manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. jablotron
  6. •
  7. Security Sensor
  8. •
  9. jablotron JA-180S User manual

jablotron JA-180S User manual

JABLOTRON ALARMS a.s.
Pod Skalkou 4567/33 46601 Jablonec n. Nisou
Czech Republic www.jablotron.com
||
|
The JA-180S wireless fire detector MHS53800
1
The JA-180S wireless fire detector
This device is designed to detect the presence of fire inside residential or
commercial buildings. It should not be installed in industrial premises. The
battery-powered detector has a built-in local warning siren combined with a
red LED indicator. Alarm information can also be transferred via a wireless
connection to Jablotron systems.
The JA-180S detector combines an optical smoke sensor with a heat
sensor. Both sensors have their outgoing signals processed digitally, resulting
in higher false alarm immunity. The optical sensor works using a light diffusion
principle and is very sensitive to the presence of large-sized particles which
are characteristic of dense smokes. By contrast, the sensor is less sensitive to
small-sized particles which are typical of cleanly burning fires. In particular, the
smoke sensor is not capable of detecting the by-products of cleanly-burning
fluids such as alcohols, for instance.This deficiency is compensated for bythe
built-in heat sensor. This sensor provides a slower reaction when compared to
the smoke sensor, but is much better at reacting to fires with rapidly rising heat
producing onlya little smoke.
Smoke / heat sensor participation is configurable by jumper-settings.
Detection range, detector positioning
The smoke detector must be installed so that any smoke easily drifts
into the detector, such as on the ceiling. It is suitable for residential
buildings, but not suitable for free spaces or an outdoor environment.
However, the detector is not suitable for installation in outdoor spaces or
interiors with an extremely high ceiling (more than 5 m) where fire by-products
would not reach the detector position. The detector must always be placed
in the section leading to the exit of the apartment (escape route), see
Figure 1. If the apartment has a floor area greater than 150 m2, an
additional detector is required in the apartment, see Fig.2. An
apartment block must be equipped with a detector in each apartment.
In family houses and residential flats or maisonettes a detector must
also be placed at the highest point of common hallways or spaces
(escape routes), see Fig.3.
KITCHEN
MINIMUM SECURITY
FOR MORE SECURITY
LIVING ROOM
BEDROOM
BEDROOMS
Fig. 1
BEDROOMS
BEDROOM
BEDROOM
LIVING ROOM
KITCHEN
MINIMUM SECURITY
FOR MORE SECURITY
Fig. 2
It is recommended to place
additional detectors in rooms
where people sleep or in rooms
with an increased risk of fire, see
Fig.2.
Positioning on level ceilings
Place the detector in the center
of the room, as level as possible.
Detectors must not be recessed
into the ceiling (worse conditions
for the spread of smoke). Never
place the detector in a room
corner (ensure a distance of at
least 0.5 meters from the corner),
see Fig 4.
BED
ROOM
KITCHEN
MINIMUM SECURITY
BED
ROOM
BED
ROOM
Fig. 3
x
Installation on sloping ceilings
If the ceiling is not suitable for mounting on a level surface (e.g. a
room under a roof ridge), the detector can be installed as in Figure 5.
0.5m
CEILING
BEST LOCATION
(CENTRE OF CEILING)
ACCEPTABLE
LOCATION
Fig. 4
90cm
Fig. 5
x
Walls, partitions, barriers and lattice ceilings
The JA-180S must not be installed closer than 0.5 m from any wall or
partition. A narrow room with a width of less than 1.2m requires the
detector(s) to be placed at a distance of at least one third of the room’s width
away. In the case of separating walls (partitions, warehouse objects) which do
not reach the ceiling, the space is considered to be fully separated if the
gap between the top of the separating wall and the ceiling does not
exceed 0.3 m. A free space of at least 0.5m is required under the detector.
Irregularities in ceiling shape which do not exceed 5% of ceiling height are
considered insignificant – the ceilingcan be regarded as being even and limits
from the table are applicable. However, any irregularity (including beams)
exceeding 5% of the ceiling height is considered to be a wall with the
consequences stated above.
x
Ventilation and air circulation
The detectors must not be installed directly by a fresh air inlet, e.g.
air conditioning vents. In the case of air being supplied through a perforated
ceiling, each detector must be placed so that no perforation hole occurs
within 0.6m of the detector.
x
Avoid installing the detector in the following locations:
Places with poor air circulation (niches, corners, apexes of A-shaped
roofs).
Places exposed to dust, cigarette smoke or steam.
Places with over-intense air circulation (close to ventilators, heat
sources or air conditioning outlets).
Kitchens and other cooking places (because steam, smoke or
oily fumes can reduce detector sensitivity).
Beside lights (electrical interference can cause a false alarm)
Areas with lots of small insects
Caution: Most false alarms are due to detector
misallocation
See CEN/TS 54-14 standards for detailed installation guidelines.
Installation
1. Open the detector by turning the rear cover to the left and remove the
battery
2. Screw the rear cover onto the desired location
3. Set the required function using the jumpers – see the table below
