  9. Parker Superheat Control User manual

Parker Superheat Control User manual

Other Parker Controllers manuals

Parker Porter MPC Series Assembly instructions

Parker

Parker Porter MPC Series Assembly instructions

Parker 690+ series User manual

Parker

Parker 690+ series User manual

Parker Sporlan PSK Series User manual

Parker

Parker Sporlan PSK Series User manual

Parker AC10 series User manual

Parker

Parker AC10 series User manual

Parker ADAPTOMODE A4A Series Guide

Parker

Parker ADAPTOMODE A4A Series Guide

Parker AC890PX Series User manual

Parker

Parker AC890PX Series User manual

Parker IPA Series Manual

Parker

Parker IPA Series Manual

Parker A4AP-DN Manual

Parker

Parker A4AP-DN Manual

Parker 890 Series Instruction manual

Parker

Parker 890 Series Instruction manual

Parker IQAN-MC2 User manual

Parker

Parker IQAN-MC2 User manual

Parker 6K8 User manual

Parker

Parker 6K8 User manual

Parker A2B Manual

Parker

Parker A2B Manual

Parker AC30V Series User manual

Parker

Parker AC30V Series User manual

Parker Lucifer EPP4 P4BG4 Series User instructions

Parker

Parker Lucifer EPP4 P4BG4 Series User instructions

Parker XLT Series Datasheet

Parker

Parker XLT Series Datasheet

Parker IQAN-XA2 User manual

Parker

Parker IQAN-XA2 User manual

Parker Hauser COMPAX-S Series User manual

Parker

Parker Hauser COMPAX-S Series User manual

Parker Compumotor 6000 Series User manual

Parker

Parker Compumotor 6000 Series User manual

Parker AC10 series User manual

Parker

Parker AC10 series User manual

Parker 514C User manual

Parker

Parker 514C User manual

Parker PLLC Service manual

Parker

Parker PLLC Service manual

Parker ADAPTOMODE A4AS Guide

Parker

Parker ADAPTOMODE A4AS Guide

Parker AC30V Series User manual

Parker

Parker AC30V Series User manual

Parker HBN15 Datasheet

Parker

Parker HBN15 Datasheet

Popular Controllers manuals by other brands

Sunricher SR-ZV9003T3-RGBW-US Installation

Sunricher

Sunricher SR-ZV9003T3-RGBW-US Installation

Ksenia intro Installation and configuration manual

Ksenia

Ksenia intro Installation and configuration manual

Inovance CAN200 Series manual

Inovance

Inovance CAN200 Series manual

Gauzy LC6 FLEX Controller Installation and operation guide

Gauzy

Gauzy LC6 FLEX Controller Installation and operation guide

Viking SLP-1 Technical practice

Viking

Viking SLP-1 Technical practice

CKD KBX-30E-U Series instruction manual

CKD

CKD KBX-30E-U Series instruction manual

Sharp Energy Sun Flux User manual & installation guide

Sharp Energy

Sharp Energy Sun Flux User manual & installation guide

Yamaha RCX40 user manual

Yamaha

Yamaha RCX40 user manual

AB Quality PowerFlex 400 Frames D-H Service bulletin

AB Quality

AB Quality PowerFlex 400 Frames D-H Service bulletin

Yamaha MJC8 owner's manual

Yamaha

Yamaha MJC8 owner's manual

AL-KO ATC operating instructions

AL-KO

AL-KO ATC operating instructions

Savant SmartControl 2 Deployment guide

Savant

Savant SmartControl 2 Deployment guide

GameSir T3S user manual

GameSir

GameSir T3S user manual

Kostal inveor operating manual

Kostal

Kostal inveor operating manual

Emerson Yarway 20-55 Operating and safety instructions

Emerson

Emerson Yarway 20-55 Operating and safety instructions

CoCo ACM-LV24 Quick installation guide

CoCo

CoCo ACM-LV24 Quick installation guide

Brooks SLA5810/20 Installation and operation manual

Brooks

Brooks SLA5810/20 Installation and operation manual

SIGMA TEK SR 011 Technical manual

SIGMA TEK

SIGMA TEK SR 011 Technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Superheat Control
Quick Reference Guide
The Sporlan Superheat Control should be installed only by a qualified professional. All other system components (valves and sensors)
should be supplied by Sporlan to ensure compatibility and proper operation. There are no user-serviceable components inside the con-
troller. Opening the case will void the warranty.
Tools required:
• Small flat screwdriver for terminals
• Cordless screwdriver
• Phillips and flat screwdrivers
• Needle-nose pliers
• Wire cutters
• Two #8 x ½” self-tapping screws to
mount the DIN rail
1. INSTALLATION
Reference diagram on back of this guide.
1. Mount the controller in a rain-tight,
protected location using the DIN rail.
The suggested mounting area is 10
inches high and 5 inches wide, depth is
3 inches.
2. Mount the suction temperature sensor to
