manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. LEGRAND
  6. •
  7. Controllers
  8. •
  9. LEGRAND Celiane Series Quick start guide

LEGRAND Celiane Series Quick start guide

This manual suits for next models

3

Other LEGRAND Controllers manuals

LEGRAND 0 884 07 User manual

LEGRAND

LEGRAND 0 884 07 User manual

LEGRAND 0 676 46 User manual

LEGRAND

LEGRAND 0 676 46 User manual

LEGRAND Arteor User manual

LEGRAND

LEGRAND Arteor User manual

LEGRAND 0670 53 User manual

LEGRAND

LEGRAND 0670 53 User manual

LEGRAND 0 488 51 User manual

LEGRAND

LEGRAND 0 488 51 User manual

LEGRAND Wattstopper LMRC-221 User manual

LEGRAND

LEGRAND Wattstopper LMRC-221 User manual

LEGRAND Bticino H4652 User manual

LEGRAND

LEGRAND Bticino H4652 User manual

LEGRAND 672 40 User manual

LEGRAND

LEGRAND 672 40 User manual

LEGRAND LE00282AC User manual

LEGRAND

LEGRAND LE00282AC User manual

LEGRAND radiant WNRCB40 User manual

LEGRAND

LEGRAND radiant WNRCB40 User manual

LEGRAND 0 698 19L User manual

LEGRAND

LEGRAND 0 698 19L User manual

LEGRAND Adorne LC7001 User manual

LEGRAND

LEGRAND Adorne LC7001 User manual

LEGRAND MRD6 v2 User manual

LEGRAND

LEGRAND MRD6 v2 User manual

LEGRAND 3550 User manual

LEGRAND

LEGRAND 3550 User manual

LEGRAND adorne WZ3ACB40 User manual

LEGRAND

LEGRAND adorne WZ3ACB40 User manual

LEGRAND 0 673 69 User manual

LEGRAND

LEGRAND 0 673 69 User manual

LEGRAND Adorne LC7001 User manual

LEGRAND

LEGRAND Adorne LC7001 User manual

LEGRAND adorne WNACB40 User manual

LEGRAND

LEGRAND adorne WNACB40 User manual

LEGRAND Valena Next User manual

LEGRAND

LEGRAND Valena Next User manual

LEGRAND BTICINO MYHOME F411U2 User manual

LEGRAND

LEGRAND BTICINO MYHOME F411U2 User manual

LEGRAND 0 884 06 User manual

LEGRAND

LEGRAND 0 884 06 User manual

LEGRAND Radiant WNRCB40 User manual

LEGRAND

LEGRAND Radiant WNRCB40 User manual

LEGRAND EasyIP VADDIO PCC User manual

LEGRAND

LEGRAND EasyIP VADDIO PCC User manual

LEGRAND Pass & Seymour RFP User manual

LEGRAND

LEGRAND Pass & Seymour RFP User manual

Popular Controllers manuals by other brands

Sunricher SR-ZV9003T3-RGBW-US Installation

Sunricher

Sunricher SR-ZV9003T3-RGBW-US Installation

Ksenia intro Installation and configuration manual

Ksenia

Ksenia intro Installation and configuration manual

Inovance CAN200 Series manual

Inovance

Inovance CAN200 Series manual

Gauzy LC6 FLEX Controller Installation and operation guide

Gauzy

Gauzy LC6 FLEX Controller Installation and operation guide

Viking SLP-1 Technical practice

Viking

Viking SLP-1 Technical practice

CKD KBX-30E-U Series instruction manual

CKD

CKD KBX-30E-U Series instruction manual

Sharp Energy Sun Flux User manual & installation guide

Sharp Energy

Sharp Energy Sun Flux User manual & installation guide

Yamaha RCX40 user manual

Yamaha

Yamaha RCX40 user manual

AB Quality PowerFlex 400 Frames D-H Service bulletin

AB Quality

AB Quality PowerFlex 400 Frames D-H Service bulletin

Yamaha MJC8 owner's manual

Yamaha

Yamaha MJC8 owner's manual

AL-KO ATC operating instructions

AL-KO

AL-KO ATC operating instructions

Savant SmartControl 2 Deployment guide

Savant

Savant SmartControl 2 Deployment guide

GameSir T3S user manual

GameSir

GameSir T3S user manual

Kostal inveor operating manual

Kostal

Kostal inveor operating manual

Emerson Yarway 20-55 Operating and safety instructions

Emerson

Emerson Yarway 20-55 Operating and safety instructions

CoCo ACM-LV24 Quick installation guide

CoCo

CoCo ACM-LV24 Quick installation guide

Brooks SLA5810/20 Installation and operation manual

Brooks

Brooks SLA5810/20 Installation and operation manual

SIGMA TEK SR 011 Technical manual

SIGMA TEK

SIGMA TEK SR 011 Technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

CÉLIANE TECHNICAL GUIDE
SCS BUS S y STEm
1
LG00129-a-UK
Touch control multifunction
Description
This control is a SCS control, which traditional pushbuttons are replaced by capacitive
sensors. Moving the finger close to a sensor is the same as pressing a pushbutton.
The device can be used to perform the functions typical of a special SCS control by
