and FW version, which have already been enrolled. For
example, this can be utilized when the building has multiple entrances
and it is necessary for all keypads to have identical functions.
In addition, this function can also be used when replacing a faulty
keypad with another. The Import button provides the history of
keypad settings on a particular position of the device.
Logo – The keypad can display a black and white picture of 128 x
64 pixels (such as a company logo etc.) which stays on the screen for
25 seconds after the last keypad operation.
The Setting tab:
Acoustic indication of selected sections:
Higher volume – Increased volume of indication (it does not apply
to alarm).
Alarms – Indicates alarm (sounds a siren).
Entrance delay – Continuous sound during the entrance delay.
Exit delay – Slow beeping (1/s)
Exit delay when partially set – Slow beeping (deactivated by
default).
Button status change –Beeps once when a status is changed.
Function:
Optical indication setting:
1. Indicates permanently – The keypad indicates permanently.
When the mains electricity is disconnected it indicates the
same way as option 3. When mains electricity is restored the
keypad indicates permanently again.
2. Section/PG status change on keypad – The status
change of a section/PG is indicated by a specific function
button and a status indicator. Entrance delay and alarms
are indicated by all function buttons and status indicators.
3. Section/PG status change on button – The keypad indicates
after a change of the section/PG status, entrance delay and
alarm only by a particular button and a section indicator.
4. Button status change on keypad – The keypad indicates
after a change of the section/PG status by a particular button
and a section indicator. Entrance delay and alarms are
indicated acoustically only.
5. Entrance delay/Alarms on button – The keypad indicates
entrance delays and alarms with a function button and a
status indicator. Change of section/PG status is not
indicated visually or acoustically.
JA-15E Wireless keypad
JA-15E Wireless keypad 2 / 3 MNX53101
6. Wake-up by pressing –The keypad starts to optically and
acoustically indicate after the front cover has been opened
and also when a key or a function button has been pressed.
RFID reader:
In order to save energy we limit the RFID reader to function for
3 seconds after pressing the keypad cover. The RFID reader can
be also completely disabled. This setting applies to wireless
keypads as long as they are permanently supplied by an external
power supply, otherwise their RFID readers will always turn off
automatically.
Permanently ON – the RFID reader is always active. This
works only when the Optical indication setting is set to the option
number 1 - Indicates permanently.
Activated by pressing – When the keypad is activated the
RFID wakes up for 3 seconds.
Disabled – RFID reader is permanently disabled.
Activated by pressing or authorization requirement – the
keypad wakes up after pressing a button on a keypad cover
or by an authorization request, for example during the entrance
delay.
Unset section by authorization only during an entrance
delay – using an access code or an RFID tag will unset a section
where an entrance delay has been triggered (provided the user
has access to the section). This authorization can be used with
wireless keypads only when they declare an entrance delay.
WARNING: This function is not recommended when the control
panel is configured to use a Common section. Unwanted
unsetting may occur to all sections assigned to the Common
section or it may even occur to the whole control panel (when
pressing the Unsetting button is followed by authorization).
Delayed panic – this function triggers a panic alarm (silent or
loud) with an adjustable delay during which the alarm can be
cancelled. Activation and deactivation is done by a function button
configured to Panic or Silent panic functions. The button pressed
once triggers the delay. Press the button the second time to
cancel the delay. When authorization is enabled then it is required
for activation and deactivation. The delay is adjustable from 1 to
255 seconds.
Backlight intensity
Indicators – Backlight intensity of indicators.
Functional buttons – Backlight intensity of the function buttons.
Keypad – Backlight intensity of the keypad.
Display – Backlight intensity of the LCD display.
Contrast – LCD display contrast.
A keypad configuration which complies with
certification requirements
must be selected
from the list of System profiles in the
Parameters tab of the N-Link SW.
Automatic stand-by mode
When the keypad is battery supplied it preserves energy by
turning off the system indication and the display after keys on
the keypad haven’t been pressed within 10 second or when
the keypad cover is closed. However the keypad still maintains
communication with the control panel and will for example signal
entrance delay. The keypad will be completely active when the
keypad cover is opened or pressed.
Alternative power supply
The keypad can be supplied from an external power supply
with 12 V DC connected in +U and GND terminals. You can use
the DE06-12 Power adaptor suitable for concealed installation.
When the keypad is supplied externally it will communicate with
the control panel permanently and it will indicate system statuses
according to the selected parameters in Internal settings in
the Devices tab. If the alternative power supply is used keep
the batteries in the detector, they will provide back up in case
the power supply is disconnected. Batteries inserted in the
detector cannot be recharged by the external power supply.
Changing the batteries
The keypad automatically checks its own battery status. When
the batteries are close to being depleted, it will inform the control
panel that the batteries need to be replaced. They should be
replaced within two weeks after the message appears. The
control panel must be switched into Service mode before
removing the keypad from the back part otherwise a tamper alarm
will be triggered.
Note:In order to make sure the keypad works correctly, we
recommend using batteries supplied by the distributor or other
quality brand lithium batteries.
Optical indication
System indicator:
Continuous green light - Normal operation. Sections
controlled by the keypad are OK, no faults.
Continuous yellow light - Normal operation, reported faults
in some of the controlled sections. You can get more detailed
information via the LCD keypad menu after user authorization
depending on the user access rights.
Optical indication followed by a rotating JABLOTRON logo on
the LCD keypad represents a radio communication fault
between the control panel and the keypad
Continuous red light – The keypad is in BOOT mode, used
while upgrading firmware.
Flashes green (2Hz) – Ongoing authorization during which
the user can change the statuses of the function buttons
or browse the keypad menu. Authorization times out after 8
seconds from the last time any of the buttons had been pressed
or it can be cancelled by pressing ESC.
Flashes yellow (8Hz) - Unsuccessful setting warning indication
Flashes red (8Hz) - Indication of a currently triggered alarm
in one of the sections controlled by the given keypad. The type of
alarm, name of the section where an alarm has been triggered
and the source of the triggered alarm are visible on the LCD
keypad.
Flashes alternately red/yellow - Triggered alarm with an
active fault indication.
Flashes alternately green/red – Ongoing authorization with
an alarm memory.
Flashes alternately green/yellow – Ongoing authorization with
an active fault indication.
Flashes yellow 2x every 2 seconds - Programming / Service
mode. All indication is disabled, function keys along with the
keypad menu are unavailable for users and the Administrator.
The keypad menu is only available for a service technician unless
a PC is connected to the control panel.
Flashes red 2x every 2 seconds - Alarm memory indication.
Flashes yellow 1x every 2 seconds - Fault indication on a
keypad which is in sleep mode (only valid for the EN50131-1
profile).
Flashes red 1x every 2 seconds - Alarm memory indication
on a keypad which is in sleep mode (only valid for the EN50131-1
profile).
No indication – The keypad is in sleep mode.
Function buttons and status indicators – the status of the
function buttons is simultaneously indicated by the status
indicators A, B, C, D.
Continuous green light - Section status is Unset or a PG
output is OFF.
Flashes green (4Hz) – Ongoing entrance delay. The control
panel waits to be Unset.
Continuous yellow light - Section status is Partially set.
Continuous red light - Section status is Set or a PG output is ON.
Flashes yellow (4Hz) - The control panel expects authorization
when partially set or it reports a fault during partial setting.
Flashes yellow (8Hz) - Unsuccessful setting warning
indication.
Flashes red (4Hz) – The control panel waits for authorization
during setting or it reports a problem during setting.
Flashes red (8Hz) - Alarm memory indication. It is indicated
until it is cancelled.
No light - Service mode or a blocked section after an alarm
(after blocking and cancelling alarm memory indication).
JABLOTRON ALARMS a.s.
Pod Skalkou 4567/33 46601 Jablonec n. Nisou
Czech Republic www.jablotron.com
||
|
JA-15E Wireless keypad
JA-15E Wireless keypad 3 / 3 MNX53101
Acoustic indication
It can be set regardless of the keypad’s optical indication and
sleep mode. The keypad can indicate entrance/exit delay or
alarm. During valid authorization (by a user code or RFID card),
the acoustic indication of exit delays is suppressed. By pressing
the functional button the keypad is muted permanently. Entrance
delay and alarm are indicated until their time expires, unless the
activation button is pressed.
Detector FW update
The detector support wireless FW updating which is done in
Service mode via the N-Link software.
1. Select Control panel

