4
2.Mechanical Specification and Input/Output Terminals
2.1 Mechanism of Supply/Charger unit
Figure 2-1
NOTE 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of am ient temperature.℃
2. Ripple & noise are measured at 20MHz of andwidth y using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. Under parallel
operation of more than one rack connecting together, ripple of the output voltage may e higher than the SPEC at light load condition. It will go ack to
normal ripple level once the output load is more than 5%.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Output of all the DRP-3200 modules are connected in parallel in the rack.
5. Derating may e needed under low input voltages. Please check the static characteristics for more details.
6. Because of component tolerance, there is a possi ility that some of units connected in parallel will reach an overcurrent limit then overloading the other
units when operating at full load condition. If overload conditions happen in parallel usage, it is suggested that derate the total output current y 10%.
7. The equivalent leakage current of the system is determined y the quantity of populated rectifiers.
8. The power supply is considered a component which will e installed into a final equipment. All the EMC tests are een executed y mounting the unit on
a mm* mm metal plate with mm of thickness. The final equipment must e re-confirmed that it still meets EMC directives.21000 1300 For guidance on how
to perform these EMC tests, please refer to EMI testing of component power supplies. (as availa le on http://www.meanwell.com)
9. The am ient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
DIMENSION
PACKING
OTHERS Rack 400*482.6*44(L*W*H, with mounting bracket) ; 365*440*44(L*W*H, without mounting bracket)
4.85Kg; 3pcs/17.4Kg/1.8CUFT
DHP-12K1U -24 DHP-12K1U -48
MODEL
NOTE 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of am ient temperature.℃
2. Derating may e needed under low input voltages. Please check the static characteristics for more details.
3. Output of all the DBR-3200 modules are connected in parallel in the rack.
4. The equivalent leakage current of the system is determined y the quantity of populated chargers.
5. The power supply is considered a component which will e installed into a final equipment. All the EMC tests are een executed y mounting the unit on
a mm* mm metal plate with mm of thickness. The final equipment must e re-confirmed that it still meets EMC directives.21000 1300 For guidance on how
to perform these EMC tests, please refer to EMI testing of component power supplies. (as availa le on http://www.meanwell.com)
6. The am ient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
DHB-12K1U -24 DHB-12K1U -48
MODEL
VOLTAGE RANGE Note.2
CHARGER
CURRENT RANGE
FREQUENCY RANGE
AC CURRENT (Typ.) per CHARGER
INPUT
OUTPUT
LEAKAGE CURRENT
per CHARGER
90 ~ 264VAC 127 ~ 370VDC
0 ~ 220A
DBR-3200-24 DBR-3200-48
47 ~ 63Hz
<1.5mA / 230VAC
17A/230VAC
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
DIMENSION
PACKING
OTHERS
-30 ~ +70 (Refer to "Derating Curve")℃
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing℃
±℃ ℃0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
Rack 400*482.6*44(L*W*H, with mounting bracket) ; 365*440*44(L*W*H, without mounting bracket)
ENVIRONMENT
5.5Kg; 3pcs/17.5Kg/2.11CUFT
ALARM SIGNAL
REMOTE ON-OFF CONTROL
The isolated TTL signal out, Please refer to Installation Manual
By electrical signal or dry contact ON: short OFF: open
FUNCTION
SAFETY &
EMC
(Note 5)
0 ~ 440A
OUTPUT VOLTAGE PROGRAMMABLE(PV)
OUTPUT CURRENT
PROGRAMMABLE(PC)
Adjustment of output voltage is allowable to 75 ~ 125% of nominal output voltage. Please refer to the Function Manual.
Adjustment of output current is allowable to 20 ~ 100% of rated current. Please refer to the Function Manual.
28.8V
27.6V
57.6V
55.2V
BOOST CHARGE VOLTAGE(Vboost)(default)
FLOAT CHARGE VOLTAGE(Vfloat)(default)
TEMPERATURE COMPENSATION
-3mV / / cell / (24V = 12 cells ; 48V = 24 cells)℃
SAFETY STANDARDS
WITHSTAND VOLTAGE
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:700VDC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH℃
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (E 50082-2), lev , criteria ANelHeavy industry
Compliance to EN55032 (CISPR32) Conduction Class B, Radiation Class A ; EN61000-3-2,-3
EMC IMMUNITY
EMC EMISSION
AUXILIARY POWER 5V @ 0.3A, tolerance 10%, ripple 150mVp-p, 12V @ 0.8A, tolerance 10%, ripple 450mVp-p±±
Note.4
SVR
10max.325
11max.
29.7
5.8 12.5
41
LED Status Indicator
47.3
18.6
53.5
107
62.4
3.6
Air flow
direction
CN1