4. Please read the receiving device (control panel) installation manual before you
connect the battery (remove the insulation tape) and set the control panel to
enrollment mode
5. When the battery is connected, the detector sends a signal to connectto the
system
6. After installing the detector, allow approx. 20 seconds for
stabilisation. This period is indicated by the LED being continuously
lit and is followed by an auto-test. Successful performance of the
auto-test is confirmed acoustically.
o
p
e
n
c
l
o
s
e
LITHIUM
3,6V AA
TEST
1
ON INSTANT alarm mode 3 OFF
1OFF FIRE alarm mode 4 OFF Smoke (EN 14064)
or heat (EN 54-5)
ON Memory ON 3 ON
2OFF Memory OFF 4 OFF Only smoke (EN 14604)
(heat indifferent)
3 OFF
4 ON
Only heat (EN 54-5)
(smoke indifferent)
3 ON
1
1234
ON
OFF
4 ON
Smoke and heat
(both simultaneously)
Testing the detector is automatically performed up to 10 secs
after battery insertion. New settings are saved directly afterwards.
J1: The FIRE / INST alarm mode jumper sets the reaction of the
system. FIRE = alarm is triggered even if the system is disarmed while
INST = alarm is triggered only in an armed system. The FIRE / INST
jumper only has an effect if the detector has a natural reaction
assigned to its address in the Jablotron control panel. It also has no
effect when used with a JA-182N or JA-180N receiver.
The JA-180S wireless fire detector MHS53800
2
Warning: In the INST position, while the system is disarmed, it
is not protecting against fire. This setting also fully disables the
optical and acoustic indication on the detector itself.
J2: Alarm memory: If the event memory is ON at the time of alarm,
alarm LED indication continues even if normal conditions are restored.
The indication can be stopped by pressing the button (indication is
valid only for FIRE settings).
J3 and J4: Smoke / heat sensor participation
Optical smoke sensor:Smoke entry into the detector is indicated as a
pre-alarm state by the LED flashing. If the smoke threshold density is
exceeded, a siren sound is generated (indication is valid only for FIRE
settings).
Heat sensor: indication logic is equal to that of the smoke sensor.
Whenever the detector cover is opened, a tamper signal is sent.
Testing the detector
The functioning of the detector can be tested by pressing and
holding the test button (e.g. for 1 sec). This activates the siren and the
LED flashes (LED only if the fire reaction is set). The strength and
quality of detector signals can be measured by the control panel in
Service mode. During testing by the test button, the detector transmits
signals which can not trigger fire alarms in the control panel.
Warning: Never start a fire in a building to test the detector.
Instead, use smoke-simulating aerosols for realistic testing.
Silencing the siren during an alarm
During a fire alarm, the detector LED flashes 2 times briefly and the
built-in siren sounds (at a higher intensity than during a test). Under
these conditions the siren can be silenced by pressing the test button
for approx. 3 sec. The LED will continue to flash until the smoke clears
from the room (indication is valid only for FIRE settings).
However, if normal conditions are not restored within approx. 10
minutes (the smoke does not clear from the room or the temperature
does not drop), the siren re-activates.
Fault indication
The detector performs regular self-testing. If a fault is detected in the
detector, its LED will start to flash rapidly. In such a case, disconnect
the battery from the detector, and after about 20 secs, re-connect it. If
after a minute the LED still flashes, then send the detector off for
repair.
Battery replacement
The detector monitors its battery voltage and if too low, a transmission is
sent to the control panel to inform the installer or user. The detector
continues to function but with a short LED flash every minute. Battery
replacement should not be delayed by more than two weeks. This
should be done by a qualified technician with the control panel in
Service mode.
After battery replacement, test the functioning of the detector using
its test button. Expired batteries should not be thrown into the garbage,
but disposed of according to local regulations.
Removing the detector from the system
If a detector is removed, the control panel announces the removal.
The detector has to be deleted in the control panel before intentional
removal.
Technical parameters
Voltage: Lithium battery type or LST14500 (AA 3.6V / 2,4 Ah)
Typical battery lifetime approx. 3 years
Communication band 868.1 MHz, Jablotron protocol
Smoke detection optical, scattered light
Smoke sensor sensitivity m = 0.11 - 0.13 dB/m to EN 54-7
Temperature detection class A2 to EN 54-5
Fire-alarm temperature +60 °C to +70 °C
Acoustic power of the built-in siren 80 dB/m
Operational temperature range -10°C to +80 °C
Dimensions, weight diameter: 126 mm, height: 65 mm, 200 g
Complies with EN 54-7, EN 54-5 class A2, EN 54-25,
ETSI EN 300220,EN 50130-4, EN 55022, EN 60950-1
Can be operated according to ERC REC 70-03
JABLOTRON ALARMS a.s. hereby declares that the JA-180S is in
compliance with the essential requirements and other relevant provisions of
Directives 1999/5/EC and 1989/106/EC. The original of the conformity
assessment can be found at www.jablotron.com, Technical support
section. Note: Although this product does not contain any harmful
materials we suggest you return the product to the dealer or
directly to the producer after use.

