S8JX
5
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not
start. Refer to Overload Protection on page 11.
*2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*3. Rated input voltage: 100 or 200 VAC at 100% load.
*4. Output characteristics: Specified at power supply output terminals.
*5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting
the output voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.
*6. For details, refer to Overload Protection on page 11.
*7. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*8. The weight indicated is for Front-mounting, Open-frame Power Supplies.
*9. The protection-ON alarm indicator will light as soon as the output is interrupted. For resetting, turn OFF the input power, leave for more than
three minutes , and then turn it back ON again.
Input specification 100/200 V (Selected)
Item Power ratings *1300 W 600 W
Efficiency 82% min. 80% min.
Input
Voltage *2
100 to 120 VAC (85 to 132 VAC)
200 to 240 VAC (170 to 264 VAC)
(Swichable)
Frequency *250/60 Hz (47 to 450 Hz)
Current *3100 V input 8 A max. 14 A max.
200 V input 4.5 A max. 8 A max.
Power factor ---
Harmonic current emissions ---
Leakage current *3100 V input 0.5 mA max.
200 V input 1 mA max.
Inrush current (for a
cold start at 25°C) *3
100 V input 25 A max. 30 A max.
200 V input 50 A max. 60 A max.
Noise filter Yes
Output *4
Voltage adjustment range *5−10% to 15% (with V. ADJ)
Ripple *32% (p-p) max.
Input variation influence 0.4% max.
Load variation influence 0.8% max. (0 to 100% load, rated input voltage)
Temperature variation influence 0.05%/°C max.
Startup time 650 ms max. 500 ms max.
Hold time *320 ms min.
Additional
functions
Overload protection *6105% of rated load current, voltage drop,
intermittent, automatic reset
105% of rated load current, Inverted L
voltage drop, the circuit will be shut OFF
when the overload exceeds 5 s. *9
Overvoltage protection *7Yes Yes *9
Overheat protection No Yes *9
Parallel operation Yes (up to 5 units)
Series operation Yes (For up to two Power Supplies; external diodes required.)
Protective circuit operation indicator No Yes (color: red)
Other
Ambient operating temperature
Refer to the derating curve in Engineering Data on page 9 (with no icing or condensation)
Storage temperature −25 to 65°C (with no icing or condensation)
Ambient operating humidity 25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 25 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 25 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 25 mA)
Insulation resistance 100 MΩmin. (between all outputs and all inputs/PE terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2h each in X, Y, and Z directions
Shock resistance 150m/s2, 3 times each in ±X, ±Y, ±Z directions
Output indicator Yes (Color: Green)
EMI Conducted Emissions *3Conforms to EN 55011 Group 1 Class A and based on FCC Class A
Radiated Emissions Conforms to EN 55011 Group 1 Class A
EMS
Electrostatic Discharge Confirms to EN61000-4-2
Radiated Electromagnetic Field Confirms to EN61000-4-3
Electrical Fast Transient/Burst Confirms to EN61000-4-4
Surge Confirms to EN61000-4-5
Conducted Disturbance Confirms to EN61000-4-6
Voltage Dips/Short Interruptions Confirms to EN61000-4-11
Approved standards
UL 508 (Recognition), UL 60950-1
cUL: CSA C22.2 No.107.1
cUR: CSA C22.2 No. 60950-1
EN/VDE: EN50178 (= VDE 0160), EN 60950-1 (= VDE 0805 Teil 1)
(Terminal block: Based on DIN50274 (VDE 0660-514))
SEMI SEMI F47-0200 (200-VAC input)
Weight *81,600 g max. 2,500 g max.