simply moving a finger close to the surface. It is produced in the 2 module flush-
mounting version, 4 keys respectively. Each zone corresponding to a key is marked at
the centre by two light blue LED. When the user moves a finger close to the zone, its
intensity increases sensibly, and remains so until the finger is moved away again. This
effect is necessary to give the user the feeling of activating the control. Therefore, the
LEDs can have two different levels of light intensity. It is however possible to select
different intensity levels using push button "P".
The control may operate in four different modes: self-learning, scenarios, swivelling,
CEN and sound system mode.
- The self-learning mode (cyclic or non-cyclic) allows to associate to each key
most of the typical automation system, sound system, video door entry system
(staircase light, open-door, call to the floor, door lock, and cycling of cameras)
functions, in additional to auxiliary controls.
- The scenario mode can be used to recall, program and delete 4 scenarios of a
scenario module.
-The swivelling mode can be used to drive the 2 consecutive light points or rolling
shutters (or rooms or groups)
- The CEN mode enables using the control with the scenario programmer 035 65
In order to clean the device, it is possible to temporarily disable the sensitive
zones by pressing two diagonally opposite zones at the same time (keys 1 – 4). The
LEDs will flash in sequence. Normal operation is automatically reinstated after 10
seconds.
Key 11.
Key 22.
Key 33.
Key 44.
Configurator housing5.
BUS6.
Selection of the LED intensity and programming pushbutton7.
LegendTechnical data
Power supply from SCS BUS: 18 – 27 Vdc
Max. consumption : 25 mA with LED=MAX
20 mA with LED= MED
17 mA with LED= MIN
Operating temperature: 0 – 40 °C
PL
A
M
SPEP
6
5
3
4
672 43
672 44
672 45
7
2
1
PRODUCT TECHNICAL SHEETS
2
LG00129-a-UK
SPE=0 M=0 Self-learning mode
To activate the programming pushbutton,
only use the screwdriver provided.
Possible function M configurator value
This operating mode can be used to associate one individual control to any key of the device. It is possible to create, delete or
change each control. A specific A/PL address on the system must always be assigned to the control (not to be used by any other
device installed on the BUS), with A=0 – 9 e PL=1 – 9.
0
Programming the Keys
1) Shortly press the key on the rear side, the LEDs will switch in succession;
2) Press, within 20 seconds, the key that needs to be programmed: the LED will
start flashing (0.5s on – 0.5s off), showing that the programming mode has been
enabled;
3) Set the control to be associated with the key using the keys and/or the
corresponding actuator; the LEDs will start to rotate;
4) You can now repeat operations 2 and 3 for all keys, including any keys already
associated, if they need changing;
5) Shortly press the key on the rear part or wait 20 seconds to exit the programming
phase;
Functions which the device can learn:
a. Automation
– ON/OFF actuator; cycling mode operation. Short pressure: ON/OFF actuator;
prolonged pressure: dimmer regulation (only for point-point control)
– Timed ON
– Flashing
– Shutters UP; shutters are rolled up until end of stroke, in bistable mode. Prolonged
pressure: UP function; short pressure: STOP
– Shutters DOWN; shutters are rolled down until end of stroke, in bistable mode.
Prolonged pressure: DOWN function; short pressure: STOP
– Lock/release actuator
– Scenario retrieval from Scenario module 035 51
– Scenario retrieval from Scenario programmer 035 65
b. Video door entry systems
– Door lock control (including during a conversation)
– Staircase light control
– Call to the floor (including general call)
c. Sound diffusion
– Amplifier ON (always in the follow-me mode). Short pressure: amplifier ON;
prolonged pressure: volume regulation UP
– Amplifier OFF. Short pressure: amplifier OFF; prolonged pressure: volume regula-
tion DOWN.
– Cycling of sound sources.
– Radio station or track change.
d. Auxiliary channels
– ON/OFF light auxiliary; cycling mode operation
– Shutters UP; shutters are rolled up until end of stroke, in bistable mode.
Prolonged pressure: UP function; short pressure: STOP
