EnglishDeutsch
 logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. M-system
  6. •
  7. Transmitter
  8. •
  9. M-system M6SVF User manual

M-system M6SVF User manual

Other M-system Transmitter manuals

M-system M2XPA2 User manual

M-system

M-system M2XPA2 User manual

M-system Mini-M M2RS User manual

M-system

M-system Mini-M M2RS User manual

M-system Mini-M M2VS User manual

M-system

M-system Mini-M M2VS User manual

M-system WRS2 User manual

M-system

M-system WRS2 User manual

M-system F2SP User manual

M-system

M-system F2SP User manual

M-system 10TG User manual

M-system

M-system 10TG User manual

M-system M5PT User manual

M-system

M-system M5PT User manual

M-system B5RS User manual

M-system

M-system B5RS User manual

M-system 10AC User manual

M-system

M-system 10AC User manual

M-system Mini-M M2XUM User manual

M-system

M-system Mini-M M2XUM User manual

M-system 35mm User manual

M-system

M-system 35mm User manual

M-system M5VF User manual

M-system

M-system M5VF User manual

M-system M3SXV User manual

M-system

M-system M3SXV User manual

M-system M5CT-5AM User manual

M-system

M-system M5CT-5AM User manual

M-system Mini-M M2TT User manual

M-system

M-system Mini-M M2TT User manual

M-system 18KJV User manual

M-system

M-system 18KJV User manual

M-system W5-UNIT User manual

M-system

M-system W5-UNIT User manual

M-system B5MS User manual

M-system

M-system B5MS User manual

M-system VOS2T-R User manual

M-system

M-system VOS2T-R User manual

M-system Mini-M M2UDS2 User manual

M-system

M-system Mini-M M2UDS2 User manual

M-system 10SP User manual

M-system

M-system 10SP User manual

M-system W5LCS User manual

M-system

M-system W5LCS User manual

M-system W2RS User manual

M-system

M-system W2RS User manual

M-system W2CFG User manual

M-system

M-system W2CFG User manual

Popular Transmitter manuals by other brands

NIVELCO EasyTREK SCA-300 Series Programming manual

NIVELCO

NIVELCO EasyTREK SCA-300 Series Programming manual

Honeywell 5816WMBR installation instructions

Honeywell

Honeywell 5816WMBR installation instructions

Kamstrup READy MTU Installation and operation guide

Kamstrup

Kamstrup READy MTU Installation and operation guide

Omega ZW Series user guide

Omega

Omega ZW Series user guide

ABB Field 264H Instructions for installation

ABB

ABB Field 264H Instructions for installation

Alinco DJ-V17T Service manual

Alinco

Alinco DJ-V17T Service manual

Dejero EnGo 3x manual

Dejero

Dejero EnGo 3x manual

Rosemount 4600 Reference manual

Rosemount

Rosemount 4600 Reference manual

Speaka Professional 2342740 operating instructions

Speaka Professional

Speaka Professional 2342740 operating instructions

trubomat GAB 1000 instruction manual

trubomat

trubomat GAB 1000 instruction manual

Teledyne Analytical Instruments LXT-380 instructions

Teledyne Analytical Instruments

Teledyne Analytical Instruments LXT-380 instructions

Rondish UT-11 quick start guide

Rondish

Rondish UT-11 quick start guide

MG 10JRE instruction manual

MG

MG 10JRE instruction manual

Burkert 8177 operating instructions

Burkert

Burkert 8177 operating instructions

Firetide HotPort 3203 Hardware installation guide

Firetide

Firetide HotPort 3203 Hardware installation guide

Tele Radio T9-02 User instructions

Tele Radio

Tele Radio T9-02 User instructions

Rotronic HygroFlex HF3 Series user guide

Rotronic

Rotronic HygroFlex HF3 Series user guide

Jamara FCX6 Pro Tel Instruction

Jamara

Jamara FCX6 Pro Tel Instruction

https://manuals.online logo
https://manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2026 Manuals.Online. All Rights Reserved.