the suction line after the heat exchanger
following the instructions provided with
the sensor. Connect the non-polarized
sensor wires to terminals 31 and 32.
Maximum torque on screw terminals
is 3.5 in-lbs.
3. Mount the pressure transducer on the
suction line near the suction tempera-
ture sensor, positioned at 12 o’clock.
Connect the wires to terminals 33, 34,
and 35. Ensure that any splices are
properly connected.
Use caution when working around high voltage components.
Safety covers should be used for personal safety on high voltage panels.
4. Connect terminals 27 and 28 to a digital
input. A short or a closed contact from
an external relay will close the valve for
pump down.
5. Connect the Electric Expansion Valve
(EEV) wires to terminals 5, 6, 7, and 8.
6. Connect the optional case temperature
sensor wires to terminals 29 and 30.
The sensor is not polarized.
7. Connect power to terminals 1 and 2.
Transformer requirements are 24 volts
AC at 40 VA, Class II.
2. SETUP
Enter values for six system variables. The
EEV is closed upon startup and the system
will not operate until completing setup.
Once powered up, the controller will dis-
play the firmware versions and then the
first variable to set.
1. Set StEP, Step Motor Stroke. Press and
then turn the SELECT knob to select
the correct number of steps for the
EEV being used. Default is 2500.
Press the SELECT knob again to save
the value. The next variable displays.
2. Set reFr, Refrigerant. Select the
actual refrigerant used in the system.
Default is 404A.
3. Set tt4P, Temperature Sensor Type.
Select 2K or 3K. Default is 2K.
4. Set Pt4P, Pressure Sensor Type. Select
Absolute or Gauge, following the steps
above. Default is Gauge.
5. Set Un_t, Temperature Units. Select
Fahrenheit or Celsius. Default is
Fahrenheit.
6. Set Un_p, Pressure Units. Select PSI ot
Bar. Default is PSI.
Setup is complete. The controller will
display SvpH. The controller is now in the
Process Values Menu. Rotate the knob to
view the values.
Temperature sensor should be mounted at
either 4 or 8 o’clock, on a free-draining line.
Sporlan Superheat Control
Installation and Operation Manual
SD-324/72016 Controller v. J
For detailed instructions,
scan this QR code or go to
www.sporlanonline.com/electronic-controls
and download Bulletin 100-50-5.1
3. OPERATION
For further system tuning, adjust parameter
setpoints as described below and in Bulletin
100-50-5.1.
1. Enter the Parameter Menu: Hold down
the SELECT knob for 5 seconds.
Rotate the knob to enter the password
“111 ”and press the SELECT knob
again.
2. To change a parameter, rotate the
SELECT knob to the desired param-
eter and press the SELECT knob. The
default parameter value will display.
3. Turn the SELECT knob to change the
parameter value and then press the
SELECT knob to save the value and
return to the Parameter Menu.
4. After all parameters are set, rotate the
SELECT knob to “ESC” and press the
SELECT knob again to save all chang-
es. Observe the system for superheat
operation.
Note: The Parameter Menu times out
after 60 seconds of inactivity and
all changes entered will be lost.
Note: Not all refrigeration systems are
designed alike. See the Kelvin II
Installation and Operation Manual
to adjust the settings according to
the specific needs of the system.
Note: Use caution when working
around high voltage components.
Dry Contacts (T3)
Evap. Outlet Temp. (T1)
Room Temp. (T2)
White
Green
Black
Black
24V
AC/DC
RS485
White
Green
Red
B-
Ground
A+
Suction Temperature
Sensor
Pressure
Transducer
Pumpdown
Relay
L1
L2
EEV
Load
Line
Liquid Line
Solenoid Valve
10”-14”
minimize
1”- 2” ideal
Evaporator
Aux. Temp. (T4)
Internal Relay
Rated 240v, 3A
*
*T3 can be used as an Auxillary Temperature Input or a Pumpdown Input signal.
Note: Piping and sensor insulation is not shown.
Refer to the evaporator manufacturer’s
installation/orientation instructions.
White
Green
Black
Black
White
Green
Red
Return Air
For 500 Step Sporlan Unipolar Valve
4 -> Gray Wire
5 -> Orange Wire
6 -> Yellow Wire
7 -> Red Wire
8 -> Black Wire
For safety information, see the Safety Guide at www.parker.com/safety or call 1-800-CPARKER.
Parker Hannin Corporation
Sporlan Division
206 Lange Drive • Washington, MO 63090 USA
phone 636 239 1111 • fax 636 239 9130
www.sporlan.com
SD-324 / 72016© 2016 Parker Hannin Corporation.
SD-324, July 2016 supersedes SD-324, October 2012 and all prior publications.