7
2 Inputs and outputs
You can see the inputs and outputs of S203 which are configured
in use. Configuration of the inputs and outputs is done in ser-
vice menu (see p. 36-39).General measurements are temperature
measurements witch can be used for serial dierent purposes. The
default names of the measurements can be changed according to
use case.
If the sensor is not connected or is defective, the measurement
value shown will be -50°C (cross sensor) or +130 °C (sensor circuit
shorted). If a measurement is in manual mode, a hand image is
shown in the beginning of the line.
Inputs and outputs
Inputs and outputs are shown by the regulator in circuit-specific
groups. First H1, then H2 and last DHW
Informational general measurements, which can be used for sev-
eral purposes. Measurements can be named in the service menu.
(Navigate: Service → Connections and configuration).
1
1
2
2
2
2
Main menu
Inputs and outputs
H1 Control circuit
H2 Control circuit
HW Domestic hot water control
>
>
>
>
Inputs and outputs
------ INPUTS AND OUTPUTS -----------------------
Outdoor temp. -18.2 °C
H1 Supply water 35.1 °C
H1 Return water 22.0 °C
H1 Room temperatur 21.5 °C
H1 Actuator control 22 %
H2 Supply water 28.1 °C
H2 Return water 21.1 °C
>
>
>
>
>
>
>
>
Measurement Range Measurement information
Home-Away-control Home/Away Home-Away mode. By pressing OK you can change the status of the Home/
Away mode. The mode can also be changed by Home/Away-switch or by
text message “Home” or “Away” when a GSM-modem (optional) is available.
--------INPUTS------------------
Outdoor temp. -50...+130 °C Measured current outdoor temperature.
Supply water -50...+130 °C Current temperature of the water entering the heating network.
Return water temperature -50...+130 °C Current temperature of the water returning form the heating network.
Room temperature -50...+130 °C Current room temperature.
DHW Supply water -50...+130 °C Current domestic hot water temperature.
DHW Circulation water temp. -50...+130 °C When there is no consumption, the measurement shows the temperature
of DHW return water. During consumption, the measurement will show the
mixed temperature of cold water and return water, in which case the meas-
urement is used in so-called anticipation to improve the regulation result.
DHW tank bottom
temperature
-50...+130 °C The HW tank bottom temperature data is used for hot water circulation
pump control.
DHW tank top temperature -50...+130 °C The hot circulation pump can be controlled by using both the bottom and
top temperature, or either separately.
H1(2) DH Return -50...+130 °C Temperature of return water after the district heat exchanger or other freely
named temperature measurement.
DH Supply water temp. -50...+130 °C Temperature of water coming from the district heating plant.
DH Return water temp. -50...+130 °C Temperature of water returning to the district heating plant.
M10 (M11) Switch alarm mode O/On Information of the alarm contact.
General compensation 0...100% General compensation input value.
Measurement M11 (12,13) -50...+130 °C Freely nameable general measurement.
Pressure switch mode O/ On When the pressure of the network lowers below the pressure alarm level,
the state of the switch is changed to on and an alarm is activated.
Pressure measurement 0.... 16 bar Pressure of the heating network.
P2 (3) Pump O/On The state of the pump.
Previous day’s average
outdoor temp.
The value is used to control the autumn dry function and as an alternative
to outdoor temperature measurement if the sensor malfunctions.
DI 1(2) Water volume The measured amount of water consumption (cumulative value).
DI 1(2) Energy measurement The measured amount of energy consumption (cumulative value).
Moisture sensor wet/dry Shows the state (wet/dry) of the moisture sensor.