BM 70 A Kurzanleitung Seite: 10 4. Entwurf 03/97
Configuration menu (Version 3.00)
Function (Fct.) Input range Description
1.0 OPERATION
1.1 DISPLAY
1.1.1 FCT.DISP identical with 3.2.1
1.1.2 UNIT.LENGTH identical with 3.2.2
1.1.3 UNIT.CONV. identical with 3.2.3
2.0 TEST
2.1 HARDWARE
2.1.1 MASTER Master hardware test.
2.1.2 DISPLAY Display hardware test.
2.1.3 STATUS Status information for Service
2.2 CUR.OUTP.I
2.2.1 VALUE I Value display Display of actual value of the current
output.
2.2.2 TEST I Select 2 mA/4 mA/6 mA/...
... 20 mA/22 mA Output of selected value to the current
output. With safety query.
2.3 SW.OUTP.
2.3.1 TEST S Select OPEN/CLOSE Switch switching contact on/off.
With safety query.
2.4 FIRMWARE
2.4.1 MASTER Display Display of master firmware version.
2.4.2 DISPLAY Display Display of display firmware version.
3.0 INSTALL.
3.1 BASIC.PARAM
3.1.1 TANKHEIGHT Select unit m/cm/mm/
inch/Ft
Enter
0.00 [m] ... max. tank height
Enter tank height (see explanatory
notes).
The unit entered here is also used for
all other length entries.
3.1.2 BLOCKDIST Enter 0.10 [m] ... tank height Enter block distance = non-measurable
range below bottom edge of flange
(see explanatory notes).
3.1.3 ANTENNA Select STANDARD
WAVE-STICK Select antenna type.
3.1.4 ANT.EXT. Enter 0.00 [m] ... tank height Enter length of antenna extension.
3.1.5 DIST.PCE. Enter 0 ... 2000 [mm] Enter length of distance piece above
flange.
3.1.6 STILLWELL Select NO / YES
If “YES“: enter 25 ... 200 [mm] Selection: without or with still well.
With still well: enter inside diameter in
[mm].
3.1.7 REF.OFFSET Enter -10.00...0...+10.00 [m] Reference offset (special function).
3.1.8 TKB.OFFSET Enter -100.00...0...+100.00 [m] Tank bottom offset (special function).
3.2 DISPLAY
3.2.1 FCT.DISPLAY Select LEVEL
DISTANCE
CONVERSION
REFLECTION
Select function of display
(value to be displayed).
3.2.2 UNIT.LENGTH Select m/cm/mm/
inch/Ft/
PERCENT/BARGRAPH
Select unit for length value to be
displayed (only for level and distance).
3.2.3 UNIT.CONV. Select m3/l(Liter)/US Gal/
GB Gal/Ft3/bbl/PERCENT/
BARGRAPH/USER UNIT
Select unit for conversion value to be
displayed (“volume table“).
(see explanatory notes)
3.2.4 USER UNIT Text entry 10 characters Enter user-defined unit for the
conversion table.
3.2.5 ERROR MSG. Select NO/YES Select whether error messages to be
shown in display..
3.3 SIG.OUTP.
3.3.1 FUNCTION I Select OFF/LEVEL/Select function of the current output.