10
ALARMS, INDICATIONS AND PULSE MEASUREMENTS
UI 15
UI 16
DI 1
DI 2
Alarm/
Indication 15
Alarm/
Indication 16
Digital input 17
Digital input 18
P2 Indication →
Name: P2 Pump
P2 Alarm →
Alarm priority ___ (1 = Emergency)
P3 Indication →
Name: P3 Pump
P3 Alarm →
Alarm priority ___ (1 = Emergency)
P1 Alarm→
Name: Pump 1 alarm
General alarm →
General alarm status
Alarm priority ___ (1 = Emergency)
Water flow measurement
Energy measurement
Water flow measurement
Energy measurement
Pulse input scaling:
Counter initial value
Name of meas.:
Pulse input scaling:
Counter initial va-
lueName of meas.:
_____ 10 l/pulse (1...100l/pulse)
______0.0 m3
DI1(2) Water flow measurement
_____ 10 kWh/pulse
(1...100 kWh/pulse)
______0.0 MWh
DI1(2) Energy measurement
Normally open
Normally closed
Normally open
Normally closed
Normally open
Normally closed
Water flow measurement
Pulse measurement settings:
Energy measurement
UI14 Measurement 14 General compensation, 0-10 V
General compensation, 0-20 mA
Home/ Away switch
Pump indication can be selected when
pump control is also connected. The regu-
lator emits a conflict alarm if the regulator
switches the pump on but it does not activa-
te. The alarm has a 5 s delay.
Pump alarm: Pump indication data is supp-
lied by the frequency converter unit. The re-
gulator emits a pump alarm when a conflict
state occurs.
When the counter initial value is set, go to
the line “Save initial value into the coun-
ter” and click “OK”.
Type of digital input:
Type of digital input:
Type of digital input:
Name________________
Name_________________
Name________________
Nimi_________________
General compensation: In circuit-specific
value settings you can specify the measu-
rement message range in which compen-
sation is used, as well as the maximum cor-
rection to supply water temperature that
can be made using compensation. You can
assign names to general compensation (e.g.
solar compensation, wind compensation or
pressure compensation).
Home/ Away control:
The control will be taken separately into use
(see Service mode→ Temperature drops). You
can also do Home/Away control in “Measurements”-
menu or by SMS message (”Home”/”Away”), if a
GSM-modem is connected to the controller.
UI 13
UI12
Measurement 13
Measurement 12
General meas. NTC10
Pressure switch
Pressure transmitter V
Pressure transmitter mA
General meas. NTC10
Pressure switch
Pressure transmitter V
Pressure transmitter mA
Pressure transmitter measurement:
Pressure measurement: Automatic/Manual
Measuring area ___(7.0 bar, setting range 0.0...25.0)
Name of meas.: (Pressure measurement 2) , other,
_________________________________,
Measurement adjustment:___0.00V, (-5.00...5.00)
Pressure measurement settings:
Pressure 2 min limit _____ (0.5 bar (0.0...20.0)
Pressure 2 max limit _____ (15.0 bar (0.0...20.0)
Pressure transmitter measurement:
Pressure measurement: Automatic/Manual
Measuring area ___(16.0 bar, setting range 0.0...25.0)
Name of meas.: (Pressure measurement 1) , other,
_________________________________,
Measurement adjustment:___0.00V, (-5.00...5.00)
Pressure measurement settings:
Pressure 1 min limit _____ (0.5 bar (0.0...20.0)
Pressure 1 max limit _____ (15.0 bar (0.0...20.0)
Pressure switch:
Pressure switch:
Normally open
Normally closed
Normally open
Normally closed
Type of digital input:
Type of digital input:
→Name: Meas. UI13; other _______________________________________
→ Name: Meas. UI12; other ______________________________________
Note
Alternative selectionsName
Input