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-7994 Rev.3 P. 1 / 4
INSTRUCTION MANUAL
SIGNAL TRANSMITTER
(high-accuracy, ultra-high speed response 30 µsec.) MODEL M6SVF
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Signal conditioner ...............................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
•The equipment must be mounted inside a panel.
•Cover the cables (power supply, input and output) using
Shield tubes in order to prevent external noise inter-
ference. (M-System recommends Nitto Electric Works
Co.,Ltd “MTF - ES Series” products or equivalent.)
•The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
•Install lighting surge protectors for those wires connected
to remote location.
■POWER INPUT RATING & OPERATIONAL RANGE
•Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 0.6W
■GENERAL PRECAUTIONS
•Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ENVIRONMENT
•Indoor use.
•When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
•Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
•Environmental temperature must be within -20 to +55°C
(-4 to +131°F) with relative humidity within 30 to 90%
RH in order to ensure adequate life span and operation.
■WIRING
•Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
•Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
•The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
Body
Front Cover
DIN Rail Adaptor
Specifications
■FRONT VIEW (with the cover open)
Zero Adj.
Power LED
Span Adj.
M6SVF
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-7994 Rev.3 P. 2 / 4
INSTALLATION
Set the unit so that its DIN rail adapter is at the bottom. When the unit is installed to an Installation Base (model M6SBS),
refer to its instruction manual.
■MOUNTING THE UNIT ON A DIN RAIL
A)Hang the upper hook at the rear side of unit on the DIN
rail.
B)Push in the lower in keeping pressing the unit to the DIN
rail.
ADIN Rail
B
■REMOVING THE UNIT
A)Pull down the DIN rail adaptor using a minus screwdriv-
er.
B)Pull out the lower part of the unit.
C)Remove the upper part from the DIN rail.
A
DIN Rail Adaptor
CB
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
■EXTERNAL DIMENSIONS unit: mm (inch)
94 (3.70)
5.9 (.23)
DIN RAIL
35mm wide
DIN RAIL HOOK
*Use a minus screwdriver: tip width 3.8 mm max., tip thickness 0.5 to 0.6 mm
102 (4.02)
[0.5 (.02)]
SCREWDRIVER
INSERTION ANGLE
: approx. 40°
WIRE INSERTION ANGLE
: approx.35°
TEST PROBE
max. 2 (.08) dia.
SCREWDRIVER
*
INSERTION ANGLE
: approx. 35°
5678
1234
• When mounting, no extra space is needed between units.
M6SVF
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-7994 Rev.3 P. 3 / 4
■CONNECTION DIAGRAM
The M6SVF, by its fast-response feature,
is not designed to eliminate noise present
in the input signal.
Use a shielded twisted-pair cable to prevent
noise from entering through the input wiring.
+
–
OUTPUT
5
6
7
8
1
2
+
–
+
–
POWER
SIGNAL
SOURCE
CONNECTOR
POWER
■WIRING INSTRUCTIONS
 •Applicablewiresize
Solid: 0.2 to 2.5 mm2(0.55 to 1.75 dia.)
Stranded: 0.2 to 2.5 mm2(Tinning wire ends may
cause contact failure and therefore is not
recommended.)
Ferruled: 0.2 to 1.5 mm2(0.55 to 1.35 dia.)
 •Exposewireconductorsby8mm(0.31”).
Expose 8 mm
• How to Connect Wires
Screwdriver
Wire
1) Insert a minus screwdriver into the wire entry opening,
between the clamp and the housing, until its tip hits the
bottom where it is firmly held.
Tension Clamp
Screwdriver
2) Insert a wire. Push the screwdriver toward the direction
indicated with the arrow in the figure below to widen the
opening if necessary.
Wire Entry
Wire
3) Confirm that the wire tip hits the bottom and pull out the
screwdriver in holding it in position.
Confirm that the wire’s insulation tube is not caught in
the clamp.
M6SVF
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-7994 Rev.3 P. 4 / 4
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Confirm that the wire insulation tubes are not caught in
the clamp.
3) Power input voltage: Check voltage across the terminal
7–8withamultimeter.
4) Input: Check that the input signal is within 0 – 100% of
the full-scale.
5) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 50% input and adjust output to 50%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed perform fine adjustment
with ZERO as output: (0% – 100%) / 2.
5) SPAN: Apply 100% input and adjust output to 100%.
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.