Reliable H Deluge Riser Maintenance manual

The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model H
Deluge Riser
Assembly
Bulletin 507 Rev. D
Bulletin 507 Rev. D
Instructions for
Installation, Operation,
Care and Maintenance
11
/
2” (40mm) Size
Electric Actuation

2.
General
Model H 1½” (40mm) Deluge Riser incorporates a solenoid
operated diaphragm type valve as the primary valve in deluge,
preaction, or special types of fire protection systems.
The valve is easily reset by external means which eliminates
the need for removing the cover.
The trim is factory assembled for every Model H Deluge Ris-
er. This trim provides valve supervising and waterflow alarm
electric connections, pressure gauges, and system draining
provisions.
Actuation by solenoid enables a full range of electrical detec-
tors to be used for remote sensing.
Operation
Model H 1½” (40mm) Deluge Riser employs a quick opening
hydraulically operated, diaphragm actuated solenoid valve.
De-energized: supply pressure is retained at the solenoid
valve inlet. Flow through the valve is prevented by a plunger
closing off the diaphragm pilot orifice and a diaphragm sealing
against the main orifice.
Energized: the plunger is lifted off the pilot orifice and vents
the pressure behind the diaphragm. The venting creates a
pressure imbalance across the diaphragm, which causes the
diaphragm to open the main orifice allowing flow through the
solenoid valve.
Once the solenoid valve has opened, water flows from the
supply through the Deluge Riser into the piping system and to
the alarm initiating water flow pressure switch.
After system shutdown and draining, the Deluge Riser is eas-
ily reset, without special tools, by first restoring detection devic-
es to the ready condition. Once the detection system is ready,
the releasing control panel can be reset which automatically
resets the solenoid valve. Next, the water supply pressure can
be restored and the Deluge Riser will be reset. The external re-
set feature of the Model H 1½” (40mm) Deluge Riser provides
a means for simple, economical system testing which is one
essential facet of a good maintenance program.
Technical Data
Rated working pressure 175 psi (12,1 bar). Minimum
Supply Pressure: 20 PSI (1,4 Bar)
Note: 1 bar=100 kPa
End connections - American Standard Taper Pipe
Threads per ANSI B2.1. Inlet and outlet 1½”. Drain ¾”.
Color-galvanized pipe and fittings with bronze valves.
Shipping Weight - 52 lbs. (23.3 Kg)
Friction Loss - expressed in equivalent length of Sch. 40
pipe, based on Hazen & Williams formula with C=120 is
29 ft. (8.84m) for the Model H Riser Assembly.
Installation position: Vertical
Listed by Underwriters Laboratories, Inc. special system
water control valves - deluge type (VLFT). Listed by Un-
derwriters’ Laboratory of Canada. NYC MEA 258-93-E.
1.
2.
3.
4.
5.
6.
7.
Figure 1 - Model H Deluge Riser Assembly