– Shutters DOWN; shutters are rolled down until end of stroke, in bistable mode
Prolonged pressure: DOWN function; short pressure: STOP
– Reset
The configuration can be made in two different modes:
- Physical configuration: connecting the physical configurators to their own
housings
- Virtual configuration: the control may be configured remotely
Configuration
672 43
672 44
672 45
CÉLIANE TECHNICAL GUIDE
SCS BUS S y STEm
3
LG00129-a-UK
NOTE: To delete the programming of all keys at the same time, shortly press the
key on the rear part. The LEDs will switch on in succession; press the rear key again
and keep it pressed for 10 seconds: the LEDs will flash in sequence for approximately
4 seconds, confirming that all key programming settings have been deleted.
Deleting the programming of the keys
1) Shortly press the key on the rear side, the LEDs will switch in succession
2) Press, within 20 seconds, the key to be deleted and keep it pressed for 4 seconds
starting now the deleted key will no longer enable any control until reprogrammed
3) The corresponding LED will flash for 4 seconds; afterwards operation 2 can be
repeated to delete another programming
4) Shortly press the relevant key or wait 20 seconds to exit the deleting mode
SPE=0 M=6 Non cyclic self-learning mode
SPE=0 M=1,2,3,5 Scenario mode
Possible function M configurator value
This mode is a variant of the self-learning mode (M=0), where, however, the keys never work cyclically. Therefore if, for example,
the ON of an actuator or dimmer is learnt, the couple of keys is configured automatically to switch on or increase the light intensity
level for the upper key, and switch off or decrease the level of intensity for the lower one. If, on the other hand, the single function
is learnt (e.g. recalling of a scenario), the other key of the pair remains without function, or retains the previous function. Always
assign to the control a specific A/PL address on the system (not to be used by any other device installed on the Bus), A=0 – 9 and
PL=1 – 9. The functions saved are the same described for M=0
6
Possible function M configurator value
This operating mode is useful if the system includes a scenario module 035 51. The combination is ensured by assigning to both items
the same address, identified by A=0 – 9 and PL=1 – 9. The user may create, delete or change the scenarios saved in the scenario
module, and can recall them using the keys. With this procedure it is possible to save up to 16 scenarios using three 4-key devices.
1-2-3-5
The following table shows the correspondence between the number of the scenario saved in the scenario module and the control keys
in the various possible configurations.
672 43
672 44
672 45
Number of the key M=1 M=5 M=2 M=3
Key 1 scenario 1 scenario 5 scenario 9 scenario 13
Key 2 scenario 2 scenario 6 scenario 10 scenario 14
Key 3 scenario 3 scenario 7 scenario 11 scenario 15
Key 4 scenario 4 scenario 8 scenario 12 scenario 16
PRODUCT TECHNICAL SHEETS
4
The combination of a scenario configured in the scenario programmer 035 65 and the corresponding control activation keys, is performed during the programming of the
scenario itself with the software supplied.
SPE=0 M=0/I; hi; hi M Swivelling modes
Possible function M configurator value
ON/OFF control: On control using the upper key, Off control using the lower key. For point-point controls, the ON/OFF functions
are performed by a quick pressure, while a longer pressure will be used for the adjustments; for the other controls only
the ON/OFF functions are performed
0/1
Control (UP-DOWN for rolling shutters): up-down control to end of stroke hi
Monostable control (UP-DOWN for rolling shutters): up-down control for the time the key is pressed hiM
These modes enable quick installation without the need for learning or scenario modules, allowing control of 2 consecutive light points or rolling shutters. The A PL address is the light
point or rolling shutter controlled by the first pair of keys. The subsequent pairs control the subsequent light points or rolling shutters. If the configurator Amb or Gr are connected to
A, in the same way the 2 pairs of keys control consecutive rooms or groups, starting from the one indicated by the configurator in PL.
