Lumel NS5 User manual

SERVICE MANUAL
SYNCHRONIZING METER
NS5

NS5-09B User's manual 2
Contents
1APPLICATION ............................................................................................................................. 3
2METER SET................................................................................................................................. 3
3BASIC REQUIREMENTS, OPERATIONAL SAFETY .................................................................. 4
4INSTALLATION............................................................................................................................ 4
5DESCRIPTION OF THE INSTRUMENT ...................................................................................... 5
5.1 Voltage inputs ..................................................................................................................... 5
5.2 External connections diagram............................................................................................. 6
6NS5 PROGRAMMING ................................................................................................................. 7
6.1 General description............................................................................................................. 7
6.2 Starting operation.............................................................................................................. 10
6.3 Language selection........................................................................................................... 11
7CONFIGURATION OF THE METER ......................................................................................... 11
PARAMETERS.................................................................................................................................. 11
7.1 Measurement .................................................................................................................... 13
7.2 Parameters ....................................................................................................................... 13
7.3 Relays ............................................................................................................................... 15
7.4 Ethernet ........................................................................................................................... 17
7.5 Modbus ............................................................................................................................. 18
7.6 Settings ............................................................................................................................. 19
7.7 Information ........................................................................................................................ 19
8SERIAL INTERFACES............................................................................................................... 20
8.1 RS485 INTERFACE – the list of parameters .................................................................... 20
8.2 Examples of registers reading and saving ........................................................................ 20
8.3 Ethernet 10/100-BASE-T .................................................................................................. 23
8.3.1 Connection of 10/100 BASE-T interface.................................................................... 24
8.3.2 Web Server................................................................................................................ 25
8.3.3 Modbus TCP/IP ......................................................................................................... 27
9MAP OF REGISTERS OF NS5 METER .................................................................................... 27
10 FIRMWARE UPGRADE............................................................................................................. 32
11 ERROR CODES ........................................................................................................................ 33
12 TECHNICAL DATA .................................................................................................................... 33
13 ORDERING CODES .................................................................................................................. 36

NS5-09B User's manual 3
1 APPLICATION
The NS5 digital synchronizing unit has been designed for the synchronization of
generators switched for parallel operation with the grid or with other generators with rated
frequency of 50 or 60 Hz. Frequency differences, voltage values, and phase shifts are shown
on a 3.5“ color TFT display screen with a resolution of 320 x 240 pixels.
Bar graphs with zero in the middle marked f and δU indicate respectively the difference in
frequency and the difference in voltage values of the generator and network signals. Phase
shift φof the generator and network voltage signals is indicated by a circular
synchronoscope. The spin speed corresponds to the difference between the network and the
generator frequency.
The synchronization point, i.e. the moment when the frequency, voltage and phase values of
the generator and the network are equal, is indicated by green indicators on the bar graphs
and inside the circle. With proper control of the BLK and START signals (detailed in p.7.3),
the SYNC synchronization relay will be activated.
The values of the measured quantities and deviations can be transferred to the master
system via RS485 interface or Ethernet.
The synchronizing unit has a galvanic separation between the individual blocks of:
- power supply,
- voltage inputs,
- Input control signals,
- RS485 Interface,
- Ethernet Interface:
- relay outputs
2 METER SET
Complete set of the Analyzer includes:
1. NS5 synchronizing unit 1 pc.
2. gasket 1 pc.
3. mounting brackets to fix the device in the panel 4 pcs.
4. connector with 16 screw terminals 1 pc.
5. connector with 14 screw terminals 1 pc.

NS5-09B User's manual 4
Fig.1, Meter set
3 BASIC REQUIREMENTS, OPERATIONAL SAFETY
In terms of operational safety the synchronizing unit meets the requirements of DIN EN
61010-1.
Safety instructions:
●The meter installation and connection should be made by qualified personnel.
All available protection requirements must be taken into consideration.
●Prior to turning the meter on verify the connections.
●Prior to removing the meter housing, always turn the supply off and disconnect the
measurement circuits.
●Removal of the meter housing during the warranty period voids the warranty.
●The synchronizing unit meets the requirements for electromagnetic compatibility in
industrial environment.
●A switch or a circuit-breaker should be installed inside the building or facility. It should
be located near the device, easily accessible to the operator, and suitably marked.
4 INSTALLATION
The synchronizing unit is adapted to be fixed to the panel by means of mounting brackets,
according to fig. 1. The housing is made of self-extinguishing plastic.

