Panasonic S-160PE1R5A Manual

R EFER EN C E N O . S M 830262-00
TECHNICALDATA& S ER V IC E M A N U A L
O utdoor U nitIndoor U nit
U - 160PE2R 8A, U - 180PE2R 8A, U - 200PE2R 8A, U - 224PE2R 8A
O rder N o. SB PAC1712007CE
S- 180PE3R 5, S- 200PE3R 5, S- 224PE3R 5
Typ e E3
S- 160PE1R 5A
Typ e E1
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 1 18/01/12 18:47:48

i
This air conditioner must be installed by the sales dealer
or installer.
This information is provided for use only by authorized
persons.
or safe installation and trouble-free operation you
must
● Carefully read this instruction booklet before beginning.
● Follow each installation or repair step exactly as shown.
● This air conditioner shall be installed in accordance with
ational Wiring Regulations.
● Pay close attention to all warning and caution notices
given in this manual.
WARNING
This symbol refers to a hazard or
unsafe practice which can result in
severe personal injury or death.
CAUTION
This symbol refers to a hazard or
unsafe practice which can result in
personal injury or product or property
damage.
If Necessary Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for
a special problem, contact our salesservice outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
SPCIAL PRCAUTINS
WARNING
WARNING When Wiring
WARNING
Risk of Electric Shock
LCTRICAL SHC CAN
CAUS SR PRSNAL
INUR R ATH. NL A
UALII PRINC
LCTRICIAN SHUL
ATTMPT T WIR THIS
SSTM.
• Do not supply power to the unit until
all wiring and tubing are completed or
reconnected and checked.
• Highly dangerous electrical voltages are
used in this system. Carefully refer to the
wiring diagram and these instructions
when wiring. Improper connections
and inadequate grounding can cause
accidental inury or death.
• Connect all wiring tightly. oose wiring
may cause overheating at connection
points and a possible fire hazard.
Provide a power outlet to be used
exclusively for each unit.
Provide a power outlet exclusively for
each unit, and full disconnection means
having a contact separation by mm
in all poles must be incorporated in the
fixed wiring in accordance with the wiring
rules.
To prevent possible hazards from
insulation failure, the unit must be
grounded.
This equipment is strongly recommended
to be installed with Earth eakage
Circuit Breaker (ECB) or Residual
Current Device (RCD). Otherwise, it may
cause electrical shock and fire in case
of equipment breakdown or insulation
breakdown.
When Transporting
• It may need two or more people to carry
out the installation work.
• Be careful when picking up and moving
the indoor and outdoor units. et a
partner to help, and bend your knees
when lifting to reduce strain on your
back. Sharp edges or thin aluminum
fins on the air conditioner can cut your
fingers.
When Installing…
Select an installation location which is
rigid and strong enough to support or hold
the unit, and select a location for easy
maintenance.
…In a Room
Properly insulate any tubing run inside a
room to prevent sweating that can cause
dripping and water damage to walls and
floors.
CAUTION
CAUTIN
Keep the fire alarm and
the air outlet at least
1.5 m away from the unit.
01_II_281317_EU_Eng_L.indb 2 2016-7-12 9:20:56
3
• Keep all tubing runs as short as
possible.
• Use the flare method for connecting
tubing.
• Apply refrigerant lubricant to the
matching surfaces of the flare and union
tubes before connecting them, then
tighten the nut with a torque wrench for
a leak-free connection.
• Check carefully for leaks before starting
the test run.
• Do not leak refrigerant while piping work
for an installation or re-installation, and
while repairing refrigeration parts.
Handle liquid refrigerant carefully as it
may cause frostbite.
When Servicing
• Turn the power OFF at the main
power box (mains), wait at least 10
minutes until it is discharged, then
open the unit to check or repair
electrical parts and wiring.
• Keep your fingers and clothing away
from any moving parts.
• Clean up the site after you finish,
remembering to check that no metal
scraps or bits of wiring have been left
inside the unit.
CAUTION
WARNING
• This product must not be
modified or disassembled under
any circumstances. Modified or
disassembled unit may cause fire,
electric shock or injury.
• Do not clean inside the indoor and
outdoor units by users. Engage
authorized dealer or specialist for
cleaning.
• In case of malfunction of this
appliance, do not repair by
yourself. Contact to the sales
dealer or service dealer for a
repair.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete
blocks to provide a solid, level foundation
for the outdoor unit. This prevents water
damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down
with bolts and a metal frame. Provide a
suitable air baffle.
…In a Snowy Area (for Heat Pump-
type Systems)
Install the outdoor unit on a raised
platform that is higher than drifting snow.
Provide snow vents.
…At least 2.5 m
Indoor unit of this air conditioner shall be
installed in a height of at least 2.5 m.
…In laundry rooms
Do not install in laundry rooms. Indoor
unit is not drip proof.
When Connecting Refrigerant
Tubing
Pay particular attention to refrigerant
leakages.
CAUTION
WARNING
• When performing piping work,
do not mix air except for
specified refrigerant (R410A)
in refrigeration cycle. It causes
capacity down, and risk of
explosion and injury due to high
tension inside the refrigerant
cycle.
• If the refrigerant comes in contact
with a flame, it produces a toxic
gas.
• Do not add or replace refrigerant
other than specified type. It may
cause product damage, burst and
injury, etc.
• Ventilate the room immediately, in the
event that is refrigerant gas leaks during
the installation. Be careful not to allow
contact of the refrigerant gas with a
flame as this will cause the generation
of toxic gas.
01_II_281317_EU_Eng_L.indb 3 2016-7-12 9:20:56
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 2 18/01/12 18:47:48

