
Controller Modes
To utilize the buttons on the front of the controller the
unit must be in “S” or “Switch” mode and unlocked. If the
system is displaying “LOCK”, the Mode Select Button may
be pressed and held to unlock the controller (repeat this
step if a system lockout is desired). To change to Switch
Mode, press the Mode Select Button when the controller
is unlocked until the System Mode Indicator displays “S”.
This mode allows access to two features:
• Alarm Simulation (5) – Hold the Alarm Simulation
Button for 3 seconds or press the filter replacement
reset button 3 times within 3 seconds to activate. This
will simulate an alarm condition and trip the alarm dry
contact in the unit for 2 seconds so that proper func-
tioning can be confirmed.
• Filter Change Reset (0) – When a new FRP (Filter Re-
placement Kit) is installed, the 1000- hour filter change
time must be reset. After replacing the filter elements,
press and hold the Filter Change Reset Button for 7
seconds. An audible beep will confirm that the time is
reset and filter alarm will be reset. (Note: this will also
trigger the Customer Alarm Relay for one second)
Normal Run/Standby Mode (run/StdbY)
“Run” mode is when the FPS-900-RS is producing ni-
trogen and supplying it to the storage tank. The system will
automatically enter “Standby” mode when the tank is fully
pressurized (70 PSIG ±5 PSIG). It will remain in “Standby”
mode until the tank pressure falls 7-10 psig.
To run the system in normal run mode:
1. Connect power to the system.
2. Open the nitrogen generator’s 3-way outlet ball
valve to nitrogen-out position.
3. On the nitrogen tank, open the gas inlet valve.
4. Push the On/Off toggle button on the upper right
control panel to the “On” position (up) and the
system will automatically turn on and start filling
the storage tank with nitrogen.
To stop the system:
1. Switch the nitrogen generator’s 3-way outlet ball
valve to the bypass position.
2. System will automatically stop once it reaches the
cut-out pressure of approximately 65-75 PSIG.
3. In the case of an emergency shut off, push the
On/Off toggle button on the upper left control panel to
the “Off” position. The unit will shut down immediately.
Alarm Mode
When an alarm mode is activated, it will trigger the
audible buzzer, alarm contact, and flash the cause of the
alarm on the screen. The customer alarm contact wiring
can be viewed on the supplied wiring diagram. The cus-
tomer alarm dry contact is constantly energized and will
constantly illuminate the LED indicator on top of the con-
tact. This is so when there is no power or power is lost on
the system, the contact will de-energize and show a fault
condition. The alarm contact has a max rating of 6A at
250VAC and 2A at 24VDC.
Bypass Mode (BPASS)
During the 30-minute fire protection piping system fill
test or an issue with the generator is detected, the opera-
tor can switch the system into manual bypass mode by
turning the handle on the 3-way ball valve to the bypass
position. With the handle in the “Bypass Mode”, the by-
pass alarm triggers the audible buzzer, alarm contact,
and flashes “BPASS” on the controller’s 7-segment dis-
play. The alarm will turn off once the handle is back to
normal run position.
BLASTOFF® Alarm Mode (B-Off)
The nitrogen generator activates a BlastOff® Alarm
when it detects potential leaks or nitrogen being overdrawn.
The BlastOff® Alarm will trigger the audible buzzer, alarm
contact, and flash “B-OFF” on the controller’s 7-segment
display. Inspect and test the system for leaks and com-
ponent failures. Power cycle the unit to reset the alarm but
avoid doing this without finding the cause, as it will shorten
the generator’s life. Contact South-Tek System or the local
installer for further troubleshooting.
Low System Pressure Alarm Mode (Lo-n2)
The low system pressure alarm activates when a sys-
tem pressure is detected below the normal functioning
limits of the nitrogen generator. This may be from an is-
sue with the generator, a supply valve being shut off, or
caused by a large leak in the fire protection system.
Power Loss Alarm Mode (-----)
The Power Loss alarm activates when the nitrogen
generator loses power for any reason. This will cause the
alarm contact to trigger.
Filter Replacement Alarm Mode (FILTr)
Once the generator has been running for 1000 hours
or more, the filter replacement alarm will activate. Re-
place the filters according to Section 9 Maintenance. Af-
ter replacing the filter elements, press and hold the Filter
Change Reset Button for 7 seconds. An audible beep
will confirm that the time is reset, and filter alarm will shut
off if it is active. (Note: resetting this will also trigger the
Customer Alarm Relay for one second)
Start-up Procedures
Use caution when working with pressurized gas.
Always leak check every line before using the system.
Note: Line leaks will cause the N2-Blast®FPS-900-RS to
run excessively, shortening its life and possibly causing
excessive wear on the compressor.
1. Visually inspect the unit to ensure no damage oc-
curred during shipping and handling.
2. Check the power connection is correct.
3. Turn the 3-way ball valve on the system output to the
“Bypass” position.
4. Open the inlet ball valve on the nitrogen storage tank
if it is closed.
11.