NS5-09B User's manual 5
Fig.2. Meter fixing
Housing dimensions 96 x 96 x 77 mm, mounting hole dimensions 92.5 x 92.5 mm. Outside the
meter there are screw terminals that allow connection of external wires with a cross-section up
to 2.5 mm2.
Fig.3. Overall dimensions of NS5 meter
5 DESCRIPTION OF THE INSTRUMENT
5.1 Voltage inputs
Voltage inputs are galvanically isolated (internal transformers). Un voltages (phase or phase-
to-phase) are automatically recalculated by the input value of the external voltage transformer
ratio. The voltage inputs specified in the order as 50...150 V or 150...400 V are programmable
in the selected range. Maximum operating voltage relative to earth is 300 V.

NS5-09B User's manual 6
5.2 External connections diagram
External connections are shown in Figures 4a, 4b.
Fig. 4a. Connections of the synchronizing unit - phase measurement voltages
Ethernet
(Option)

NS5-09B User's manual 7
Fig. 4b Connections of the synchronizing unit - phase-to-phase measurement voltages
6 NS5 PROGRAMMING
6.1 General description
Fig.5 Front panel
Ethernet
(Option)

NS5-09B User's manual 8
NS5 synchronizing unit has 6 buttons and a graphical color display.
Description of the front panel:
V, Hz, °,% units of displayed quantities
K kilo = 103,
US, fS,
UG, fG
δf, δU, ϕ
Indications of displayed parameters
Input measuring signals:
US- network voltage, fS– network frequency,
UG- generator voltage, fG– generator frequency,
Input control signals:
BLK - synchronization lock (SYNC relay will not be activated even if the other synchronization
conditions are met)
START - start of synchronization - unlocking the SYNC relay. After the START signal, the
meter expects that measured values of the voltage δU and frequency δf difference and the
phase shift φof the voltage signals from the generator and the network will be within the set
admissible values, then it generates a pulse that activates the SYNC relay with the set lead in
time.
Output signals (relay contacts):
- AL - fault relay is activated in case of faulty external circuit connection when a fault occurs
and if the measured values are outside the measuring range,
- SYNC - synchronization relay,
Calculated values:
δf, δU- difference in frequency and difference of voltage values of the generator and
network signals,
ϕ- phase shift of the generator and network voltage signals,
The SYNC synchronization relay will be energized after synchronization conditions have been
met.
Synchronization conditions:
-δU≤δU ≤+δU
-δf≤δf ≤+δf
IϕI≤Δϕ
BLK = "0"; START = "1" ( detailed description in p. 7.3 Relays )
where:
-δU - lower limit of voltage difference during synchronization,
+δU - upper limit of voltage difference during synchronization,
-δf - acceptable frequency difference when connecting "from below",
+δf - acceptable frequency difference when connecting "from above”,
ϕ−phase shift,
Δϕ −acceptable phase shift,
The difference in the values of the voltage and frequency of the generator UG,fGand network
US,fS is calculated according to the formulas:

NS5-09B User's manual 9
δU = 100 (UG-US)/US[%]
δf = 100 (fG-fS)/fS[%]
The phase shift of the generator voltage UGrelative to the network voltage USis expressed in
degrees:
ϕ= (UG,US)[ ° ]
Fixed phase shift compensation: positive value means that the generator voltage UG is ahead
of the network voltage US.
Fig.6, Synchronoscope with phase shift visualization
The spin speed and direction correspond to the difference between the network and the
generator frequency.
Fig.7. Screen when synchronization conditions are met
The values of measured parameters are presented on the next pages selected by pressing
the following buttons: (next page ) or (previous page).
Meter buttons can perform various functions depending on the operating location. Functions
are described on the bar at the bottom of the screen. If no description is present, it means that
the button is inactive at that moment.