ii
This air conditioner must be installed by the sales dealer
or installer.
This information is provided for use only by authorized
persons.
or safe installation and trouble-free operation you
must
● Carefully read this instruction booklet before beginning.
● Follow each installation or repair step exactly as shown.
● This air conditioner shall be installed in accordance with
ational Wiring Regulations.
● Pay close attention to all warning and caution notices
given in this manual.
WARNING
This symbol refers to a hazard or
unsafe practice which can result in
severe personal injury or death.
CAUTION
This symbol refers to a hazard or
unsafe practice which can result in
personal injury or product or property
damage.
If Necessary Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for
a special problem, contact our salesservice outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
SPCIAL PRCAUTINS
WARNING
WARNING When Wiring
WARNING
Risk of Electric Shock
LCTRICAL SHC CAN
CAUS SR PRSNAL
INUR R ATH. NL A
UALII PRINC
LCTRICIAN SHUL
ATTMPT T WIR THIS
SSTM.
• Do not supply power to the unit until
all wiring and tubing are completed or
reconnected and checked.
• Highly dangerous electrical voltages are
used in this system. Carefully refer to the
wiring diagram and these instructions
when wiring. Improper connections
and inadequate grounding can cause
accidental inury or death.
• Connect all wiring tightly. oose wiring
may cause overheating at connection
points and a possible fire hazard.
Provide a power outlet to be used
exclusively for each unit.
Provide a power outlet exclusively for
each unit, and full disconnection means
having a contact separation by mm
in all poles must be incorporated in the
fixed wiring in accordance with the wiring
rules.
To prevent possible hazards from
insulation failure, the unit must be
grounded.
This equipment is strongly recommended
to be installed with Earth eakage
Circuit Breaker (ECB) or Residual
Current Device (RCD). Otherwise, it may
cause electrical shock and fire in case
of equipment breakdown or insulation
breakdown.
When Transporting
• It may need two or more people to carry
out the installation work.
• Be careful when picking up and moving
the indoor and outdoor units. et a
partner to help, and bend your knees
when lifting to reduce strain on your
back. Sharp edges or thin aluminum
fins on the air conditioner can cut your
fingers.
When Installing…
Select an installation location which is
rigid and strong enough to support or hold
the unit, and select a location for easy
maintenance.
…In a Room
Properly insulate any tubing run inside a
room to prevent sweating that can cause
dripping and water damage to walls and
floors.
CAUTION
CAUTIN
Keep the fire alarm and
the air outlet at least
1.5 m away from the unit.
01_II_281317_EU_Eng_L.indb 2 2016-7-12 9:20:56
3
• Keep all tubing runs as short as
possible.
• Use the flare method for connecting
tubing.
• Apply refrigerant lubricant to the
matching surfaces of the flare and union
tubes before connecting them, then
tighten the nut with a torque wrench for
a leak-free connection.
• Check carefully for leaks before starting
the test run.
• Do not leak refrigerant while piping work
for an installation or re-installation, and
while repairing refrigeration parts.
Handle liquid refrigerant carefully as it
may cause frostbite.
When Servicing
• Turn the power OFF at the main
power box (mains), wait at least 10
minutes until it is discharged, then
open the unit to check or repair
electrical parts and wiring.
• Keep your fingers and clothing away
from any moving parts.
• Clean up the site after you finish,
remembering to check that no metal
scraps or bits of wiring have been left
inside the unit.
CAUTION
WARNING
• This product must not be
modified or disassembled under
any circumstances. Modified or
disassembled unit may cause fire,
electric shock or injury.
• Do not clean inside the indoor and
outdoor units by users. Engage
authorized dealer or specialist for
cleaning.
• In case of malfunction of this
appliance, do not repair by
yourself. Contact to the sales
dealer or service dealer for a
repair.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete
blocks to provide a solid, level foundation
for the outdoor unit. This prevents water
damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down
with bolts and a metal frame. Provide a
suitable air baffle.
…In a Snowy Area (for Heat Pump-
type Systems)
Install the outdoor unit on a raised
platform that is higher than drifting snow.
Provide snow vents.
…At least 2.5 m
Indoor unit of this air conditioner shall be
installed in a height of at least 2.5 m.
…In laundry rooms
Do not install in laundry rooms. Indoor
unit is not drip proof.
When Connecting Refrigerant
Tubing
Pay particular attention to refrigerant
leakages.
CAUTION
WARNING
• When performing piping work,
do not mix air except for
specified refrigerant (R410A)
in refrigeration cycle. It causes
capacity down, and risk of
explosion and injury due to high
tension inside the refrigerant
cycle.
• If the refrigerant comes in contact
with a flame, it produces a toxic
gas.
• Do not add or replace refrigerant
other than specified type. It may
cause product damage, burst and
injury, etc.
• Ventilate the room immediately, in the
event that is refrigerant gas leaks during
the installation. Be careful not to allow
contact of the refrigerant gas with a
flame as this will cause the generation
of toxic gas.
01_II_281317_EU_Eng_L.indb 3 2016-7-12 9:20:56
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 3 18/01/12 18:47:4

iii
CAUTION
CAUTIN
• Ventilate any enclosed areas when
installing or testing the refrigeration
system. eaked refrigerant gas,
on contact with fire or heat, can
produce dangerously toxic gas.
• Confirm after installation that no
refrigerant gas is leaking. If the gas
comes in contact with a burning
stove, gas water heater, electric
room heater or other heat source,
it can cause the generation of toxic
gas.
thers
CAUTION
WARNING
• Do not sit or step on the unit.
You may fall down accidentally.
CAUTION
CAUTIN
• Do not touch the air inlet or
the sharp aluminum fins of the
outdoor unit. ou may get
injured.
• Do not stick any object into the
FA CASE.
ou may be injured and the unit
may be damaged.
01_II_281317_EU_Eng_L.indb 4 2016-7-12 9:20:57
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 4 18/01/12 18:47:4

iv
2. The standards for minimum room volume are as follows.
(1)No partition (shaded portion)
(2)When there is an effective opening with the adjacent room
for ventilation of leaking refrigerant gas (opening without
a door, or an opening 0.15% or larger than the respective
floor spaces at the top or bottom of the door).
(3) If an indoor unit is installed in each partitioned room and
the refrigerant tubing is interconnected, the smallest room
of course becomes the object. But when mechanical
ventilation is installed interlocked with a gas leakage
detector in the smallest room where the density limit is
exceeded, the volume of the next smallest room becomes
the object.
3. The minimum indoor floor space compared with the
amount of refrigerant is roughly as follows: (When the
ceiling is 2.7 m high)
40.5
54.0
27.0
13.5
0.0 20100304060708090 10050
67.5
81.0
94.5
108.0
121.5
135.0
148.5
162.0
175.5
189.0
202.5
216.0
229.5
243.0
256.0
270.0
m2m3
15
10
5
0
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
283.5
297.0
310.5
324.0
337.5
kg
Check of Density Limit
The room in which the air conditioner is to be installed
requires a design that in the event of refrigerant gas
leaking out, its density will not exceed a set limit.
The refrigerant (R410A), which is used in the air conditioner,
is safe, without the toxicity or combustibility of ammonia, and
is not restricted by laws imposed to protect the ozone layer.
However, since it contains more than air, it poses the risk of
suffocation if its density should rise excessively. Suffocation
from leakage of refrigerant is almost non-existent. With the
recent increase in the number of high density buildings,
however, the installation of multi air conditioner systems is
on the increase because of the need for effective use of floor
space, individual control, and energy conservation by curtailing
heat and carrying power, etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit of the
multi air conditioner system is to be installed in a small room,
select a suitable model and installation procedure so that if the
refrigerant accidentally leaks out, its density does not reach the
limit (and in the event of an emergency, measures can be made
before injury can occur).
In a room where the density may exceed the limit, create an
opening with adjacent rooms, or install mechanical ventilation
combined with a gas leak detection device. The density is as
given below. Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m3)
< Density limit (kg/m3)
The density limit of refrigerant which is used in multi air
conditioners is 0.44 kg/m3(ISO 5149).
NOTE
1. If there are 2 or more refrigerating systems in a single
refrigerating device, the amount of refrigerant should be as
charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A,
B and C is 10 kg.
The possible amount of leaked refrigerant gas in rooms D,
E and F is 15 kg.
e.g., charged
amount (10 kg)
Indoor unit
Outdoor unit
e.g., charged
amount (15 kg)
Room A Room B Room C Room D Room E Room F
Outdoor unit
Refrigerant tubing
Indoor unit
Mechanical ventilation device – Gas leak detector
Refrigerant tubing
Outdoor unit
Indoor unit
Very
small
room Small
room Medium
room Large room
Range below the
density limit of
0.44 kg/m³
(Countermeasures
not needed)
Range above the
density limit of 0.44
kg/m³
(Countermeasures
needed)
Total amount of refrigerant
Min. indoor volume
Min. indoor floor area
(when the ceiling is 2.7 m high)
CAUTION
CAUTIN
• Ventilate any enclosed areas when
installing or testing the refrigeration
system. eaked refrigerant gas,
on contact with fire or heat, can
produce dangerously toxic gas.
• Confirm after installation that no
refrigerant gas is leaking. If the gas
comes in contact with a burning
stove, gas water heater, electric
room heater or other heat source,
it can cause the generation of toxic
gas.
thers
CAUTION
WARNING
• Do not sit or step on the unit.
You may fall down accidentally.
CAUTION
CAUTIN
• Do not touch the air inlet or
the sharp aluminum fins of the
outdoor unit. ou may get
injured.
• Do not stick any object into the
FA CASE.
ou may be injured and the unit
may be damaged.
01_II_281317_EU_Eng_L.indb 4 2016-7-12 9:20:57
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 18/01/12 18:47:4

