Pilz PNOZ X9 User manual

PNOZ X9
Operating Manual-19526-EN-10
}Safety relays

Preface
This document is the original document.
All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made
for the user's internal purposes. Suggestions and comments for improving this documenta-
tion will be gratefully received.
Source code from third-party manufacturers or open source software has been used for
some components. The relevant licence information is available on the Internet on the Pilz
homepage.
Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®,
SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks
of Pilz GmbH & Co. KG in some countries.
SD means Secure Digital

Contents
Operating Manual PNOZ X9
19526-EN-10 | 3
Introduction ............................................................................................................................4
Validity of documentation.......................................................................................................... 4
Using the documentation .......................................................................................................... 4
Definition of symbols................................................................................................................. 4
Safety ...................................................................................................................................... 5
Intended use ............................................................................................................................. 5
Safety regulations ..................................................................................................................... 5
Safety assessment ................................................................................................................... 5
Use of qualified personnel ........................................................................................................ 6
Warranty and liability ................................................................................................................ 6
Disposal .................................................................................................................................... 6
For your safety.......................................................................................................................... 6
Unit features ...........................................................................................................................7
Safety features ....................................................................................................................... 7
Block diagram/terminal configuration ................................................................................. 8
Function Description ............................................................................................................. 8
Operating modes ...................................................................................................................... 8
Timing diagram ......................................................................................................................... 9
Installation ..............................................................................................................................10
Wiring ......................................................................................................................................10
Preparing for operation ......................................................................................................... 11
Operation ................................................................................................................................14
Status indicators ....................................................................................................................... 14
Faults – Interference .............................................................................................................. 15
Dimensions in mm .................................................................................................................15
Technical details ....................................................................................................................16
Safety characteristic data ......................................................................................................... 22
Supplementary data ..............................................................................................................23
Service life graph ...................................................................................................................... 24
Order reference ......................................................................................................................24
EC declaration of conformity ................................................................................................ 25

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 4
Introduction
Validity of documentation
This documentation is valid for the product PNOZ X9. It is valid until new documentation is
published.
This operating manual explains the function and operation, describes the installation and
provides guidelines on how to connect the product.
Using the documentation
This document is intended for instruction. Only install and commission the product if you
have read and understood this document. The document should be retained for future ref-
erence.
Definition of symbols
Information that is particularly important is identified as follows:
DANGER!
This warning must be heeded! It warns of a hazardous situation that poses
an immediate threat of serious injury and death and indicates preventive
measures that can be taken.
WARNING!
This warning must be heeded! It warns of a hazardous situation that could
lead to serious injury and death and indicates preventive measures that can
be taken.
CAUTION!
This refers to a hazard that can lead to a less serious or minor injury plus
material damage, and also provides information on preventive measures
that can be taken.
NOTICE
This describes a situation in which the product or devices could be dam-
aged and also provides information on preventive measures that can be
taken. It also highlights areas within the text that are of particular import-
ance.

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 5
INFORMATION
This gives advice on applications and provides information on special fea-
tures.
Safety
Intended use
The safety relay PNOZ X9 provides a safety-related interruption of a safety circuit.
The safety relay meets the requirements of EN 60947-5-1 and EN 60204-1 and may be
used in applications with:
}E-STOP pushbuttons
}Safety gates
}Light grids and safety switches with detection of shorts across contacts
The following is deemed improper use in particular
}Any component, technical or electrical modification to the product,
}Use of the product outside the areas described in this manual,
}Use of the product outside the technical details (see Technical details [ 16]).
NOTICE
EMC-compliant electrical installation
The product is designed for use in an industrial environment. The product
may cause interference if installed in other environments. If installed in other
environments, measures should be taken to comply with the applicable
standards and directives for the respective installation site with regard to in-
terference.
Safety regulations
Safety assessment
Before using a device, a safety assessment in accordance with the Machinery Directive is
required.
The product as an individual component fulfils the functional safety requirements in accord-
ance with EN ISO 13849 and EN 62061. However, this does not guarantee the functional
safety of the overall plant/machine. To achieve the relevant safety level of the overall plant/
machine’s required safety functions, each safety function needs to be considered separ-
ately.

