CM-22200 CTX6 Series Compac®Thermoplastic Emergency Unit with Xtest
dimensions
5-11/16"
(128.3mm)
5-1/4"
(133.6mm)
11-1/16"
(280.9mm)
photometry
Meets Life Safety Code standard minimum illuminance of 0.1 FC and average
illuminance of 1.0 FC.Assumes open space with no obstructions, mounting
height: 8', ceiling height: 9', and reflectances: 80/50/20.Analysis based on
independently tested photometrics.
3'
Xtest testing specifications
• Automatic Test:The system charger and lamps are continually being
controlled via pre-determined parameters specific to each model
configuration, automatically.The battery is controlled via a true open circuit
test each hour after initial installation. One each month the Xtest System
illuminates lamps under load for 30 minutes, simulating a power outage
with a true charger off condition, without affecting long term battery life.
This is above and beyond the requirements of the National Fire Protection
Association.This gives you unequaled control and confidence, knowing you
are meeting self-test code requirements each and every month.
• Manual Test:A manual test switch allows for the Xtest system to perform
the following tests at any time:
Press Button
Once–5 second test, charger off, no load
Twice–60 second test, charger off, lamps on
Three–90 minute test, charger off, lamps on
6-Second Hold–Fully reinitializes micro-processor.
Pressing once during any test will cancel/abort testing.
Location of sensor for laser activation
of manual test via handheld remote laser
tester (this is an optional feature, specify
“LX” option)
SELF-TEST / DIAGNOSTIC
CHARGER
BATTERY
LAMPS
CHG-TEST
Xtest Status Indicator Panel
AC/Green Charger/Red Batt/Red Lamp/Red Status/Fault Action
On AC power is on/OK None
FPerforming Test None
On F F F Lamp/Battery Disconnected or Charger Fault Check connections; if ok, replace circuit board
On F Charger fault Replace circuit board
On F Battery disconnected/fault Check connection or replace battery
On F Lamp disconnected/bad or remote disconnected Check connection then press manual test once to
determine bad lamp/replace lamp or check remote lamp.*
Fault Indications:
Four LED indicators provide visible indication of system status:
*If unit has remote capacity and remote cable is connected to charger board but not connected to
a remote load, then either connect remote load or disconnect cable from charger board.
On=Steady F=Flashing Blank=Off
lamp spacing avg. fc. max. fc. min. fc.
CTX6 5.4W tungsten 24ft. 1.0 2.00 0.1
CTX618 9W tungsten 39ft. 1.4 2.70 0.1
Test Numbers:
CTX6 - CSWA
CTX618 - CSWC
© 2016 Philips Lighting Holding B.V. All rights reserved.
Philips reserves the right-make changes in specications
and/or-discontinue any product at any time without notice
or obligation and will not be liable for any consequences
resulting from the use of this publication.
philips.com/luminaires
Philips Lighting North America Corporation
200 Franklin Square Drive, Somerset, NJ 08873
Tel. 855-486-2216
Philips Lighting Canada Ltd.
281 Hillmount Rd, Markham, ON, Canada L6C 2S3
Tel. 800-668-9008
CM-22200 08/16 page 2 of 2