The possible A and PL configurations are the following:
- Point-point: A=1 – 9 is the room, PL=1 – 9 is the light point.
- Room: A=AMB, PL=1 – 9 is the no. of the room.
- Group: A=GR, PL=1 – 9 is the no. of the group.
- General: A=GEN, PL=0 all pairs send the same general controls.
Cancel a scenario
1) The scenario module must be in the “self-learning enabled” configuration;
2) Shortly press the key on the rear side, the LEDs will switch in succession;
3) Press, within 20 seconds, the key corresponding to the scenario to be deleted and
keep it pressed for 4 seconds;
4) The corresponding LED will flash for 4 seconds, alternating with the others;
afterwards operation 2 can be repeated to delete another programmin;
5) Shortly press the relevant key or wait 20 seconds to exit the deleting mode;
NOTE:
the entire memory can only be reset from the scenario module: press and hold
down the "DEL" key for 10 seconds after enabling programming on the scenario module.
SPE=0 M=CEN Scenario programmer mode
Possible function M configurator value
Always assign to the control a specific A/PL address on the system (not to be used by any other device installed on the Bus), A=0
– 9, PL=0 – 9.
The A=0, PL=0 configuration cannot be accepted. This operating mode can only be used if the system includes a scenario
programmer (035 65).
CEN
672 43
672 44
672 45
DEL
035 51
Programming a scenario
1) In order to program, change or cancel a scenario, it is necessary to enable the pro-
gramming mode of the Module 035 51 so that the programming status LED is green
(use the lock/unlock key on the Scenario Module for at least 0.5 seconds).
2) Press briefly the pushbutton on the back, the LEDs turn on in succession.
3) Quickly press the key corresponding to the scenario to be programmed: the LED will
start flashing (upon receiving the update of the scenario module), confirming that the
programming mode is active.
4) Set the scenario using the corresponding controls and/or actuators.
5) Press the pushbutton to exit programming: the LEDs flash in succession, it is now
possible to repeat points 2, 3 and 4 for all scenarios, including those keys that have
already been associated, if they need changing.
6) Press the pushbutton on the back to exit programming, or wait 20 seconds to exit
programming automatically.
035 51
Scenario reset
pushbutton
Scenarios/learning reset
LED
Lock/unlock programming
pushbutton
Programming status LED
LG00129-a-UK
CÉLIANE TECHNICAL GUIDE
SCS BUS S y STEm
5
Mode with SPE=1 - sound system mode -
Press the rear key for more than 2 seconds to select among different LED intensities, depending on installation needs.
Once the device has been installed, wait two minutes for the self-calibration procedure to be completed. During this period, controls may be automatically sent to the system.
Selection of the LED intensity
Level when key pressed Level in idle status
100% 60% Default
75% 30%
45% OFF
672 43
672 44
672 45
This function is used to control the amplifiers and the sound system sources.
The functions performed are the following:
1) With a quick pressure of key 1, the following sequence is sent:
- OFF of the sources, only if M > 0
- ON of the M source (source 1 if M=0);
- ON of the amplifier.
2) With an extended pressure of key 1:
- for point-point controls, if the amplifier is already on, only the volume is adjusted
(VOL+); if the amplifier is off, the switch on sequence is sent first;
- for Room and General controls, only the volume is adjusted.
3) With an extended pressure of key 2, the volume is adjusted (VOL-). A quick pressure
sends the OFF control to the amplifier.
4) When key 3 is pressed the source is changed.
5) Key 4 is the control for the active source.
M=0 – 9 indicates the source to be activated before switching the amplifier on. If M=0,
source 1 is switched on without first switching OFF the sources (follow-me mode).
The possible A and PL configurations are the following:
- Audio point: A=0 – 9 is the amplifier room, PL=0 – 9 is the amplifier audio point.
- Room: A=AMB, PL= 0 – 9 is the room that the control is targeted at.
- General: A=GEN, PL= 0.
LG00129-a-UK