3.
Installation
Model H 1½” (40mm) Deluge Riser Assembly is factory as-
sembled as illustrated in Figure 1. The only piping connections
required at the time of installation are an appropriate water sup-
ply connection, the system piping connection and a ¾” NPT
(R¾) drain line connection. Installation is vertical as illustrated.
Electrical connections are required from a releasing control
panel to the solenoid valve, supply water control valve super-
vising switch, and the water flow alarm pressure switch. Refer
to Bulletin 700 for further instructions when making these con-
nections to the Potter PFC-4410-RC Releasing/Control Panel
used with Reliable Special Hazards & Special Systems. Fea-
tures and options available for Electrical Deluge and Preaction
Systems, including fire detection means, are described in Bul-
letin 700.
Resetting Deluge Riser Assembly
Refer to Figures 1 & 2
Close the control valve, Item 1.
Open drain valve, Item 3, and emergency release
station, Item 2, and drain system.
Open all drain valves and vents at low points through-
out the system, closing them when flow of water has
stopped.
Inspect and replace any portion of the detection sys-
tem subjected to fire conditions.
Electric actuation - open the solenoid valve, Item 4, by
operating a detector or an electric manual emergen-
cy station. After residual water has drained through
the solenoid valve, cause it to close by resetting the
detector or manual station; and thereafter, the Re-
leasing/Control Panel. Refer to Bulletin 700, “Special
Hazards & Special Systems” for details.
Close the emergency releasing station, Item 2. Open
slightly the control valve, closing drain valve, Item
3, when water flows from it. Close the control valve
again and observe supply pressure gauge, Item 6, for
any drop in pressure. No pressure drop confirms all
valves are leak tight and the Riser Assembly is prop-
erly set then the control valve, Item 1, is reopened.
Check that the control valve is fully open, and prop-
erly supervised.
Inspection and Testing
Refer to Figures 1 & 2
Water supply - be sure the valve, Item 1, controlling
water supply to the Deluge Riser is open fully and
properly supervised in this position.
Other valves - check that valves, Items 2 , 3 and 37,
are closed and not leaking, by performing Step 6
above.
The automatic drain valve, Item 38, monitors internal
leakage. Push in on its plunger to be sure ball check
is off its seat. If no water appears, the Deluge Riser
Assembly is leak tight.
1.
2.
3.
4.
5.
6.
7.
1.
2.
3.
Operation test - Open the solenoid valve, Item 4, us-
ing the procedure in Step 5 above. Note: Operation
test will cause full flow into the deluge system unless
the control valve is throttled or closed prior to per-
forming this test.
Reset the Riser Assembly (Steps 1-7 above).
Testing Detection System Without Flow Through
Deluge Riser
Close the control valve, Item 1.
Operate detection system - refer to Bulletin 700.
Operation of the detection system must result in a
sudden drop of water pressure indicated on supply
pressure gauge, item 6. When gauge drops to zero,
open drain valve until all water above the control
valve drains away.
Reset detection system - reverse operations per-
formed in Step 2 above. The solenoid valve closes
when the Releasing/Control Panel is reset.
Reset the Riser Assembly (Steps 1-7 above).
Maintenance
Reliable Deluge Riser Assemblies and associated equip-
ment shall periodically be given a thorough inspection and
test. NFPA 25 provides minimum requirements for inspection,
testing and maintenance. The Deluge Riser should be tested,
operated, cleaned and inspected at least annually and parts
replaced as required.
Maintenance Procedures
Refer to Figures 2 & 3
Steady water flow into the system, as evidenced by dripping
at the automatic drain valve, is caused by water leaking past
the solenoid valve or past the emergency station valve. To lo-
cate and correct the trouble, proceed as follows:
Maintenance of Solenoid Valve
Caution: Do not expose plastic or elastomeric ma-
terials to any type of commercial cleaning
fluid. Parts should be cleaned with a mild
soap and water solution.
1.1 Disassemble valve as per the Disassembly
Instructions on page 6. Remove extrane-
ous matter. Clean parts in a mild soap and
water solution.
1.2 Examine surface of the plunger seal and
diaphragm. If damaged, replace plunger
or diaphragm.
1.3 Inspect orifices in the body, cover, and dia-
phragm for nicks or dirt. Clean as neces-
sary. Damage may require a new valve or
replacement parts.
1.4 Examine surfaces of the diaphragm or seal
in contact with the main orifice. Clean if
dirty or replace if damaged or worn.
1.5 Check all springs. If broken, replace.
4.
5.
1.
2.
3.
4.
5.
1.