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 6
Use of qualified personnel
The products may only be assembled, installed, programmed, commissioned, operated,
maintained and decommissioned by persons who are competent to do so.
A competent person is a qualified and knowledgeable person who, because of their train-
ing, experience and current professional activity, has the specialist knowledge required. To
be able to inspect, assess and operate devices, systems and machines, the person has to
be informed of the state of the art and the applicable national, European and international
laws, directives and standards.
It is the company’s responsibility only to employ personnel who
}Are familiar with the basic regulations concerning health and safety / accident prevention,
}Have read and understood the information provided in the section entitled Safety
}Have a good knowledge of the generic and specialist standards applicable to the specific
application.
Warranty and liability
All claims to warranty and liability will be rendered invalid if
}The product was used contrary to the purpose for which it is intended,
}Damage can be attributed to not having followed the guidelines in the manual,
}Operating personnel are not suitably qualified,
}Any type of modification has been made (e.g. exchanging components on the PCB
boards, soldering work etc.).
Disposal
}In safety-related applications, please comply with the mission time TM in the safety-related
characteristic data.
}When decommissioning, please comply with local regulations regarding the disposal of
electronic devices (e.g. Electrical and Electronic Equipment Act).
For your safety
The unit meets all the necessary conditions for safe operation. However, please note the
following:
}Note for overvoltage category III: If voltages higher than low voltage (>50 VAC or >120
VDC) are present on the unit, connected control elements and sensors must have a rated
insulation voltage of at least 250 V.

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 7
Unit features
}Positive-guided relay outputs:
– 7 safety contacts (N/O), instantaneous
– 2 auxiliary contacts (N/C), instantaneous
}2 semiconductor outputs
}Connection options for:
– E-STOP pushbuttons
– Safety gate limit switches
– Start buttons
– Light grids and safety switches with detection of shorts across contacts
}LED indicator for:
– Supply voltage
– Input state
– Switch state of the safety contacts
– Start circuit
}Semiconductor outputs signal:
– Supply voltage is present
– Switch status of the safety contacts
}See order reference for unit types
Safety features
The safety relay meets the following safety requirements:
}The circuit is redundant with built-in self-monitoring.
}The safety function remains effective in the case of a component failure.
}The correct opening and closing of the safety function relays is tested automatically in
each on-off cycle.

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 8
Block diagram/terminal configuration
A1 A2
B1 B2
S11 S12 S21 S22 S52 S33 S34 S37 23 33 43 53 63 73 81 9113
24 34 44 54 64 74 82 9214Y35Y32Y31Y30Y2Y1
Input Input Input Start
Feed-
back
K1
K2
K3
0 V 24 V
*Insulation between the non-marked area and the relay contacts: Basic insulation (over-
voltage category III), Protective separation (overvoltage category II)
Function Description
The safety relay PNOZ X9 provides a safety-oriented interruption of a safety circuit. When
supply voltage is supplied the "POWER" LED is lit. The unit is ready for operation when the
feedback loop Y1-Y2 and the start circuit S33-S34 are closed. The "START" LED is lit.
}Input circuit is closed (e.g. E-STOP pushbutton not operated):
– The LEDs "CH.1IN" and "CH.2 IN" are lit.
– Safety contacts 13-14, 23-24, 33-34, 43-44, 53-54, 63-64 and 73-74 are closed, the
auxiliary contacts 81-82 and 91-92 are opened. The unit is active.
– A high signal is present at the semiconductor output switch state Y32.
– The LEDs "CH.1 OUT" and "CH.2 OUT" are lit. The "START" LED goes out.
}Input circuit is opened (e.g. E-STOP pushbutton operated):
– The LEDs "CH.1IN" and "CH.2 IN" go out.
– Safety contacts 13-14, 23-24, 33-34, 43-44, 53-54, 63-64 and 73-74 are opened re-
dundantly, the auxiliary contacts 81-82 and 91-92 are closed.
– A low signal is present at the semiconductor output switch state Y32.
– The LEDs "CH.1 OUT" and "CH.2 OUT" go out.
}A high signal is present at semi-conductor output Y35 if the supply voltage is present and
the internal fuse has not blown.
Operating modes
}Single-channel operation: No redundancy in the input circuit, earth faults in the start and
input circuit are detected.
}Dual-channel operation without detection of shorts across contacts: Redundant input cir-
cuit, detects PNOZ X9
– earth faults in the start and input circuit,
– short circuits in the input circuit.

