
 6
 
TROUBLE SHOOTING GUIDE 
SYMPTOM POSSIBLE 
CAUSE WHAT TO 
CHECK REMEDY 
 
CAN'T START BREW CYCLE 
1. No water. 
 
 
2. No power. 
 
 
3. Warmer switch not on 
 
 
4. Brew start switch. 
 
 
5. Timer or timer harness. 
 
 
 
6. Solenoid valve. 
 
 
1. Incoming water lines & water shut 
 off valve. 
 
2. Fuse or circuit breaker. 
 Power cord and plug connections. 
 
3. Switch is on and lighted red, 
continuity 
 
4. Switch continuity. 
 (Normally closed.) 
 
5. Wire leads to solenoid and 
 white 3-pin connector. 
 
 
6. (A) Voltage at solenoid valve 
 terminals. Start a brew cycle and 
 check for 120 volts AC. 
 (B) If voltage is present at 
 terminals, check for water at line 
 pressure on the inlet side of 
 solenoid valve. 
 
 
1. Be sure water shut off is open. 
 
 
2. Replace or reset circuit protector 
 
 
3. If warmer switch does not make and 
 break contact, replace warmer switch. 
 
4. If brew start switch does not make and 
 break contact, replace brew start switch. 
 
5. Make sure these connections are tight. If 
 so, and all else checks out OK, replace 
 timer. 
 
6. (A) If voltage is not present at terminals, 
 refer to steps 2 through 5. 
 
 (B) If voltage is present at terminals and 
 water at line pressure is present on the 
 inlet side of the solenoid, but not present 
 on the outgoing side, replace solenoid. 
 
 
NO HOT WATER 
1. Tank heater. 
 
 
 
 
 
 
 
 
2. Hi-limit thermostat or main 
 thermostat. 
 
1. Check the voltage at the tank 
 heater terminals. Voltage should be 
 as indicated on the serial tag (on 
 rear of brewer.) 
 
 
 
 
 
 
2. Check the voltage between the 
VIOLET/RED wire on the tank 
element and the incoming terminal 
(VIOLET/BLACK) on tthe hi-limit 
thermostat, then the outgoing 
terminal (VIOLET/BLACK) on the 
hi-limit thermostat. 
 
1. (A) If correct voltage is present at the 
 tank heater terminals and water in tank is 
 not being heated, replace the tank heater. 
 (B) If voltage is not present at the tank 
 heater terminals refer, to step 2. 
 (C) If incorrect voltage is present at the 
 tank heater terminals, check voltage at 
 outlet. 
 
2. (A) If voltage is present on the incoming 
 terminal of the hi-limit thermostat, but 
 not on the outgoing terminal, replace the 
 hi-limit thermostat. 
 (B) Check voltage at the terminal blocks. 
If voltage is not present check outlet or 
circuit breaker. 
 (C) If voltage is not present on the 
 incoming terminal of the hi-limit 
 thermostat, replace the main thermostat. 
 
 
DRIPPING 
1. Not siphoning properly. 
 
 
 
2. Solenoid valve not seating 
 properly. 
 
 
 
 
 
1. Water should flow freely from the 
 sprayhead. 
 
 
2. Solenoid valve assembly. 
 
 
 
 
 
 
1. (A) Clean sprayhead holes. 
 (B) Check tightness of sprayhead tube. 
 (C) See "DELIMING" , Page 5. 
 
2. Be sure spring is in place and any 
 particles are cleaned from valve seat. If 
 valve seat is worn or mutilated, replace 
 solenoid valve. 
 
 
 
STEAMING OR SPITTING 
AROUND FUNNEL 
 
1. Main thermostat. 
 
 
 
2. High altitude. 
 
1. Thermostat points stuck or out of 
 calibration. 
 
 
2. Located above 5,000 feet. 
 
1. (A) Adjust thermostat. 
 (B) Thermostat should be calibrated or 
 replaced. 
 
2. See "INSTALLATION 
 INSTRUCTIONS", Page 4.. 
 
 
WATER KEEPS RUNNING 
1. Solenoid valve. 
 
2. Start switch. 
 
 
3. Timer 
 
 
1. Refer to "DRIPPING", Step 1. 
 
2. Remove wires from switch and 
 check continuity. 
 
3. Solid state timers are not 
 repairable. If timer will not shut 
 off, replace timer. 
 
 
1. Refer to "DRIPPING", Step 1. 
 
2. If start switch does not make and break 
 contact, switch should be replaced. 
 
3. Replace timer.