Firmware update. You’ll see
JA-15E in the dialog window. If N-Link contains newer
firmware than the one in the keypad then it will be
automatically offered.
2. Pressing the OK button will perform update of selected
devices.
3. After the FW update is finished, check the keypad’s internal
settings in the Internal settings in the Devices tab.
4. Check the keypad’s functionality.
Note:
−The mini USB connector (10) is used to update the firmware
by connecting the keypad with a computer via a mini USB
cable. Use this method when wireless update fails.
Technical specifications
Power 2 x Lithium battery type CR123A
Please note: Batteries are not included
Typical battery lifetime 1-2 years according to settings
Low battery voltage detection 5 V
External supply input power 0,5 W
Communication band 868.1 MHz, JA-10 protocol
Communication range approx. 200 m (open area)
RFID frequency 125 kHz
Size 120x130x30 mm
Weight 215 g
Classification Grade 2/environmental class II/ACE type B
(if selected in the N-Link SW)
- According to EN 50131-1, EN 50131-3, EN 50131-5-3, EN 50131-6
- Operational environment indoor general
- Operating temperature range -10 to +40 °C
- Average operational humidity 75% RH
- Certification body Trezor Test
Also complies with ETSI 300 220-2, ETSI EN 300 330-2,
EN 50130-4, EN 55032, EN 58581,EN 68368-1
Can be operated according to ERC REC 70-03
JABLOTRON ALARMS a.s. hereby declares that the JA-15E is in
a compliance with the relevant European Union harmonization
legislation: Directives No: 2014/53/EU, 2014/35/EU, 2014/30/EU,
2011/65/EU. The original of the conformity assessment can be
found at www.jablotron.com - Section Downloads.
Note:
Although this product does not contain any harmful
materials we suggest y
ou return the product to the dealer
or directly to the producer after use.