NS5-09B User's manual 10
Fig.8, Sample designation of buttons
The top of the screen shows the status of the relay outputs (SYNC, AL ),the status of
control input signals START, BLK, the Ethernet connection symbol , indicators of
receipt and transmit of the date at RS485 ( RX, TX )
Fig.9, Visualization of measurements (synchronoscope, bar graphs)*
*The phase shift range on the synchronoscope screen: 0..360o,
the phase shift range on the bar graphs screen: -180..+180o
6.2 Starting operation
When power is turned on, the synchronizing unit displays the logo, NS5 meter name, version,
current firmware version and MAC for versions with Ethernet, and then switches to
measurement mode. Displayed information:
NS5 v:1.00– type of the synchronizing unit, program version number
Bootloader v.01.05 bootloader version number
U: 50...150 V – voltage version
MAC: AA:BB:CC:DD:EE:FF (versions with Ethernet)
Function of
button 1
Function of
button 2
Function of
button 3
Function of
button 4
Function of
button 5
Function of
button 6

NS5-09B User's manual 11
6.3 Language selection
The preset language is English. To select a different language, press and hold the Menu
button for about 10 seconds. The language selection menu will then appear. The language
selection is made by buttons or and then confirmed again by pressing the OK
button.
7CONFIGURATION OF THE METER
PARAMETERS
During normal operation (Measurement) the unit displays and signals the values that
characterize the state and the course of the generator synchronization process. The NS5
meter performs voltage measurement functions (voltage difference), frequency (frequency
difference), and phase shift between the voltage signals of the network and the generator.
The meter menu is divided into the following groups:
Parameters – configuration of parameters of the meter,
Relays – configuration of SYNC and AL relays,
Ethernet – configuration of Ethernet interface parameters,
Modbus – configuration of RS485 interface parameters,
Settings - settings: password, language, brightness level,
Information – preview of program version, serial no., MAC address,
To enter the parameter menu, press the button for about 3 seconds.
Use the buttons to select the desired group and accept with the button
Return to normal operation by pressing the button
Parameters
Primary
voltage of
transformer
0000100
Secondary
voltage of
transformer
00100.0
Compensation
of fixed phase
shift
±000,0
Default
settings of
parameters
: No
*Yes
Fig. 10a. Programming matrix
Relays
SYNC
Low value of
voltage
difference
–δU [%]
000.0
High value
of voltage
difference
δU [%]
000.0
Acceptable
freq.
difference at
down
–δ[f]
000.00
Acceptable
freq.
difference at
up
δ[f]
000.00
Down switching
acceptable ZL-
: Yes
* No
Up switching
acceptable
ZL+
: Yes
* No
Exit
Select
Menu

NS5-09B User's manual 12
Acceptable
phase shift
∆ϕ [°]
000.0
Relay lead
time
tbSYNC
[ms]
000
Pulse mode
: permanent
switching
* switching
pulse
Width of the
switching
pulse [ms]
000
Input signals
BLK,START
: Active
* Inactive
Set defaults
: No
*Ye s
AL
Relative
voltage
difference
δU [%] ≥
000.0
Relative
frequency
difference
δf [%] ≥
000.0
Phase shift
∆ϕ [°] ≥
000.0
Set defaults
: No
*Ye s
Fig. 10b. Programming matrix
Ethernet
Addresse
s
DHCP
* Deact.
: Act.
Mode
* Auto
: 10Mb/s
* 100Mb/s
IP Address
00.000.000.000
Subnet Mask
255.255.255.000
Gateway
Address
000.000.000.000
DNS Address
008.008.008.008
MAC Address
aa.bb.cc.00:21:01
Acquired from DHCP or entered manually when DHCP is
deactivated.
Modbus
TCP
Address
001
Port
00502
Max.
connection
limit
1
Waiting time
[s]
001
WWW
Port
00080
Fig. 10c. Programming matrix
Modbus
Address
001
Baudrate
* 4800b/s
: 9600 b/s
* 19,2 kb/s
* 38,4 kb/s
* 57,6 kb/s
* 115,2 kb/s
Mode
: RTU 8N2
* RTU 8E1
* RTU 8O1
* RTU 8N1
Settings Password
****
Language
* English
: Polski
* Deutsch
Back light level
* Minimum
*Medium
: Maximum
Set defaults
meter params
: No
*Ye s
Information Type
NS5
Order code
12200
Boot Version
1.04
Program
Version
1.00
Serial
Number
15070006
MAC Address
aa.bb.cc.00:21:
01
Fig. 10d. Programming matrix