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 9
}Dual-channel operation with detection of shorts across contacts: Redundant input circuit,
PNOZ X9 detects
– earth faults in the start and input circuit,
– short circuits in the input circuit,
– shorts across contacts in the input circuit.
}Automatic start: Unit is active once the input circuit has been closed.
}Manual start: Unit is active once the input circuit and the start circuit are closed.
}Monitored start: Unit is active once
– the input circuit is closed and then the start circuit is closed and opened again.
– the start circuit is closed and then opened again once the input circuit is closed.
}Increase in the number of available contacts by connecting contact expandsion modules
or external contactors/relays.
Timing diagram
Out semi OUT
Out semi ON
[2] [3]
[1]
Legend
}Power: Supply voltage
}Start: Start circuit
}Input: Input circuit
}Output safe: Safety contacts
}Output aux: Auxiliary contacts
}Out semi ON: Semiconductor output supply voltage
}Out semi OUT: Semiconductor output switch state
}[1]: Automatic start
}[2]: Manual start
}[3]: Monitored start
}a: Input circuit closes before start circuit
}b: Start circuit closes before input circuit
}t1: Switch-on delay
}t2: Delay-on de-energisation

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 10
}t3: Recovery time
Installation
}The unit should be installed in a control cabinet with a protection type of at least IP54.
}Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).
}When installed vertically: Secure the unit by using a fixing element (e.g. retaining bracket
or end angle).
Wiring
Please note:
}Information given in the "Technical details [ 16]" must be followed.
}Delivery condition: Link between Y1-Y2 (feedback loop)
}Outputs 13-14, 23-24, 33-34, 43-44, 53-54, 63-64, 73-74 are safety contacts, the outputs
81-82, 91-92 are auxiliary contacts (e.g. for display).
}Do notuse auxiliary contacts 81-82, 91-92 and semiconductor outputs Y32, Y35 for
safety circuits!
}Do not connect undesignated terminals.
}To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details [ 16]).
}Calculation of the max. cable length lmax in the input circuit:
Rlmax
Rl / km
Imax =
Rlmax = max. overall cable resistance (see Technical details [ 16])
Rl/km = cable resistance/km
}Use copper wiring with a temperature stability of 60/75 °C.
}To prevent EMC interferences (particularly common-mode interferences) the measures
described in EN60204-1 must be executed. This includes the separate routing of cables
of the control circuits (input, start and feedback loop) from other cables for energy trans-
mission or the shielding of cables, for example.
}Adequate protection must be provided on all output contacts with capacitive and inductive
loads.
}Do not switch low currents using contacts that have been used previously with high cur-
rents.
}When connecting magnetically operated, reed proximity switches, ensure that the max.
peak inrush current (on the input circuit) does not overload the proximity switch.
}With a 24 VDC supply voltage via terminals B1, B2, the power supply must comply with
the regulations for extra low voltages with safe electrical separation (SELV, PELV).