v
7-1
7-2
7-3
Section 7. REMOTE CONTROLLER FUNCTIONS SECTION...............................................
7-2. List of Simple Setting Items................................................................................................. 7-47-3. Detailed Settings Function .................................................................................................. 7-57-4. List of Detailed Setting Items .............................................................................................. 7-87-5. Simple Setting Items ............................................................................................................
7-107-6. Detailed Setting Items ........................................................................................................ 7-137-7. Remote Controller Servicing Functions .......................................................................... 7-147-8. Test Run Function ..............................................................................................................
7-1. Simple Settings Function ....................................................................................................
8-1
8-2
8-3
Section 8. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER RECEIVER.......
Important Safety Instructions ...............................................................................................
Optional Controller (Remote Controller) ..............................................................................
8-5
8-5
8-3
8-6
8-7
8-8
8-8
8-9
8-9
8-9
8-11
8-12
8-13
8-14
8-14
8-16
8-20
60Bὒᕞࢩࣥࢢࣝኳᇙ60LQGE
8-1. Names and Functions ..........................................................................................................
8-2. Installing Batteries ...............................................................................................................
8-3. Setting the Current Time .....................................................................................................
8-4. Operation ..............................................................................................................................
8-5. Timer Operation ...................................................................................................................
8-6. Adjusting the Wind Direction ..............................................................................................
8-7. Operating Multiple In/Outdoor Units Simultaneously (Group Control) ..........................
8-8. Using the Remote Controller ..............................................................................................
8-9. For Best Results ..................................................................................................................
8-10. Addresses ..........................................................................................................................
8-11. Emergency Operation ......................................................................................................
8-12. Miscellaneous Settings ....................................................................................................
8-13. Before Requesting Service ..............................................................................................
How to Install the Wireless Remote Controller Receiver ..................................................
8-14. Common to All Models ....................................................................................................
8-15. CZ-RWSC3 ........................................................................................................................
8-16. Common to All Models ....................................................................................................
—— CONTENTS ——
Section 1. SPECI FI CA TI ONS
1-1. U nit Specif ications
1-2. M aj or Component Specif ications
1-3 . Other Component Specif ications
1-4. D imensional D ata
1-5 . Ref rigerant Flow D iagram
1-6 . Operating Range
...................................................................................................1-1
...............................................................................................................2-1
...............................................................................................3 -1
.......................................................................................1-14
.................................................................................................................1-18
...................................................................................................1-22
..................................................................................................................1-23
.................................1-24
........................................................................................................1-26
........................................................................................................1-3 4
.....................................................................................................1-41
.............................................................................................1-6 8
............................................................................................................1-7 1
.............................................................................1-7 1
.........................................................................1-7 2
...................................................1-7 3
................................................................1-7 3
....................................................................................................................1-8 8
.............................................................................3 -2
................................................................................3 -4
.........................................................................................1-6
.................................................................................................................1-2
1-7 . Capacity Correction G raph A ccording to Temperature Condition
1-8 . Noise Criterion Curv es ......................................................................................................1-29
1-9. I ndoor Fan Perf ormance
1-10 . EL ECTRI CA L WI RI NG
1-11. I nstallation I nstructions
Section 2. TEST RU N
Section 3 . EL ECTRI CA L D A TA
3 -2. I ndoor U nits (Electric Wiring D iagram)
3 -1. Outdoor U nits (Electric Wiring D iagram)
................................................................................4-1
..................................................................................................................4-2
............................................4-8
Section 4. PROCESS A ND FU NCTI ONS
4-2. Outdoor U nit Control PCB (A CX A 7 3 -0 47 7 0 , A CX A 7 3 -0 47 5 0 )
4-1. Control Functions
..........................................................................................5 -1
........................................................5 -2
.............................................................................5 -4
Section 5 . TROU BL E D I A G NOSI S
.....................................................................................................5 -5
.....................................................................................5 -3 2
...............5 -3 3
.....5 -3 4
...................................................................................5 -3 5
........................................................................................5 -3 6
................................................................5 -3 7
.............5 -3 8
5 -1. Contents of Remote Controller Switch A larm D isplay
5 -2. Outdoor U nit Control Panel L ED D isplay
5 -3 . PA C Sy stem A larm Codes
5 -4. I nspection of Parts (Outdoor U nit)
5 -5 . Sy mptom: Thermostat in OFF continues or cy cles OFF & ON too f req uently
5 -6 . Sensor Temperature D isplay Function
(D isplay ed regardless of operation and stop)
5 -7 . Table of Thermistor Characteristics
5 -8 . How to Remov e the Compressor
5 -9. How to Remov e the Electrical Component Box
5 -10 . Sy mptom: Thermostat in OFF continues or cy cles OFF & ON too f req uently
..............................6 -1
.................................................................................................................................6 -2
................................................................................................................................6 -2
Section 6 . OU TD OOR U NI T M A I NTENA NCE REM OTE CONTROL L ER
.........................................................................6 -3
....6 -8
...6 -10
........................................................6 -11
6 -1. Ov erv iew
6 -2. Functions
6 -3 . Normal D isplay Operations and Functions
6 -4.
M onitoring Operations: D isplay of I ndoor U nit and Outdoor U nit Sensor Temperatures
6 -5 . M onitoring the Outdoor U nit A larm History : D isplay of Outdoor U nit A larm History
6 -6 . Settings M odes: Setting the Outdoor U nit EEPROM
..........................................................................................................2-2
....................................................................................................................................2-22-2. Caution ...............................................................................................................2-22-3 . Test Run Procedure ....................................................................................2-32-4. I tems to Check Bef ore the Test Run ................................................................................2-32-5 . Test Run U sing the Remote Controller
.............................................................................................................................2-42-6 . Precautions .........................................................2-52-7 . Table of Self -D iagnostic Functions and Corrections
.......................................................................................................................2-62-8 . Sy stem Control ......................................................................................................2-122-9. Caution f or Pump D own
2-1. Preparing f or Test Run
I ndoor U nits (Ty pe E1, E3 )
..........................................................................4-124-3 . Outdoor U nit HI C Board (A CX A 7 3 -0 47 6 0 ) ...........................................................4-134-4. I ndoor U nit Control PCB Switches and Functions
1-12. HOW TO PROCESS TU BI NG
1-13 . V A CU U M PU RG I NG
1-14. REG A RD I NG REFRI G ERA NT FI L L I NG
1-15 . PRECA U TI ONS REG A RD I NG TEST RU N
1-16 . CHECK S A FTER I NSTA L L A TI ON HA V E COM PL ETED
1-17 . REG A RD I NG D EL I V ERY TO THE CU STOM ER
1-19. Capacity Table
.........................................................................................................................1-7 4
1-18 . Supplement
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 6 18/01/26 14:04:02