NS5-09B User's manual 13
7.1 Measurement
Measurement – normal meter operation. Values of quantities characterizing the state and
the course of the synchronization process of the generator are displayed and signaled. The
NS5 meter performs voltage measurement functions (voltage difference), frequency
(frequency difference), and phase shift between the voltage signals of the network and the
generator.
You can change the page by pressing the button or .
Maximum and minimum values are displayed on a separate page. Deleting maximum or
minimum values is done by pressing the button
7.2 Parameters
In this group the parameters of the meter are set. To enter the Parameters group
press the button for about 3 seconds and then using the button or
select Parameters and confirm with the button .
Fig. 11. Screens for entering a password
Access to configuration of parameters is protected by a password, if it has been
introduced and is different from zero. When the password is 0000, the password prompt
is bypassed. If the password is incorrect, the message "Invalid password. Read-only
menu.” is displayed. Then you can view the parameters, but the changes are blocked.
When the password is valid or not entered, we can set values according to Table 1.
Select
Menu
Del

NS5-09B User's manual 14
Fig.12, Screens of Parameter group
Using the buttons we select a parameter and confirm it using the button .
Then using the buttons you can select the parameter characteristics or set the
desired parameter values, i.e. the decimal digit position can selected with the button or
, the value of the digit with the button or . The active position is indicated by the
cursor. The selected characteristic or value of the parameter should be confirmed by pressing
the button or canceled by pressing the button . To exit the Parameter
procedure press the button or wait for about 120 seconds. To exit the Menu of the
parameter selection press the button or wait for about 120 seconds.
Exit
Esc
Cancel
OK
Select
◄▼▲► - values setting
OK - approval
Cancel - decline
Menu button
min 3 sec.
Measurement
Button
Select Buttons
and
Select

NS5-09B User's manual 15
Table 1
No. Parameter name Characteristic /
value Description Default
value
1 Primary voltage of transformer 1 .. 1245183 V 100
2 Secondary voltage of transformer 0.1 .. 1000.0 100.0
3 Compensation of fixed phase shift
−90.0° .. +90.0° 0.0°
4 Default settings of parameters No, Yes No
When a parameter changes, it is checked whether the value is within the range. In case of
setting the value out of range, the value is set to the maximum value (when the value is too
high) or to the minimum value (when the value is too low).
To configure NS5 synchronizing unit you can also use the free eCon software
available at manufacturer’s website.
7.3 Relays
Select Relays in the options and confirm by pressing the button .
Fig.13.Screens of Relays group
Table 2
No. Parameter name range Notes / description Default
value
1
SYNC relay
Low value of voltage difference -δU -20.0 .. 0 [%]
δU = 100 (UG-US)/US[%]
-0.5
2 High value of voltage difference δU 0 .. 20.0[%] 0.5
3 Acceptable freq. difference at down -
δf
-3.00 .. -0.00 [%]
δf = 100 (fG-fS)/fS[%]
-0.05
4 Acceptable freq. difference at up δf 0.00 .. 3.00 [%] 0.05
Select
Button
Select Buttons
and
Select
Buttons
and
Select

NS5-09B User's manual 16
5 Down switching acceptable ZL- Yes
No
Yes
6 Up switching acceptable ZL+ Yes
No
Yes
7 Acceptable phase shift Δϕ 0.0..20.0 [°] 2
8 Relay lead/ delay time tbSYNC [ms] -999..999 [ms] tbSYNC
For positive values, the
function acts as a relay
switching lead.
For negative values, the
function acts as a relay
switching delay.
0
9 Pulse mode No
Yes
permanent switching
switching pulse
No
10 Width of the switching pulse [ms] 0..999 [ms] 0
11 Input signals BLK,START Active
Inactive
Graphic illustration of BLK
and START input signals
control with SYNC
synchronization relay in
Fig.14
Active
12 Set defaults Yes
No
No
13
14
AL relay
Relative voltage difference
δU ≥
20..100.0 [%] δU = 100 I(UG-US)/USI[%] 20
15 Relative frequency difference δf≥10..100.0 [%] δf = 100 I(fG-fS)/fSI[%] 10
16 Phase shift Δϕ ≥20.0 .. 360.0 [°] 20
17 Set defaults No
yes
No

NS5-09B User's manual 17
a,b) SYNC relay energized after synchronization conditions are met
c) SYNC relay not energized despite meeting
synchronization conditions (START signal
blocked by BLK signal)
d) SYNC relay not energized despite meeting
synchronization conditions (BLK signal did not
change its status from "1" to "0")
Fig.14, Graphic illustration of BLK and START input signals control with SYNC
synchronization relay
7.4 Ethernet
Select Ethernet group in the options and confirm selection using the button .
Fig.15, Ethernet mode screen
Select
signal status signal status
signal status signal status

