GENERAL
Before installing the detector, the user must read these instructions
carefully and store this manual for future reference. BSR-6060/A/MAR
is used on ships and is a thermal and rate of rise detector
simultaneously. It co-operates with
BSR-2104/MAR, BSR-2114/MAR panels.
The device transmits an analogue value to the panel which depends of
the area’s temperature and the rate of temperature rise. The analogue
o
value is 100 (temperature 56 C) and increases one unit per degree of
o
the temperature increase. If the temperature rises rapidly (over 5 C per
minute) then the analogue value that sends the detector to the panel is
128. The factory setting of the panel is to issue an alarm when the
analogue value is greater than 104. The panel issues an alarm if the
o
temperature rises rapidly or if the temperature exceeds the 60 C.The
o o
user can change this analogue value from 100(56 C) up to 120(76 C).
The detector have two parts, one plastic base which is installed on the
ceiling and the main unit of the detector which is fastened to the base by
a simple turning to the right. The detectors have an indication led which
lights continuously in case of fire detection until there is a reset signal
from the panel. When we silence the sirens the LED remains lit to show
us the detector that issued the alarm. The LED goes off when we
RESET the panel. The indication led also flashes every 8 sec to indicate
good operation.
ADDRESS SETTING
To set each detector’s address you have to use the device BSR-2143
photo.1. (refer to it’s instruction manual). After the address setting mark
this number to the sticker on the detector’s base (ADR:XXX). Each
detector must have an
address with which it is recognized from the panel.
It`s forbidden for two devices with same addresses to be connect to the
same loop.
OPERATION CHECK
It is advised to conduct a good operation test every 6 months and every
time the detector position is changed. It is essential to have good air
circulation inside the detector. Therefore care must be taken so that the
vents of the detector are not covered.
NOTE
The detectors must be placed in the ceiling on visible areas with no side
obstacles and away from sides with no air circulation or strong air
2
currents and vapors. Each detector covers almost 50 m and the
distance between two detectors must not exceed 15m.
2
The cables cross section must be from 0.5 to 1.5mm .
ATTENTION!!
After the device is installed, care must be taken, so that the detector
vents are not blocked by anything (i.e. dust, paint). Failing to do so will
prevent the smoke particles to enter the detection chamber.
After the installation, it is the sole responsibility of the user to
maintain the detector for good operation.
921606004_09_002
ADDRESSABLE RATE OF RISE HEAT DETECTOR
BSR-6060/A/MAR
Page 1 of 3
Thank you for your trust in our products
Olympia Electronics - European manufacturer
103 (diam.) x 48 (height) mm
Alarm LED
A2R
5 °C / min
IP22
EN 54-5, IEC 60092-504, IEC 60533
o
-10 to 60 C
Up to 95%
2 years
145gr.
TECHNICAL CHARACTERISTICS
IDLE STATE POWER CONSUMPTION
ALARM POWER CONSUMPTION
SENSITIVITY
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
DEGREES OF COVER PROTECTION
OPERATION VOLTAGE
RELATIVE HUMIDITY
TYPICAL WEIGHT
EXTERNAL DIMENSIONS
GUARANTEE
INDICATORS
CLASS
18-30V DC
1.5 mA (with indication LED activated)
1mA