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 11
Important for detection of shorts across contacts:
As this function for detecting shorts across contacts is not failsafe, it is tested by Pilz during
the final control check. If there is a danger of exceeding the cable runs, we recommend the
following test after the installation of the device:
1. Unit ready for operation (output contacts closed)
2. Short circuit the test terminals S12, S22 for detecting shorts across the inputs.
3. The unit's fuse must be triggered and the output contacts must open. Cable lengths in
the scale of the maximum length can delay the fuse triggering for up to 2 minutes.
4. Reset the fuse: remove the short circuit and switch off the supply voltage for approx. 1
minute.
Preparing for operation
Supply voltage AC DC
A1
A2
L1
N
FE
B1
B2
L+
L-
Input circuit Single-channel Dual-channel
E-STOP
without detection of shorts across
contacts
S1
S22
S21
S11
S52
S12
S1
S11
S12
S52
S22
S21
E-STOP
with detection of shorts across
contacts
S1
S22
S21
S12
S11
S52
S11
Safety gate
without detection of shorts across
contacts
S1
S22
S21
S11
S52
S12
S1 S2
S22
S21
S11
S12
S52
Safety gate
with detection of shorts across
contacts

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 12
Input circuit Single-channel Dual-channel
Light guard or safety switch, de-
tection of shorts across contacts
via ESPE (only when UB: 24 V DC)
B
NOTICE
With single-channel wiring the safety level of your machine/plant may be
lower than the safety level of the unit (see Safety characteristic
data [ 22]).
NOTICE
Operation with a light guard or safety switch
It must not be possible to switch off the supply voltage for the PNOZ X9
separately from the supply voltage for the light guard or safety switch.
Start circuit Single-channel, dual-channel
without detection of shorts
across contacts
Dual-channel with detection of
shorts across contacts
Automatic start
Y1
S37
Y1
S37
Automatic start with start-up test
(safety gate, dual-channel)
Y1
S37 S33
S34
Simultaneity S1 and S2: Max. 150
ms
Manual start
Y1
S37
Y1
S37
Monitored start
S33
S34
S3
S37
Y1
S12
S34
S3
S37
Y1

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 13
NOTICE
In the event of an automatic start or manual start with a bridged start
contact (fault case)
The unit starts up automatically when the safeguard is reset, e.g. when the
E-STOP pushbutton is released. Use external circuit measures to prevent
an unexpected restart.
Feedback loop without feedback loop monitor-
ing
with feedback loop monitoring
Link or contacts from external con-
tactors
Semiconductor output
Y31, Y30: External supply voltage
PLC
PLC
Legend
}S1/S2: E-STOP/safety gate switch
}S3: Reset button
}: Switch operated
}: Gate open
}: Gate closed
INFORMATION
With automatic and manual start, Y1 and S37 must not be linked.

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 14
Operation
When the relay outputs are switched on, the mechanical contact on the relay cannot be
tested automatically. Depending on the operational environment, measures to detect the
non-opening of switching elements may be required under some circumstances.
When the product is used in accordance with the European Machinery Directive, a check
must be carried out to ensure that the safety contacts on the relay outputs open correctly.
Open the safety contacts (switch off output) and start the device again, so that the internal
diagnostics can check that the safety contacts open correctly
}for SIL CL 3/PL e at least 1x per month
}for SIL CL 2/PL d at least 1x per year
NOTICE
The safety function should be checked after initial commissioning and each
time the plant/machine is changed. The safety functions may only be
checked by qualified personnel.
Status indicators
LEDs indicate the status and errors during operation:
LED on
POWER
Supply voltage is present.
START
Start circuit is closed.
CH.1 IN
Channel 1 input circuit is closed.
CH.2 IN
Channel 2 input circuit is closed.
CH.1 OUT
Channel 1 safety contacts are closed.
CH.2 OUT
Channel 2 safety contacts are closed.

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 15
Faults – Interference
}Earth fault: The supply voltage fails and the safety contacts open. Once the cause of the
respective fault has been rectified and the supply voltage is switched off for approx.
1minute, the unit is ready for operation again.
}Contact malfunctions: If the contacts have welded, reactivation will not be possible after
the input circuit has opened.
}LED "POWER" does not light: Short circuit or no supply voltage.
Dimensions in mm
121 (4.76")
75 (2.95")
87 (3.42")
90 (3.54")