Other jablotron Keypad manuals

jablotron JA-80E User manual

jablotron

jablotron JA-80E User manual

jablotron JA-10E User manual

jablotron

jablotron JA-10E User manual

jablotron 100 User manual

jablotron

jablotron 100 User manual

jablotron KB-2051 User manual

jablotron

jablotron KB-2051 User manual

jablotron JA-150E User manual

jablotron

jablotron JA-150E User manual

jablotron JA-63F User manual

jablotron

jablotron JA-63F User manual

jablotron JA-115E User manual

jablotron

jablotron JA-115E User manual

jablotron JA-155E User manual

jablotron

jablotron JA-155E User manual

jablotron JA-60F User manual

jablotron

jablotron JA-60F User manual

jablotron JA-114E User manual

jablotron

jablotron JA-114E User manual

jablotron KB-1051 User manual

jablotron

jablotron KB-1051 User manual

Popular Keypad manuals by other brands

Apxalarm 6150RFAPX2 Installation and setup guide

Apxalarm

Apxalarm 6150RFAPX2 Installation and setup guide

Russound A-K3 installation manual

Russound

Russound A-K3 installation manual

Bosch DS7446KP installation instructions

Bosch

Bosch DS7446KP installation instructions

rako WCM-041 instruction manual

rako

rako WCM-041 instruction manual

AAS ADVANTAGE DKE 26-100L User & installation manual

AAS

AAS ADVANTAGE DKE 26-100L User & installation manual

Linear Pro Access LPWKP Operation instructions

Linear

Linear Pro Access LPWKP Operation instructions

Aeware in.k400 manual

Aeware

Aeware in.k400 manual

AMC UNIKA manual

AMC

AMC UNIKA manual

Aritech ATS111-N Series Installation sheet

Aritech

Aritech ATS111-N Series Installation sheet

Unitech K19 Specifications

Unitech

Unitech K19 Specifications

Alarm Lock A-100 - A-100IMWP manual

Alarm Lock

Alarm Lock A-100 - A-100IMWP manual

Channel Vision A0127 instructions

Channel Vision

Channel Vision A0127 instructions

Siemens SPCK420 user manual

Siemens

Siemens SPCK420 user manual

Crestron Cameo C2N-CBD Operations & installation guide

Crestron

Crestron Cameo C2N-CBD Operations & installation guide

Dormakaba La Gard 5750 User operating instructions

Dormakaba

Dormakaba La Gard 5750 User operating instructions

HAI 54A00-1 manual

HAI

HAI 54A00-1 manual

AMERICAN ACCESS SYSTEMS 19-01i Installation and programming instructions

AMERICAN ACCESS SYSTEMS

AMERICAN ACCESS SYSTEMS 19-01i Installation and programming instructions

CAMDEN CV-634PR installation instructions

CAMDEN

CAMDEN CV-634PR installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.