NS5-09B User's manual 18
Table 3
No. Parameter name range Notes / description Default
value
1
Address
es
DHCP Deact./Act. Enabling/disabling DHCP
client (the service of
automatic acquiring the
parameters of Ethernet
interface IP protocol of the
meter from external DHCP
servers located within the
same LAN network).
Deact.
2 Mode Auto, 10Mb/s, 100Mb/s Auto
3 IP Address 0.0.0.0...255.255.255.255 10.0.1.161 Acquired from
DHCP or
entered
manually when
DHCP is
deactivated.
-
4 Subnet Mask 0.0.0.0...255.255.255.255 255.0.0.1 -
5 Gateway Address 0.0.0.0...255.255.255.255 0.0.0.0 -
6 DNS Address 0.0.0.0...255.255.255.255 10.0.0.44 -
7 MAC Address Aa:bb:cc:00:21:01 -
8
Modbus
TCP
Address 1 ... 247 1
9 Port 80 … 32000 1
10 Max. connection limit 1 … 4 1
11 Waiting time 10 .. 360 60s
12 WWW Port 80 ... 32000 80
7.5 Modbus
Select Modbus group in the options and confirm by pressing the button .
Fig.16. Screens of Modbus group
Table 4
No. Parameter name Characteristic / value Description Default value
1 Address 1…247 Address on the Modbus
network.
1
2 Baudrate 4800 b/s, 9600 b/s, 19,2 kb/s,
38,4 kb/s, 57,6 kb/s, 115,2
kb/s
Baud rate 9600 b/s
3 Mode RTU 8N2, RTU 8E1, RTU
8O1, RTU 8N1
Transmission mode RTU 8N2
Select

NS5-09B User's manual 19
7.6 Settings
Select Settings group in the options and confirm by pressing the button .
Table 5
No. Parameter name Characteristic /
value Description Default
value
1 Password 0 ... 9999 0 – off 0
2 Language English, Polish, Deutsch English
3 Backlight level Minimum, Medium,
Maximum
Maximum
4 Set defaults meter params. No, Yes No
Fig.17, Screens of Settings group
7.7 Information
Select Information group in the options and confirm by pressing the button .
Fig.18. Screen of Information group
Table 6
No. Parameter name Characteristic /
value Description Default value
1 Type Type of synchronizing unit NS5
2 Order code First 5 digits of ordering code e.g.12200
3 Boot Version Loader version e.g.1.04
4 Program Version Version of the meter main program e.g.0.60
5 Serial Number ddmmxxxx Current serial number of the meter np.16070006
Select
Select

NS5-09B User's manual 20
day month current number
6 MAC Address xx:xx:xx:xx:xx:xx 48-bit hardware address of the
Ethernet interface written in
hexadecimal
e.g.64:0E:0D:0C:
0B:0A
8SERIAL INTERFACES
8.1 RS485 INTERFACE – the list of parameters
The implemented protocol is in accordance with the standard PI-MBUS-300 Rev G of Modicon
Company. The list of serial link parameters of NS5 meter:
●ID 0xDF
●meter address 1..247,
●baud rate 4.8, 9.6, 19.2, 38.4, 57.6, 115.2 kb/s,
●operation mode Modbus RTU,
●information unit 8N2, 8E1, 8O1, 8N1,
●maximum time to commence the response 600 ms,
●maximum number of read registers in one query
- 61 registers – 4 byte,
- 122 registers – 2 byte,
●implemented functions - 03, 04, 06, 16, 17,
- 03, 04 registers reading,
- 06 one register record
- 16 n - registers record,
- 17 device identification
Default settings: address 1, baud rate 9.6 kbit/s, RTU 8N2 mode,
8.2 Examples of registers reading and saving
Readout of n-registers (code 03h)
Example 1 . Readout of 2 16-bit registers of integer type, starting with the register addressed
0FA0h (4000) - registers values 10, 100.
Request:
A
ddress of the
device
Function
Address of the register Number of registers Checksum
CRC
B1 B0 B1 B0
01 03 0F A0 00 02 C7 3D
Response:
Address of
the device
Function
Number of
bytes
Value from the register
0FA0 (4000)
Value from register
0FA1 (4001)
Checksum
CRC
B1 B0 B1 B0
01 03 04 00 0A 00 64 E4 6F
Table of contents
Other Lumel Measuring Instrument manuals