vi
7-1
7-2
7-3
Section 7. REMOTE CONTROLLER FUNCTIONS SECTION...............................................
7-2. List of Simple Setting Items................................................................................................. 7-47-3. Detailed Settings Function .................................................................................................. 7-57-4. List of Detailed Setting Items .............................................................................................. 7-87-5. Simple Setting Items ............................................................................................................
7-107-6. Detailed Setting Items ........................................................................................................ 7-137-7. Remote Controller Servicing Functions .......................................................................... 7-147-8. Test Run Function ..............................................................................................................
7-1. Simple Settings Function ....................................................................................................
8-1
8-2
8-3
Section 8. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER RECEIVER.......
Important Safety Instructions ...............................................................................................
Optional Controller (Remote Controller) ..............................................................................
8-5
8-5
8-3
8-6
8-7
8-8
8-8
8-9
8-9
8-9
8-11
8-12
8-13
8-14
8-14
8-16
8-20
60Bὒᕞࢩࣥࢢࣝኳᇙ60LQGE
8-1. Names and Functions ..........................................................................................................
8-2. Installing Batteries ...............................................................................................................
8-3. Setting the Current Time .....................................................................................................
8-4. Operation ..............................................................................................................................
8-5. Timer Operation ...................................................................................................................
8-6. Adjusting the Wind Direction ..............................................................................................
8-7. Operating Multiple In/Outdoor Units Simultaneously (Group Control) ..........................
8-8. Using the Remote Controller ..............................................................................................
8-9. For Best Results ..................................................................................................................
8-10. Addresses ..........................................................................................................................
8-11. Emergency Operation ......................................................................................................
8-12. Miscellaneous Settings ....................................................................................................
8-13. Before Requesting Service ..............................................................................................
How to Install the Wireless Remote Controller Receiver ..................................................
8-14. Common to All Models ....................................................................................................
8-15. CZ-RWSC3 ........................................................................................................................
8-16. Common to All Models ....................................................................................................
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 7 18/01/12 18:47:0

vii
– MEMO –
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 8 18/01/12 18:47:0

1-1
11 1. SPECIFICATIONS
1-1. UnitSpecications.....................................................................................................1-2
1-2. MajorComponentSpecications.............................................................................1-6
1-3. OtherComponentSpecications...........................................................................1-14
1-4. DimensionalData.....................................................................................................1-18
1-5. RefrigerantFlowDiagram.......................................................................................1-22
1-6. OperatingRange......................................................................................................1-23
1-7. CapacityCorrectionGraphAccordingtoTemperatureCondition.....................1-24
1-8. NoiseCriterionCurves............................................................................................1-26
1-9. IndoorFanPerformance..........................................................................................1-29
1-10. ELECTRICALWIRING..............................................................................................1-34
1-11. Installation Instructions ..........................................................................................1-41
ŠOutdoorUnit
1. Tubing Length ...............................................................................................................................1-41
2. Check of limit density .........................................................................................................................1-42
3. SELECTING TH E INSTALLATION SITE ..........................................................................................1-43
4. INSTALLATION SERV ICE SPACE....................................................................................................1-44
5. TRANSPORT AND INSTALL TH E OUTDOOR UNIT .......................................................................1-45
6. REFRIG ERANT INSTALLATION........................................................................................................1-46
7. SELECTING TH E LOCATION FOR INSTALLATION SERV ICE .......................................................1-49
ŠIndoorUnit
8. SELECTING TH E INSTALLATION SITE .......................................................................................... 1-50
9 . H OW TO INSTALL TH E INDOOR UNIT ............................................................................................1-51
1-12.HOWTOPROCESSTUBING....................................................................................1-68
1-13.VACUUMPURGING..................................................................................................1-71
1-14.REGARDINGREFRIGERANTFILLING....................................................................1-71
1-15.PRECAUTIONSREGARDINGTESTRUN...............................................................1-72
1-16.CHECKSAFTERINSTALLATIONHAVECOMPLETED...........................................1-73
1-17.REGARDINGDELIVERYTOTHECUSTOMER........................................................1-73
1-18.Supplement...............................................................................................................1-74
1-19.CapacityTable..........................................................................................................1-88
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 1 18/01/26 13:2:1

1-2
11 Single-Type
1-1.UnitSpecications
DuctedTypeS-160PE1R5A/U-160PE2R8A
INDOOR M ODEL S-160PE1R5A - -
PANEL M ODEL - - -
OUTDOOR M ODEL - U-160PE2R8A -
Branch pipe M ODEL -
Performance test condition ISO13253 / AS / NZS3823.1
Power supply ø , H z 1ø 50H z 3ø 50H z -
V - 230V 240V - 400V 415V M in M ax
C
O
O
L
I
N
G
Capacity kW - 16.0 16.0 - - - 5.4 18.0
BTU/h - 54600 54600 - - - 18400 61400
Current A - 2.62 2.70 - 7.40 7.00 - -
Input power W - 59 0 640 - 4.59 0k 4.540k - -
TOTAL W - - 5.180k 5.180k - -
Annual consumption
TOTAL kWh * 4 - - - - 259 0 - - -
EER/AEER/EER CLASS
TOTAL (W/W)* 5 / (" A" ~ " G " )
- - - - 3.09 /3.01/- 3.09 - -
Power factor % - - - - 9 1 9 1 - -
Noise indoor dB-A (H /M /L) 51/49 /47 - - - - -
Power Level dB 73/71/69 - - - - -
Noise outdoor dB-A(H /L) - - - 59 /- - -
Power Level dB - - - 77/- - -
HE
A
T
I
N
G
Capacity kW - 18.0 18.0 - - - 5.6 20.0
BTU/h - 61400 61400 - - - 19 100 68200
Current A - 2.62 2.70 - 7.20 6.9 0 - -
Input power W - 59 0 640 - 4.520k 4.470k - -
TOTAL W - - 5.110k 5.110k - -
COP/ACOP/COP CLASS
TOTAL (W/W)* 5 / (" A" ~ " G " )
- - - - 3.52/3.44/- 3.52 - -
Power factor % - - - - 9 1 9 1 - -
Noise indoor dB-A (H /M /L) 51/49 /47 - - -
Power Level dB 73/71/69 - - -
Noise outdoor dB-A (H /L) - 61/- - -
Power Level dB - 79 /- - -
EX TRA LOW TEM P
Total capacity(kW)/Input power(W)/COP
- -
M ax Current(A) / M ax Input power(W) - 2.9 0/0.66k 3.00/0.71k - 20.0/12.6k 20.0/12.9 k -
Starting current(A) / Comp output(W) - - - - 7.40/3.8k 7.00/3.8k -
ora - - -
Fan motor output (Indoor/Outdoor) W 440 120 × 2 -
M oisture removal volume L/h(Pt/h) 9 .0 (18.9 ) - -
External static pressure Pa 100 / (10/150) - -
Indoor
irflo
Cooling m3/min (m3/h) (H /M /L) 60/50/42 (3600/3000/2520) - - -
H eating m3/min (m3/h) (H /M /L) 60/50/42 (3600/3000/2520) - - -
Outdoor
irflo
Cooling m3/min (m3/h) - 164 (9 840) - -
H eating m3/min (m3/h) - 164 (9 840) - -
Refrigerant type / amount g(oz) - R410A 5.60k (19 7.5) - -
Product dimension H eight mm (inch) 430 (16-15/16) 1500 (59 -1/16) -
Width mm (inch) 1100 (+ 100) (43-5/16 (+ 3-15/16)) 9 80 (38-37/64) -
Depth mm (inch) 700 (27-9 /16) 370 (14-9 /16) -
Packing dimension H eight mm (inch) 515 (20-9 /32) 1642 (64-41/64) -
Width mm (inch) 1315 (51-25/32) 109 5 (43-7/64) -
Depth mm (inch) 812 (31-31/32) 529 (20-53/64) -
Weight (NET) kg (lb) 53 (117) 127 (280) -
(G ROSS) kg (lb) 61 (134) 139 (306) -
Layers limit (actually) 6 (7) 1(2) -
Operation condition Cool (DBT) 18°C ~ 32°C -15°C ~ 46°C -
H eat (DBT) 16°C ~ 30°C -20°C ~ 24°C -
P
I
P
I
N
G
Pipe diameter mm (inch) (Liquid)ø 9 .52(3/8) (G as)ø 19 .05(3/4) -
-
Connecting method, Standard length m (ft) iiaflar -
Pipe length range m (ft) 5~ 50m (16.4~ 164.0) -
Indoor unit & Outdoor unit height difference m (ft)
30m(OD located lower)/30m(OD located higher) (9 8.4/9 8.4) -
Add gas amount g/m (oz/ ft) (Liquid)ø 9 .52(3/8) : 50g(0.54) -
Pipe length for additional gas m (ft) 30m (9 8.4) -
aiiaroiiaairflooiai3/min.) shall be multiplied by 16.7 and rounded down the decimal point.
rioaorarraoraroiiorarariraoa
230V shall be used.
* 3: Network Impedance shall be applicable for EUROPE and CH INA models.
* 4: The annual consumption is calculated by multiplying the input power at 230V (400V ) by an average of 500 hours per year in cooling mode.
aaiaioiaoiaoraiiri
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 2 18/01/26 13:2:1

