10
Send a message: H1 Info.
The controller sends a supply water info from the H1 heating
circuit to your mobile phone that shows current supply water
-
ter control.
-
ing the supply water control and the actuator control.
The message cannot be changed or sent back to the controller.
Key words:
H1 info:
--- H1 SUPPLY WATER-------------
According to curve 35.1 °C/
Away -control effect -6.0 °C/
Calculated supply water
setting = 29.1 °C.
--- MEASUREMENTS --------------
Supply water = 35.2 °C
Outdoor temp.= -10.7 °C
--- ACTUATOR CONTROL----------
Actuartor control = 20 %
H1 INFO
H2 INFO
temperature Explanation
----- ROOM TEMPERATURE --------------
Room temperature setting Room temperature setting set by the user.
Time program eect on room temp. Room temperature drop by weekly or exception schedule.
Away -control eect Home/Away mode for reduction of room temperature. The trigger can come
from the controller (see Inputs and outputs-> Home-Away-control), from the
Home/Away switch or be sent as a text message.
Force control eect Room temperature has been forced permanently to the desired reduction
in room temperature (see Control mode selection, p.13).
Eect of autumn drying
Calculated room temperature Current room temperature setting determined by the controller.
----- MEASUREMENTS -------------------
Supply water temperature Current measured supply water temperature.
Outdoor temp. Themeasured outdoor temperature. Outdoortemperature dataisdisplayedifthe
delayed outdoor temperatureisnotusedinsupplywatercontrol.
Delayed outdoor temperature If the heating mode is set to radiator heating, the delayed temperature
measurement can be used in supply water control. Typically 2 hours delay
time is used (time can be set in service menu). In supply water control the
controller uses delayed measurement as an outdoor temperature.
Anticipated outdoor temperature
measurement can be used in supply water control. Typically 2 hours antici-
pation time is used (time can be set in service menu). In supply water con-
trol the controller takes into account the outdoor temperature change rate.
Room temperature The measured room temperature or room temperature from the bus. The
measurement is not necessarily taken into use in all control processes.
Delayed room temperature
when calculating the room compensation demand (the delay time of room
temperature measurement is adjustable, default 0.5 hours).
Return water temperature Presents measured return water temperature.
----- ACTUATOR CONTROL ---------------
Actuator control Current actuator control.
Actuator control 1 (2)
the valve and the controller will then start up actuator 2.
Actuators control 50%means thatthevalve1istotallyopenandthevalve2istotallyclosed. 100%
means that both valves are open.
----- PUMPS-------------------
P2.1 (3.1) Pump The state of the pump.
P2.2 (3.2) Pump The state of the reserve pump/alternative pump.
P2.1 (3.1) Pump control Control of the pump.
P2.2 (3.2) Pump control Control of the reserve pump/alternative pump.
P2.1 (3.1) Run time Running time for pump from the counter.
P2.2 (3.2) Run time Running time for reserve/ alternative pump from the counter.
Pump in progress Indicates which of the pumps is running in P2.1 or P2.2 (H1)/ P3.1 or P3.2 (H2
circuit).