4.
1½” DELUGE RISER ASSEMBLY, P/N 6503003001 and P/N 6503003007(*), PARTS LIST
ITEM
NO. PART NO. DESCRIPTION Number
REQ’D
1 6201201500 Valve, Butterball, 1½” (BB-SCS02) 1
2 6201001500 Valve, Butterball, 1½” (BB-SC100) 1
3 98840170 Valve, Globe, ¾” 1
4 6871080000 Valve, Solenoid, 2” 1
5 98840160 Valve, Gauge, 3-Way, ¼” 2
6 98248001 Gauge, Pressure, Water 2
7 98543230 Nipple, ½” X 3” Lg. (Galv.) 1
8 96606607 Tee, ½” X ½” X ¼” (Galv.) 1
9 96606601 Tee, ¾” (Galv.) 1
10 96606622 Tee, 1½” X ½” X 1½” (Galv.) 1
11 96606621 Tee, 1½” X ¾” X 1½” (Galv.) 1
12 96606625 Tee, 2” X 1½’ X 1½” (Galv.) 1
13 98543238 Nipple, 2” X Close (Galv.) 1
14 98543275 Nipple, 1½” X 2½” Lg. (Galv.) 1
15 98543274 Nipple, 1½” (thd X grv) X 4” Lg. (Galv.) 2
16 98543276 Nipple, 1½” X 3½” Lg. (Galv.) 2
17 98543288 Nipple, 1½” X 9½” Lg. (Galv.) 1
18 98543290 Nipple, ¾” X 8½” Lg. (Galv.) 1
19 98543279 Nipple, ¾” X Close (Galv.) 5
20 98543212 Nipple, ½” X Close (Galv.) 4
21 98543227 Nipple, ¼” X Close (Galv.) 2
22 95306209 Clamping Ring (OETIKER #515) 2
23 95306210 Clamping Ring (OETIKER #575) 2
24 95106905 Plate, Base 1
25 98543204 Nipple, ½” X 6” Lg. (Galv.) 1
26 94616910 Nameplate, 1½” Deluge System 1
27 94606910 Name Plate, Manual Emergency Station 1
28 6999991339 Switch, Pressure (Eps10-1) 1
6999992366 Switch, Pressure (Epsa10-2)(*)
30 98614403 Plug, ¼” (Galv.) 2
31 98614401 Plug, ¾” (Galv.) 1
32 98750025 Cross, 2” X 1½” (Zinc Coated) 1
33 98085680 Coupling, 1½” Grooved With ¾” npt Outlet 1
35 95200002 Plug, 1½” (Galv.) 1
36 95106904 Plate, Base, Manual Emer. Station 1
37 98840109 Valve, Ball ½” 1
38 78653100 Valve, Ball Drip, Automatic Drain 1
39 75000075 Cup, Priming, ¾” 1
40 98174400 Elbow, ½” Street (Galv.) 2
41 98048022 Bushing, ¾” X ½” (Galv.) 1
42 98048025 Bushing, ¾” X ¼” (Galv.) 1
43 98174402 Elbow, ¾” (Galv.) 1
44 98174401 Elbow, ½” (Galv.) 1
45 98761651 Tee, ½” (Galv.) 2
46 98815200 Union, ½” (Galv.) 1
47 98750005 Cross, ¾” (Galv.) 1
48 98543216 Nipple, ½” X 3½” Lg. (Galv.) 1
49 98543228 Nipple, ½” X 4½” Lg. (Galv.) 1
50 98543209 Nipple, ½” X 2” Lg. (Galv.) 1
51 98840180 Valve, Check, ¾” 1
52 98840181 Valve, Check, ½” 1
53 98085668 Couping, Reducer 2” X 1½” (Galv.) 1
(*) Canadian Type

5.
When difficulty in performance is experienced, contact Reliable Technical Services before any field adjustment is made. Should
replacement parts be needed, use only Reliable supplied parts. When ordering specify part number, name, size, model and serial
number of the unit.
Figure 2