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 16
Technical details
General 774605 774606 774609
Certifications
CCC, CE, EAC (Euras-
ian), TÜV, cULus Listed
CCC, CE, EAC (Euras-
ian), TÜV, cULus Listed
CCC, CE, EAC (Euras-
ian), TÜV, cULus Listed
Electrical data 774605 774606 774609
Supply voltage
Voltage 100 - 120 V 200 - 230 V 24 V
Kind AC AC AC
Voltage tolerance -15 %/+10 % -15 %/+10 % -15 %/+10 %
Output of external
power supply (AC) 11 VA 11 VA 11 VA
Frequency range AC 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
Supply voltage
Voltage 24 V 24 V 24 V
Kind DC DC DC
Voltage tolerance -15 %/+10 % -15 %/+10 % -15 %/+10 %
Output of external
power supply (DC) 5,5 W 5,5 W 5,5 W
Residual ripple DC 160 % 160 % 160 %
Duty cycle 100 % 100 % 100 %
Inputs 774605 774606 774609
Number 222
Voltage at
Input circuit DC 24 V 24 V 24 V
Start circuit DC 24 V 24 V 24 V
Feedback loop DC 24 V 24 V 24 V
Current at
Input circuit DC 50 mA 50 mA 50 mA
Start circuit DC 100 mA 100 mA 100 mA
Feedback loop DC 100 mA 100 mA 100 mA
Min. input resistance at
power-on 89 Ohm 89 Ohm 89 Ohm

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 17
Inputs 774605 774606 774609
Max. overall cable resist-
ance Rlmax
Single-channel at UB
DC 45 Ohm 45 Ohm 45 Ohm
Single-channel at UB
AC 45 Ohm 45 Ohm 45 Ohm
Dual-channel without
detection of shorts
across contacts at UB
DC 90 Ohm 90 Ohm 90 Ohm
Dual-channel without
detection of shorts
across contacts at UB
AC 90 Ohm 90 Ohm 90 Ohm
Dual-channel with de-
tection of shorts across
contacts at UB DC 15 Ohm 15 Ohm 15 Ohm
Dual-channel with de-
tection of shorts across
contacts at UB AC 15 Ohm 15 Ohm 15 Ohm
Semiconductor outputs 774605 774606 774609
Number 222
Voltage 24 V 24 V 24 V
Current 20 mA 20 mA 20 mA
External supply voltage 24 V 24 V 24 V
Voltage tolerance -20 %/+20 % -20 %/+20 % -20 %/+20 %
Residual current at "0"
signal 0,1 mA 0,1 mA 0,1 mA
Max. internal voltage drop 4 V 4 V 4 V
Conditional rated short cir-
cuit current 100 A 100 A 100 A
Lowest operating current 0 mA 0 mA 0 mA
Utilisation category in ac-
cordance with EN
60947-1 DC-12 DC-12 DC-12
Relay outputs 774605 774606 774609
Number of output con-
tacts
Safety contacts (N/O),
instantaneous 777
Auxiliary contacts (N/C) 222
Max. short circuit current
IK 1 kA 1 kA 1 kA
Utilisation category
In accordance with the
standard EN 60947-4-1 EN 60947-4-1 EN 60947-4-1

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 18
Relay outputs 774605 774606 774609
Utilisation category of
safety contacts
AC1 at 400 V 400 V 400 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 5 A 5 A 5 A
Max. power 2000 VA 2000 VA 2000 VA
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 8 A 8 A 8 A
Max. power 2000 VA 2000 VA 2000 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 8 A 8 A 8 A
Max. power 200 W 200 W 200 W
Utilisation category of
auxiliary contacts
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 8 A 8 A 8 A
Max. power 2000 VA 2000 VA 2000 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 8 A 8 A 8 A
Max. power 200 W 200 W 200 W
Utilisation category
In accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Utilisation category of
safety contacts
AC15 at 230 V 230 V 230 V
Max. current 5 A 5 A 5 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 7 A 7 A 7 A
Utilisation category of
auxiliary contacts
AC15 at 230 V 230 V 230 V
Max. current 5 A 5 A 5 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 7 A 7 A 7 A
Utilisation category in ac-
cordance with UL
Voltage 240 V AC G. P. 240 V AC G. P. 240 V AC G. P.
With current 8 A 8 A 8 A
Voltage 24 V DC Resistive 24 V DC Resistive 24 V DC Resistive
With current 5 A 5 A 5 A
Pilot Duty B300, R300 B300, R300 B300, R300