1-3
11 Single-Type
HighStaticPressureDuctedTypeS-180PE3R5/U-180PE2R8A
INDOOR M ODEL S-180PE3R5 - -
PANEL M ODEL - - -
OUTDOOR M ODEL - U-180PE2R8A -
Branch pipe M ODEL -
Performance test condition ISO13253 / AS / NZS3823.1
Power supply ø , H z 1ø 50H z 3ø 50H z -
V 220V 230V 240V 380V 400V 415V M in M ax
C
O
O
L
I
N
G
Capacity kW - 18.0 18.0 - - - 5.4 20.0
BTU/h - 61400 61400 - - - 18400 68200
Current A - 3.10 3.00 - 8.55 8.25 - -
Input power W - 580 580 - 5.380k 5.380k - -
TOTAL W - - 5.9 60k 5.9 60k - -
Annual consumption
TOTAL kWh * 4 - - - - 29 80 - - -
EER/AEER/EER CLASS
TOTAL (W/W)* 5 / (" A" ~ " G " )
- - - - 3.02/2.9 6/- 3.02 - -
Power factor % - - - - 9 1 9 1 - -
Noise indoor dB-A (H /M /L) 46/44/41 - - - - -
Power Level dB 78/76/73 - - - - -
Noise outdoor dB-A(H /L) - - - 59 /- - -
Power Level dB - - - 77/- - -
HE
A
T
I
N
G
Capacity kW - 20.0 20.0 - - - 5.6 22.4
BTU/h - 68200 68200 - - - 19 100 76400
Current A - 3.10 3.00 - 8.05 7.80 - -
Input power W - 580 580 - 5.080k 5.080k - -
TOTAL W - - 5.660k 5.660k - -
COP/ACOP/COP CLASS
TOTAL (W/W)* 5 / (" A" ~ " G " )
- - - - 3.53/3.46/- 3.53 - -
Power factor % - - - - 9 1 9 1 - -
Noise indoor dB-A (H /M /L) 46/44/41 - - -
Power Level dB 78/76/73 - - -
Noise outdoor dB-A (H /L) - 61/- - -
Power Level dB - 79 /- - -
EX TRA LOW TEM P
Total capacity(kW)/Input power(W)/COP
- -
M ax Current(A) / M ax Input power(W) - 5.40/1150 5.30/1150 - 20.0/12.6k 20.0/13.1k -
Starting current(A) / Comp output(W) - - - - 8.55/4.2k 8.25/4.2k -
ora - - -
Fan motor output (Indoor/Outdoor) W 560 × 2 120 × 2 -
M oisture removal volume L/h(Pt/h) 3.8 (8.0) - -
External static pressure Pa 60 / (100/150) - -
Indoor
irflo
Cooling m3/min (m3/h) (H /M /L) 72/63/53 (4320/3780/3180) - - -
H eating m3/min (m3/h) (H /M /L) 72/63/53 (4320/3780/3180) - - -
Outdoor
irflo
Cooling m3/min (m3/h) - 164 (9 840) - -
H eating m3/min (m3/h) - 164 (9 840) - -
Refrigerant type / amount g(oz) - R410A 5.60k (19 7.5) - -
Product dimension H eight mm (inch) 486 (19 -1/8) 1500 (59 -1/16) -
Width mm (inch) 1456 (57-5/16) 9 80 (38-37/64) -
Depth mm (inch) 9 16 (36-1/16) 370 (14-9 /16) -
Packing dimension H eight mm (inch) 610 (24-1/32) 1642 (64-41/64) -
Width mm (inch) 1646 (60-13/16) 109 5 (43-7/64) -
Depth mm (inch) 1132 (44-9 /16) 529 (20-53/64) -
Weight (NET) kg (lb) 85 (188) 127 (280) -
(G ROSS) kg (lb) 105 (232) 139 (306) -
Layers limit (actually) 4 (5) 1(2) -
Operation condition Cool (DBT) 18°C ~ 32°C -15°C ~ 46°C -
H eat (DBT) 16°C ~ 30°C -20°C ~ 24°C -
P
I
P
I
N
G
Pipe diameter mm (inch) (Liquid)ø 9 .52(3/8) (G as)ø 19 .05(3/4) -
-
Connecting method, Standard length m (ft)
iiflararaioio
iiaflar -
Pipe length range m (ft) 5~ 50m (16.4~ 164.0) -
Indoor unit & Outdoor unit height difference m (ft)
30m(OD located lower)/30m(OD located higher) (9 8.4/9 8.4) -
Add gas amount g/m (oz/ ft) (Liquid)ø 9 .52(3/8) : 50g(0.54) -
Pipe length for additional gas m (ft) 30m (9 8.4) -
aiiaroiiaairflooiai3/min.) shall be multiplied by 16.7 and rounded down the decimal point.
rioaorarraoraroiiorarariraoa
230V shall be used.
* 3: Network Impedance shall be applicable for EUROPE and CH INA models.
* 4: The annual consumption is calculated by multiplying the input power at 230V (400V ) by an average of 500 hours per year in cooling mode.
aaiaioiaoiaoraiiri
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 3 18/01/26 13:2:1