6.
DISASSEMBLY INSTRUCTIONS
WARNING: Depressurize system and turn off electrical
power to the valve before attempting repair.
The valve need not be removed from the line.
To remove the coil assembly:
Unscrew the nut on the top of the coil assembly. The
wave washer and coil assembly can now be removed.
Maximum retightening torque on coil assembly nut is 53
inch-lbs (5.98 N-m).
To disassemble the pressure vessel
(Ref. Figure 3)
Caution: Do not use a pipe wrench directly on the sleeve
tube.
These valves contain a hex style flange in the sleeve as-
sembly. A wrench may be applied directly to the hex
flange in order to loosen the sleeve assembly. Unscrew
the sleeve assembly. The plunger and return spring may
now be removed. Maximum retightening torque is 270
inch-lbs (30.5 N-m).
Unscrew the four (4) cover screws. If the cover cannot
be easily lifted off the body, laterally tap the cover or gen-
tly pry the cover from the body with a screwdriver. Care
must be taken not to damage diaphragm, cover, or body.
Diaphragm return spring(s), diaphragm assembly, and o-
rings can now be removed. Maximum retightening torque
on cover screws is 135 inch-lbs (15.25 N-m).
Replacement Parts: When ordering replacement parts
kit, specify part number (P/N 6999991583). Parts includ-
ed in each kit are marked with an asterisk (*). See ex-
ploded view, Figure 3.
Maintenance of Emergency Station Valve
This valve, Item 2, is not field serviceable. In the
event that leakage is occurring it must by replaced
with a new manual emergency releasing station. Re-
placement is made by removing the coupling, Item
33 and loosening the union, Item 46, and then un-
screwing the segment of piping which begins with
nipple, Item 16, at the inlet to the valve. When order-
ing replacement valve, Item 2, also order two clamp
rings, Item 22, for remounting the nameplate base,
Item 36. Make certain both new clamp rings have
been slipped onto the nipple, Item 16, above the
valve before the new valve is attached to this nipple.
After all piping is reconnected, reposition the name-
plate, as shown, and tighten the new clamp rings
over the two nameplate tabs using crimping pliers to
draw the bands tight.
2.
FIGURE 3
The solenoid valve is manufactured by the Skinner Valve
Division of Parker Hannifin Corp. For more detailed main-
tenance instructions contact The Reliable Literature De-
partment and request Form 10M 7203.

7.
SOLENOID VALVE INSPECTIONS, TESTS AND MAINTENANCE
WARNING: THE OWNER IS RESPONSIBLE FOR MAINTAINING THE FIRE PROTECTION SYSTEM IN PROPER
OPERATING CONDITION. ANY SYSTEM MAINTENANCE OR TESTING THAT INVOLVES PLACING A CONTROL
VALVE OR DETECTION SYSTEM OUT OF SERVICE MAY ELIMINATE THE FIRE PROTECTION OF THAT SYS-
TEM. PRIOR TO PROCEEDING, NOTIFY ALL AUTHORITIES HAVING JURISDICTION. CONSIDERATION SHOULD
BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN THE AFFECTED AREA.
WARNING: PRIOR TO OPERATING THE SOLENOID VALVE, BE SURE TO CLOSE THE SYSTEM CONTROL
VALVE TO AVOID UNINTENTIONAL OPERATION OF THE DELUGE VALVE
Inspections: It is imperative that the system be inspected and tested in accordance with NFPA 25 on a regular
basis. The frequency of the inspections may vary due to contaminated water supplies, corrosive water supplies, or
corrosive atmospheres. In addition, the alarm devices, detection systems, or other connected trim may require a
more frequent schedule. Refer to the system description and applicable codes for minimum requirements.
The valve must be inspected at least monthly for cracks, corrosion, leakage, etc., and cleaned, repaired, or re-
placed, or replaced as necessary.
If leakage is suspected through the solenoid valve, the valve diaphragms and seats should be inspected and if
necessary, repaired or replaced.
WARNING: CLOSE SYSTEM CONTROL VALVE, TURN OFF POWER SUPPLY, AND DEPRESSURIZE VALVE
BEFORE DISASSEMBLING VALVE. IT IS NOT NECESSARY TO REMOVE THE VALVE FROM THE PIPE LINE TO
MAKE INSPECTIONS.
When lubricating valve components, use high grade silicone grease (Dow Corning® 111 Compound Lubricant or
equal).
When reassembling, tighten parts to torque values indicated in the manufacturer’s maintenance instructions
(packed with valve).
After maintenance is completed, operate the valve a few times to be sure of proper operation. A metallic “click”
signifies the solenoid is operating.
All service must be performed by qualified personnel. Upon completion of inspections or replacement of the valve,
the entire system must be checked for proper operation. See appropriate system description and testing instruc-
tions for additional information.
1.
2.
3.
4.
5.
6.
7.