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 19
Relay outputs 774605 774606 774609
External contact fuse pro-
tection, safety contacts
In accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Max. melting integral 240 A²s 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A 10 A
Blow-out fuse, slow 6 A 6 A 6 A
Blow-out fuse, gG 10 A 10 A 10 A
Circuit breaker 24V
AC/DC, characteristic
B/C 6 A 6 A 6 A
External contact fuse pro-
tection, auxiliary contacts
Max. melting integral 240 A²s 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A 10 A
Blow-out fuse, slow 6 A 6 A 6 A
Blow-out fuse, gG 10 A 10 A 10 A
Circuit breaker 24 V
AC/DC, characteristic
B/C 6 A 6 A 6 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Conventional thermal
current while loading
several contacts
774605 774606 774609
Ith per contact at UB AC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact 8 A 8 A 8 A
Conv. therm. current
with 2 contacts 5,6 A 5,6 A 5,6 A
Conv. therm. current
with 3 contacts 4,6 A 4,6 A 4,6 A
Conv. therm. current
with 4 contacts 4 A 4 A 4 A
Conv. therm. current
with 5 contacts 3,5 A 3,5 A 3,5 A
Conv. therm. current
with 6 contacts 3,2 A 3,2 A 3,2 A
Conv. therm. current
with 7 contacts 3 A 3 A 3 A

PNOZ X9
Operating Manual PNOZ X9
19526-EN-10 | 20
Conventional thermal
current while loading
several contacts
774605 774606 774609
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact 8 A 8 A 8 A
Conv. therm. current
with 2 contacts 8 A 8 A 8 A
Conv. therm. current
with 3 contacts 8 A 8 A 8 A
Conv. therm. current
with 4 contacts 7 A 7 A 7 A
Conv. therm. current
with 5 contacts 6 A 6 A 6 A
Conv. therm. current
with 6 contacts 5,5 A 5,5 A 5,5 A
Conv. therm. current
with 7 contacts 5 A 5 A 5 A
Times 774605 774606 774609
Switch-on delay
With automatic start
typ. 200 ms 200 ms 200 ms
With automatic start
max. 250 ms 250 ms 250 ms
With automatic start
after power on typ. 220 ms 220 ms 220 ms
With automatic start
after power on max. 300 ms 300 ms 300 ms
With manual start typ. 200 ms 200 ms 200 ms
With manual start max. 250 ms 250 ms 250 ms
With monitored start
typ. 150 ms 150 ms 150 ms
With monitored start
max. 220 ms 220 ms 220 ms
Delay-on de-energisation
With E-STOP typ. 20 ms 20 ms 20 ms
With E-STOP max. 30 ms 30 ms 30 ms
With power failure typ. 170 ms 170 ms 170 ms
With power failure max. 250 ms 250 ms 250 ms
Recovery time at max.
switching frequency 1/s
After E-STOP 50 ms 50 ms 50 ms
After power failure 300 ms 300 ms 300 ms
Min. start pulse duration
with a monitored start 50 ms 50 ms 50 ms
Supply interruption before
de-energisation 35 ms 35 ms 35 ms
Simultaneity, channel 1
and 2 max. 150 ms 150 ms 150 ms
Other manuals for PNOZ X9
2
Table of contents
Other Pilz Relay manuals

Pilz
Pilz PNOZ XV3.1P User manual

Pilz
Pilz S1IM 19540-3FR-04 User manual

Pilz
Pilz PNOZ X10 User manual

Pilz
Pilz PNOZ 16 User manual

Pilz
Pilz PNOZ XV3.1P Owner's manual

Pilz
Pilz PZE X5 User manual

Pilz
Pilz PNOZ mc9p User manual

Pilz
Pilz PNOZ mc5.1p User manual

Pilz
Pilz PSWZ X1P Owner's manual

Pilz
Pilz PNOZ s2 User manual