1-4
11 Single-Type
HighStaticPressureDuctedTypeS-200PE3R5/U-200PE2R8A
INDOOR M ODEL S-200PE3R5 - -
PANEL M ODEL - - -
OUTDOOR M ODEL - U-200PE2R8A -
Branch pipe M ODEL -
Performance test condition ISO13253 / AS / NZS3823.1
Power supply ø , H z 1ø 50H z 3ø 50H z -
V 220V 230V 240V 380V 400V 415V M in M ax
C
O
O
L
I
N
G
Capacity kW - 20.0 20.0 - - - 6.3 22.4
BTU/h - 68200 68200 - - - 21500 76400
Current A - 3.30 3.20 - 9 .10 8.75 - -
Input power W - 610 610 - 5.380k 5.380k - -
TOTAL W - - 5.9 9 0k 5.9 9 0k - -
Annual consumption
TOTAL kWh * 4 - - - - 29 9 5 - - -
EER/AEER/EER CLASS
TOTAL (W/W)* 5 / (" A" ~ " G " )
- - - - 3.12/3.06/- 3.12 - -
Power factor % - - - - 9 2 9 2 - -
Noise indoor dB-A (H /M /L) 46/44/41 - - - - -
Power Level dB 78/76/73 - - - - -
Noise outdoor dB-A(H /L) - - - 60/- - -
Power Level dB - - - 79 /- - -
HE
A
T
I
N
G
Capacity kW - 22.4 22.4 - - - 7.1 25.0
BTU/h - 76400 76400 - - - 24200 85300
Current A - 3.30 3.20 - 8.85 8.55 - -
Input power W - 610 610 - 5.59 0k 5.59 0k - -
TOTAL W - - 6.200k 6.200k - -
COP/ACOP/COP CLASS
TOTAL (W/W)* 5 / (" A" ~ " G " )
- - - - 3.61/3.54/- 3.61 - -
Power factor % - - - - 9 1 9 1 - -
Noise indoor dB-A (H /M /L) 46/44/41 - - -
Power Level dB 78/76/73 - - -
Noise outdoor dB-A (H /L) - 62/- - -
Power Level dB - 81/- - -
EX TRA LOW TEM P
Total capacity(kW)/Input power(W)/COP
- -
M ax Current(A) / M ax Input power(W) - 5.70/1220 5.60/1220 - 20.0/12.8k 20.0/13.2k -
Starting current(A) / Comp output(W) - - - - 9 .10/4.8k 8.75/4.8k -
ora - - -
Fan motor output (Indoor/Outdoor) W 560 × 2 120 × 2 -
M oisture removal volume L/h(Pt/h) 6.0 (12.6) - -
External static pressure Pa 75 / (120/180) - -
Indoor
irflo
Cooling m3/min (m3/h) (H /M /L) 72/63/53 (4320/3780/3180) - - -
H eating m3/min (m3/h) (H /M /L) 72/63/53 (4320/3780/3180) - - -
Outdoor
irflo
Cooling m3/min (m3/h) - 160 (9 600) - -
H eating m3/min (m3/h) - 160 (9 600) - -
Refrigerant type / amount g(oz) - R410A 6.40k (225.8) - -
Product dimension H eight mm (inch) 486 (19 -1/8) 1500 (59 -1/16) -
Width mm (inch) 1456 (57-5/16) 9 80 (38-37/64) -
Depth mm (inch) 9 16 (36-1/16) 370 (14-9 /16) -
Packing dimension H eight mm (inch) 610 (24-1/32) 1642 (64-41/64) -
Width mm (inch) 1646 (60-13/16) 109 5 (43-7/64) -
Depth mm (inch) 1132 (44-9 /16) 529 (20-53/64) -
Weight (NET) kg (lb) 86 (19 0) 138 (304) -
(G ROSS) kg (lb) 106 (234) 150 (331) -
Layers limit (actually) 4 (5) 1 (2) -
Operation condition Cool (DBT) 18°C ~ 32°C -15°C ~ 46°C -
H eat (DBT) 16°C ~ 30°C -20°C ~ 24°C -
P
I
P
I
N
G
Pipe diameter mm (inch) ~ 30 m (Liquid)ø 12.7(1/2) (G as)ø 19 ,05(3/4) -
Pipe diameter mm (inch) Over 30 m (Liquid)ø 12.7(1/2) (G as)ø 25.4(1) -
Connecting method, Standard length m (ft)
iiflararaioio iiflararaioio
-
Pipe length range m (ft) 5~ 50m (16.4~ 164.0) -
Indoor unit & Outdoor unit height difference m (ft)
30m(OD located lower)/30m(OD located higher) (9 8.4/9 8.4) -
Add gas amount g/m (oz/ ft) iig(0.860) -
Pipe length for additional gas m (ft) 30m (9 8.4) -
aiiaroiiaairflooiai3/min.) shall be multiplied by 16.7 and rounded down the decimal point.
rioaorarraoraroiio°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
* 3: Network Impedance shall be applicable for EUROPE and CH INA models.
* 4: The annual consumption is calculated by multiplying the input power at 230V (400V ) by an average of 500 hours per year in cooling mode.
aaiaioiaoiaoraiiri
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 4 18/01/26 13:2:20

1-5
11 Single-Type
HighStaticPressureDuctedTypeS-224PE3R5/U-224PE2R8A
INDOOR M ODEL S-224PE3R5 - -
PANEL M ODEL - - -
OUTDOOR M ODEL - U-224PE2R8A -
Branch pipe M ODEL -
Performance test condition ISO13253 / AS / NZS3823.1
Power supply ø , H z 1ø 50H z 3ø 50H z -
V 220V 230V 240V 380V 400V 415V M in M ax
C
O
O
L
I
N
G
Capacity kW - 22.4 22.4 - - - 6.3 25.0
BTU/h - 76400 76400 - - - 21500 85300
Current A - 4.20 4.10 - 10.3 9 .9 - -
Input power W - 830 830 - 5.380k 5.380k - -
TOTAL W - - 6.210k 6.210k - -
Annual consumption
TOTAL kWh * 4 - - - - 3105 - - -
EER/AEER/EER CLASS
TOTAL (W/W)* 5 / (" A" ~ " G " )
- - - - 3.00/2.9 5/- 3.00 - -
Power factor % - - - - 75 76 - -
Noise indoor dB-A (H /M /L) 47/45/42 - - - - -
Power Level dB 79 /77/74 - - - - -
Noise outdoor dB-A(H /L) - - - 60/- - -
Power Level dB - - - 79 /- - -
HE
A
T
I
N
G
Capacity kW - 25.0 25.0 - - - 7.1 28.0
BTU/h - 85300 85300 - - - 24200 9 5500
Current A - 4.20 4.10 - 9 .85 9 .50 - -
Input power W - 830 830 - 6.270k 6.270k - -
TOTAL W - - 7.100k 7.100k - -
COP/ACOP/COP CLASS
TOTAL (W/W)* 5 / (" A" ~ " G " )
- - - - 3.52/3.46/- 3.52 - -
Power factor % - - - - 9 2 9 2 - -
Noise indoor dB-A (H /M /L) 47/45/42 - - -
Power Level dB 79 /77/74 - - -
Noise outdoor dB-A (H /L) - 62/- - -
Power Level dB - 81/- - -
EX TRA LOW TEM P
Total capacity(kW)/Input power(W)/COP
- -
M ax Current(A) / M ax Input power(W) - 6.40/1440 6.30/1440 - 20.0/12.9 k 20.0/13.4k -
Starting current(A) / Comp output(W) - - - - 10.3/5.5k 9 .9 /5.5k -
ora - - -
Fan motor output (Indoor/Outdoor) W 750 × 2 120 × 2 -
M oisture removal volume L/h(Pt/h) 6.2 (13.0) - -
External static pressure Pa 75 / (130/200) - -
Indoor
irflo
Cooling m3/min (m3/h) (H /M /L) 84/72/59 (5040/4320/3540) - - -
H eating m3/min (m3/h) (H /M /L) 84/72/59 (5040/4320/3540) - - -
Outdoor
irflo
Cooling m3/min (m3/h) - 160 (9 600) - -
H eating m3/min (m3/h) - 160 (9 600) - -
Refrigerant type / amount g(oz) - R410A 6.40k (225.8) - -
Product dimension H eight mm (inch) 486 (19 -1/8) 1500 (59 -1/16) -
Width mm (inch) 1456 (57-5/16) 9 80 (38-37/64) -
Depth mm (inch) 9 16 (36-1/16) 370 (14-9 /16) -
Packing dimension H eight mm (inch) 610 (24-1/32) 1642 (64-41/64) -
Width mm (inch) 1646 (60-13/16) 109 5 (43-7/64) -
Depth mm (inch) 1132 (44-9 /16) 529 (20-53/64) -
Weight (NET) kg (lb) 88 (19 5) 138 (304) -
(G ROSS) kg (lb) 108 (239 ) 150 (331) -
Layers limit (actually) 4 (5) 1 (2) -
Operation condition Cool (DBT) 18°C ~ 32°C -15°C ~ 46°C -
H eat (DBT) 16°C ~ 30°C -20°C ~ 24°C -
P
I
P
I
N
G
Pipe diameter mm (inch) ~ 30 m (Liquid)ø 12.7(1/2) (G as)ø 19 ,05(3/4) -
Pipe diameter mm (inch) Over 30 m (Liquid)ø 12.7(1/2) (G as)ø 25.4(1) -
Connecting method, Standard length m (ft)
iiflararaioio iiflararaioio
-
Pipe length range m (ft) 5~ 50m (16.4~ 164.0) -
Indoor unit & Outdoor unit height difference m (ft)
30m(OD located lower)/30m(OD located higher) (9 8.4/9 8.4) -
Add gas amount g/m (oz/ ft) (Liquid)ø 12.7(1/2) : 80g(0.860) -
Pipe length for additional gas m (ft) 30m (9 8.4) -
aiiaroiiaairflooiai3/min.) shall be multiplied by 16.7 and rounded down the decimal point.
rioaorarraoraroiio°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
* 3: Network Impedance shall be applicable for EUROPE and CH INA models.
* 4: The annual consumption is calculated by multiplying the input power at 230V (400V ) by an average of 500 hours per year in cooling mode.
aaiaioiaoiaoraiiri
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 18/01/26 13:2:20

