The function of this device depends upon the software. Detailed information on load-
able software and attainable functionality as well as the software itself can be ob-
tained from the manufacturer´s product database. Planning, installation and commis-
sioning of the device are carried out with the aid of KNX-certified software. The latest
versions of product database and the technical descriptions are available on our
website.
Intended use
– Switching of electrothermal valve drives for heaters or cooling ceilings
– Installation in sub-distribution units on DIN rail according to DIN EN 60715
Product characteristics
– Switching operation or PWM operation
– Valve drives with characteristics opened or closed without power controllable
– Valve drives 230 V or 24 V controllable
– Disabling of individual outputs via bus
– Overload-protected, short circuit-protected
– Protection against jamming valves
– Cyclical monitoring of the input signals can be parameterized
– Feedback via bus, e.g. in case of overload or sensor failure
– Bus connection with standard bus terminal
PWM operation: electrothermal valve drives only have the positions "open"
and "closed". In PWM operation, switch-on and switch-off during the drive's
cycle time achieves an almost constant behaviour.
Overload protection
In order to protect the device and connected valve drives, in case of overload or
short-circuit the device determines which output is involved and switches it off. Non-
overloaded outputs continue to work, which means that the rooms in question are still
heated.
– In case of major overloads the actuator initially switches all off the outputs
A1...A6 off.
– In the case of more minor overloads the actuators switches output groups
A1...A3 and/or A4...A6 off.
– The actuator determines the overloaded output in up to 4 test cycles.
– If in the event of only a minor overload it is not possible to unambiguously
identify any output as overloaded, then the actuator switches individual out-
puts off one after the other.
– The overload can be reported to the bus for each output.
Basic heating actuator 6-gang
4 / 9
82590713 01.02.2023
J0082590713