Other jablotron Security Sensor manuals

jablotron JA-151P-WG User manual

jablotron

jablotron JA-151P-WG User manual

jablotron JA-120PC User manual

jablotron

jablotron JA-120PC User manual

jablotron JA-60P User manual

jablotron

jablotron JA-60P User manual

jablotron JA-111ST User manual

jablotron

jablotron JA-111ST User manual

jablotron JA-80IR User manual

jablotron

jablotron JA-80IR User manual

jablotron JA-120PW User manual

jablotron

jablotron JA-120PW User manual

jablotron JA-151P-WG User manual

jablotron

jablotron JA-151P-WG User manual

jablotron JA-152M User manual

jablotron

jablotron JA-152M User manual

jablotron JA-85P User manual

jablotron

jablotron JA-85P User manual

jablotron JA-159P User manual

jablotron

jablotron JA-159P User manual

jablotron JB-EXT-TH-R User manual

jablotron

jablotron JB-EXT-TH-R User manual

jablotron JK-16 PROFI User manual

jablotron

jablotron JK-16 PROFI User manual

jablotron JA-151ST-A User manual

jablotron

jablotron JA-151ST-A User manual

jablotron JA-151P-WW User manual

jablotron

jablotron JA-151P-WW User manual

jablotron JA-83P User manual

jablotron

jablotron JA-83P User manual

jablotron JA-181M User manual

jablotron

jablotron JA-181M User manual

jablotron JA-187P User manual

jablotron

jablotron JA-187P User manual

jablotron JA-60V User manual

jablotron

jablotron JA-60V User manual

jablotron JA-158P User manual

jablotron

jablotron JA-158P User manual

jablotron JA-158P User manual

jablotron

jablotron JA-158P User manual

jablotron JA-80PB User manual

jablotron

jablotron JA-80PB User manual

jablotron JA-84P User manual

jablotron

jablotron JA-84P User manual

jablotron JA-152SHM User manual

jablotron

jablotron JA-152SHM User manual

jablotron JA-60N User manual

jablotron

jablotron JA-60N User manual

Popular Security Sensor manuals by other brands

Inovonics EN1751 installation instructions

Inovonics

Inovonics EN1751 installation instructions

BUCKINGHAM MFG 488 Series Replacement instructions

BUCKINGHAM MFG

BUCKINGHAM MFG 488 Series Replacement instructions

Intelbras VP 5311 MW Pet user manual

Intelbras

Intelbras VP 5311 MW Pet user manual

DANLERS WM-HBWD IP66 Series quick start guide

DANLERS

DANLERS WM-HBWD IP66 Series quick start guide

REXROTH DBA Series manual

REXROTH

REXROTH DBA Series manual

SICK Prime KTX-WP92342242ZZZZ manual

SICK

SICK Prime KTX-WP92342242ZZZZ manual

Somogyi Elektronic home PIR 06/WH instruction manual

Somogyi Elektronic

Somogyi Elektronic home PIR 06/WH instruction manual

Jade JD-WD10 manual

Jade

Jade JD-WD10 manual

SYR SefeTech Connect Operation and maintenance

SYR

SYR SefeTech Connect Operation and maintenance

AGFA XD 17 user manual

AGFA

AGFA XD 17 user manual

Honeywell Satronic IRD 1020 manual

Honeywell

Honeywell Satronic IRD 1020 manual

CLAS OE 3010 manual

CLAS

CLAS OE 3010 manual

Besantek BST-HVD7 instruction manual

Besantek

Besantek BST-HVD7 instruction manual

Texora ULTRA-V Instructions for use

Texora

Texora ULTRA-V Instructions for use

Bosch RF940E Installation instructions and operators manual

Bosch

Bosch RF940E Installation instructions and operators manual

LEGRAND 6 460 03 instruction manual

LEGRAND

LEGRAND 6 460 03 instruction manual

Vaxcel T0270 Assembly and installation instructions

Vaxcel

Vaxcel T0270 Assembly and installation instructions

Berker 102 09 Operation and assembly instructions

Berker

Berker 102 09 Operation and assembly instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.