1-6
11
11-2. M aj or Component Specif ications
(A ) I ndoor U nits
High Static Pressure D ucted Ty pe S-18 0 PE3 R5
M OD EL No.
Source
Controller P.C.B. A ss' y
Fan (Number...diameter) mm
Fan motor
WM odel...Nominal output
Power source rpmNo. of pole...r.p.m. (230V , H igh)
Coil resistance
(Ambient temperature 20°C)
V AC, µ FRun capacitor
Electronic expansion v alv e
Coil
Coil resistance (at 20°C)
V alve body
Heat exchanger
Coil mmRows...fin pitch mFace area 2
S-18 0 PE3 R5
230 - 240V , single-phase, 50H z
ACX A73C22170
SIROCCO (2...ø 250)
DM UB6D3AC...560W
DM UB6D4AC...560W
100 - 39 1 V DC
8P...1080
–
–
–
––
Aluminium plate fin / Copper tube
3...1.8
0.505
1
1
1-2. M aj or Component Specif ications
(A ) I ndoor U nits
D ucted Ty pe S-16 0 PE1R5 A
M OD EL No.
Source
Controller P.C.B. A ss' y
Fan (Number...diameter) mm
Fan motor
WM odel...Nominal output
Power source rpmNo. of pole...r.p.m. (230V , H igh)
Coil resistance
(Ambient temperature 20°C)
V AC, µ FRun capacitor
Electronic expansion v alv e
Coil
Coil resistance (at 20°C)
V alve body
Heat exchanger
Coil mmRows...fin pitch mFace area 2
S-16 0 PE1R5 A
230 - 240V , single-phase, 50H z
C39 37-840-1Y
SIROCCO(2 / Ø 225)
Y SK 350-4G 440W
220-240 V AC
4P/1150± 30
Aluminum plate fin / Copper tube
3...1.4
0.363
-
-
-
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 6 18/01/26 13:2:20

1-7
11
11-2. M aj or Component Specif ications
(A ) I ndoor U nits
High Static Pressure D ucted Ty pe S-18 0 PE3 R5
M OD EL No.
Source
Controller P.C.B. A ss' y
Fan (Number...diameter) mm
Fan motor
WM odel...Nominal output
Power source rpmNo. of pole...r.p.m. (230V , H igh)
Coil resistance
(Ambient temperature 20°C)
V AC, µ FRun capacitor
Electronic expansion v alv e
Coil
Coil resistance (at 20°C)
V alve body
Heat exchanger
Coil mmRows...fin pitch mFace area 2
S-18 0 PE3 R5
230 - 240V , single-phase, 50H z
ACX A73C22170
SIROCCO (2...ø 250)
DM UB6D3AC...560W
DM UB6D4AC...560W
100 - 39 1 V DC
8P...1080
–
–
–
––
Aluminium plate fin / Copper tube
3...1.8
0.505
1
11-2. M aj or Component Specif ications
(A ) I ndoor U nits
D ucted Ty pe S-16 0 PE1R5 A
M OD EL No.
Source
Controller P.C.B. A ss' y
Fan (Number...diameter) mm
Fan motor
WM odel...Nominal output
Power source rpmNo. of pole...r.p.m. (230V , H igh)
Coil resistance
(Ambient temperature 20°C)
V AC, µ FRun capacitor
Electronic expansion v alv e
Coil
Coil resistance (at 20°C)
V alve body
Heat exchanger
Coil mmRows...fin pitch mFace area 2
S-16 0 PE1R5 A
230 - 240V , single-phase, 50H z
C39 37-840-1Y
SIROCCO(2 / Ø 225)
Y SK 350-4G 440W
220-240 V AC
4P/1150± 30
Aluminum plate fin / Copper tube
3...1.4
0.363
-
-
-
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 7 18/01/26 13:2:20

1-8
11
1
(A ) I ndoor U nits
High Static Pressure D ucted Ty pe S-20 0 PE3 R5
M OD EL No.
Source
Controller P.C.B. A ss' y
Fan (Number...diameter) mm
Fan motor
WM odel...Nominal output
Power source rpmNo. of pole...r.p.m. (230V , H igh)
Coil resistance
(Ambient temperature 20°C)
V AC, µ FRun capacitor
Electronic expansion v alv e
Coil
Coil resistance (at 20°C)
V alve body
Heat exchanger
Coil mmRows...fin pitch mFace area 2
S-20 0 PE3 R5
230 - 240V , single-phase, 50H z
ACX A73C22170
SIROCCO (2...ø 250)
DM UB6D3AC...560W
DM UB6D4AC...560W
100 - 39 1 V DC
8P...1080
–
–
–
––
Aluminium plate fin / Copper tube
3...1.8
0.642
1(A ) I ndoor U nits
High Static Pressure D ucted Ty pe S-224PE3 R5
M OD EL No.
Source
Controller P.C.B. A ss' y
Fan (Number...diameter) mm
Fan motor
WM odel...Nominal output
Power source rpmNo. of pole...r.p.m. (230V , H igh)
Coil resistance
(Ambient temperature 20°C)
V AC, µ FRun capacitor
Electronic expansion v alv e
Coil
Coil resistance (at 20°C)
V alve body
Heat exchanger
Coil mmRows...fin pitch mFace area 2
S-224PE3 R5
230 - 240V , single-phase, 50H z
ACX A73C22170
SIROCCO (2...ø 250)
DM UB8D4AC...750W
DM UB8D5AC...750W
100 - 39 1 V DC
8P...1180
–
–
–
––
Aluminium plate fin / Copper tube
3...1.8
0.642
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 8 18/01/26 13:2:20

1-9
11 1(A ) I ndoor U nits
High Static Pressure D ucted Ty pe S-224PE3 R5
M OD EL No.
Source
Controller P.C.B. A ss' y
Fan (Number...diameter) mm
Fan motor
WM odel...Nominal output
Power source rpmNo. of pole...r.p.m. (230V , H igh)
Coil resistance
(Ambient temperature 20°C)
V AC, µ FRun capacitor
Electronic expansion v alv e
Coil
Coil resistance (at 20°C)
V alve body
Heat exchanger
Coil mmRows...fin pitch mFace area 2
S-224PE3 R5
230 - 240V , single-phase, 50H z
ACX A73C22170
SIROCCO (2...ø 250)
DM UB8D4AC...750W
DM UB8D5AC...750W
100 - 39 1 V DC
8P...1180
–
–
–
––
Aluminium plate fin / Copper tube
3...1.8
0.642
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 18/01/26 13:2:20