8.
Figure 4 — Model H Deluge System
Ordering Information
Specify (Ref. Figure 4):
Item No. Component Part Mfgr. Description Technical Bulletin
1 Deluge Riser Assembly B Model H 507
2
Releasing / Control Panel
C
Model PFC-4410-RC
Potter #5403550
Reliable 700
Batteries 12 VDC, 12 AMP Hours (90 Hours Backup) FM
12 VDC, 7 AMP Hours (60 Hours Backup)
Optional Accessories
CA2Z (Class A Wiring Module for Initiating Circuits)
CAM (Class A Wiring Module for Indicating Circuits)
ARM-1 / ARM-2 (Auxiliary Relay Module)
RA-4410-RC (Remote Annunciator)
3 Alarm Annunciator A
Model SSM24-8 24 VDC / Polarized Bell
Model SSM24-10 24 VDC / Polarized Bell
Model MA24-D 24 VDC / Polarized Sounder
Model MASS24LO 24 VDC / Polarized Sounder Strobe
Reliable 700
4 Trouble Annunciator A Model SSM24-6 24 VDC / Polarized Bell
Model MA24-D 24 VDC / Polarized Sounder Reliable 700
5 Manual Emergency Station (Elec.) A Model BNG-1 (SPDT) 1 & 2 Area Detection
Model BNG-1F (DPDT) Cross Zoned Detection Reliable 700
6 Detection Various Smoke, Heat Detectors, etc. Reliable 722
7 Sprinklers B Open Type Reliable 104/106
System Equipment Manufacturers
(A) Notifier
(B) The Reliable Automatic Sprinkler Co., Inc.
(C) Potter Electric Signal Company
Patents
U.S. Patent number 5,720,351

9.
Installation Measurements

The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A 12/10 P/N 9999970118
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Automatic sprinklers
Flush automatic sprinklers
Recessed automatic sprinklers
Concealed automatic sprinklers
Adjustable automatic sprinklers
Dry automatic sprinklers
Intermediate level sprinklers
Open sprinklers
Spray nozzles
Alarm valves
Retarding chambers
Dry pipe valves
Accelerators for dry pipe valves
Mechanical sprinkler alarms
Electrical sprinkler alarm switches
Water flow detectors
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Deluge valves
Detector check valves
Check valves
Electrical system
Sprinkler emergency cabinets
Sprinkler wrenches
Sprinkler escutcheons and guards
Inspectors test connections
Sight drains
Ball drips and drum drips
Control valve seals
Air maintenance devices
Air compressors
Pressure gaugesIdentification signs
Fire department connection
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Reliable...For Complete Protection
Table of contents
Other Reliable Industrial Equipment manuals

Reliable
Reliable DDX PrePaK User manual

Reliable
Reliable N2-Blast DDX-LP PrePaK Maintenance manual

Reliable
Reliable 500PS User manual

Reliable
Reliable B1 Maintenance manual

Reliable
Reliable F1FR56 User manual

Reliable
Reliable A-2 Maintenance manual

Reliable
Reliable NS-ASAM Manual

Reliable
Reliable R0029B User manual

Reliable
Reliable N2-Blast DDX Maintenance manual

Reliable
Reliable H PrePak User guide