1-10
11
(B) Outdoor Units
U-180PE2R8A
MODEL No.
Source
Controller P.C.B. Ass'y
Control circuit fuse
Compressor
Model....number
Source
WNominal output
ccCompressor oil
Coil resistance
(Ambient temperature 25°C) ΩU-V 0.678 U-W 0.700 V-W 0.691
Safety control
Overload relay models
Operation temperature Open °C
Close °C
WCrank case heater
Refrigerant amount at shipment kg
High pressure switch
Set pressure MPaOFF
3.05±0.2MPa ON
Fan
mmNumber...diameter
m3 / hAir circulation
Fan speeds (Max.)
Fan motor
Model No.
Source
No. of pole
WNominal output
Safety device
Operating temperature Open °C
Close °C
VAC, µF
Heat exchanger
Coil
mmRows...fin pitch
m2
U-180PE2R8A
400/415V 3-Phase 50Hz
ACXA73C07280
30A
5JD650XDB22
520V DC MOTOR
4,200
2,050
Discharge temperature control
–
–
–
230V-36W
R410A-5.6
2...ø540
164
NFD-81FW-D8120-1, NFD-81FW-D8120-2
~280V / 1-phase
8
120
–
–
–
–
Aluminium plate fin / Copper tube
2...17FPI
1.367Face area
Run capacitor
4.15 +0
-0.2
(B) Outdoor U nits
U -16 0 PE2R8 A
M OD EL No.
Source
Controller P.C.B. A ss' y
Control circuit fuse
Compressor
M odel....number
Source WNominal output ccCompressor oil
Coil resistance
(Ambient temperature 25°C) U-V 0.678 U-W 0.700 V -W 0.69 1
Safety control
Overload relay models
Operation temperature Open °C
Close °CWCrank case heater
Ref rigerant amount at shipment kg
High pressure switch
Set pressure M PaOFF 3.05± 0.2M PaON
Fan mmNumber...diameter m3/ hAir circulation
Fan speeds (M ax.)
Fan motor
M odel No.
Source
No. of pole WNominal output
Safety device
Operating temperature Open °C
Close °C
V AC, µ F
Heat exchanger
Coil mmRows...fin pitch m2
U-160PE2R8A
400/415V 3-Phase 50H z
ACX A73C07280
30A
5JD 650X DB22
520V DC M OTOR
4,200
2,050
Discharge temperature control
––
–
230V -36W
R410A-5.6
2...ø 540
164
NFD-81FW-D8120-1, NFD-81FW-D8120-2
~ 280V / 1-phase
8
120
––––
Aluminium plate fin / Copper tube
2...17FPI
1.367Face area
Run capacitor
4.15 + 0
-0.2
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 10 18/01/26 13:2:20

1-11
11
(B) Outdoor Units
U-180PE2R8A
MODEL No.
Source
Controller P.C.B. Ass'y
Control circuit fuse
Compressor
Model....number
Source
WNominal output
ccCompressor oil
Coil resistance
(Ambient temperature 25°C) ΩU-V 0.678 U-W 0.700 V-W 0.691
Safety control
Overload relay models
Operation temperature Open °C
Close °C
WCrank case heater
Refrigerant amount at shipment kg
High pressure switch
Set pressure MPaOFF
3.05±0.2MPa ON
Fan
mmNumber...diameter
m3 / hAir circulation
Fan speeds (Max.)
Fan motor
Model No.
Source
No. of pole
WNominal output
Safety device
Operating temperature Open °C
Close °C
VAC, µF
Heat exchanger
Coil
mmRows...fin pitch
m2
U-180PE2R8A
400/415V 3-Phase 50Hz
ACXA73C07280
30A
5JD650XDB22
520V DC MOTOR
4,200
2,050
Discharge temperature control
–
–
–
230V-36W
R410A-5.6
2...ø540
164
NFD-81FW-D8120-1, NFD-81FW-D8120-2
~280V / 1-phase
8
120
–
–
–
–
Aluminium plate fin / Copper tube
2...17FPI
1.367Face area
Run capacitor
4.15 +0
-0.2
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 11 18/01/26 13:2:20

1-12
11
(B) Outdoor Units
U-200PE2R8A
MODEL No.
Source
Controller P.C.B. Ass'y
Control circuit fuse
Compressor
Model....number
Source
WNominal output
ccCompressor oil
Coil resistance
(Ambient temperature 25°C) ΩU-V 0.678 U-W 0.700 V-W 0.691
Safety control
Overload relay models
Operation temperature Open °C
Close °C
WCrank case heater
Refrigerant amount at shipment kg
High pressure switch
Set pressure MPaOFF
3.05±0.2MPa ON
Fan
mmNumber...diameter
m3 / hAir circulation
Fan speeds (Max.)
Fan motor
Model No.
Source
No. of pole
WNominal output
Safety device
Operating temperature Open °C
Close °C
VAC, µF
Heat exchanger
Coil
mmRows...fin pitch
m2
U-200PE2R8A
400/415V 3-Phase 50Hz
ACXA73C07260
30A
5JD650XDB22
520V DC MOTOR
4,800
2,050
Discharge temperature control
–
–
–
230V-36W
R410A-6.4
2...ø540
160
~280V / 1-phase
8
120
–
–
–
–
Aluminium plate fin / Copper tube
3...17FPI
1.367Face area
Run capacitor
NFD-81FW-D8120-1, NFD-81FW-D8120-2
4.15 +0
-0.2
(B) Outdoor Units
U-224PE2R8A
U-V 0.678 U-W 0.700 V-W 0.691
MODEL No.
Source
Controller P.C.B. Ass'y
Control circuit fuse
Compressor
Model....number
Source WNominal output ccCompressor oil
Coil resistance
(Ambient temperature 25°C) Ω
Safety control
Overload relay models
Operation temperature Open °C
Close °CWCrank case heater
Refrigerant amount at shipment kg
High pressure switch
Set pressure MPaOFF MPaON
Fan mmNumber...diameter m3/ hAir circulation
Fan speeds (Max.)
Fan motor
Model No.
Source
No. of pole WNominal output
Safety device
Operating temperature Open °C
Close °C
VAC, µF
Heat exchanger
Coil mmRows...fin pitch m2
Face area
Run capacitor
U-224PE2R8A
400/415V 3-Phase 50Hz
ACXA73C07260
30A
520V DC MOTOR
5,500
2,050
–
–
–
230V-36W
R410A-6.4
2…ø540
160
~280V / 1-phase
8
120
–
–
–
–
3...17FPI
1.367
5JD650XDB22
Discharge temperature control
Aluminium plate fin / Copper tube
3.05±0.2
NFD-81FW-D8120-1, NFD-81FW-D8120-2
4.15 +0
-0.2
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 12 18/01/26 13:2:21
This manual suits for next models
7
Table of contents
Other Panasonic Inverter manuals

Panasonic
Panasonic VF0 Series 400V class User manual

Panasonic
Panasonic EVERVOLT EVHB-I7 User manual

Panasonic
Panasonic VF200 User manual

Panasonic
Panasonic U-200PE1E8 Manual

Panasonic
Panasonic S-200PE2E5 Manual

Panasonic
Panasonic EVERVOLT Smart Box User manual

Panasonic
Panasonic VF100 User manual

Panasonic
Panasonic VF0 Series User manual

Panasonic
Panasonic U-26PE1U6 Manual

Panasonic
Panasonic M2X Series User manual