The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
• Maximum working pressure - 175 psi (12.1 bar).
• Minimum end head pressure - 7 psi (0.5 bar).
• The minimum clearance between the deflec-
tor and the top of storage is 3 ft. (0.92m). For
clearances of 3 ft. (0.92m) up to 4 ft. (1.21m), the
minimum design pressure is 22 psi (1.52 bar).
For clearances of 4 ft. (1.21m) and greater, the
minimum design pressure is established by the
minimum flow requirement (however, the pres-
sure can never be less than 7 psi (0,48 bar)).
• Available temperature ratings are Ordinary, 165
°F (74°C) and Intermediate, 212°F (100°C). Se-
lection of temperature rating is based on the
expected maximum ambient temperature expo-
sure, and in accordance with the applicable de-
sign criteria from NFPA 13. In accordance with
the listing of the sprinkler, the density curves
normally associated with high temperature rated
sprinklers [286°F (141°C)] may be used with ei-
ther the ordinary or intermediate temperature rat-
ing of the N252 EC sprinklers.
• The obstruction criteria in NFPA 13 for Extend-
ed Coverage Pendent Sprinklers shall be used
for the locating and positioning Model N252 EC
sprinklers relative to obstructions.
Design Criteria for FM
The Model N252 EC Pendent sprinkler is FM Approved for
use in accordance with the following guidelines:
• FM Approved for installations governed by data
sheets 2-0 and 8-9.
• The Model N252 EC Pendent is FM Approved
as a K25.2 Extended Coverage Quick Response
Pendent Storage and Non-storage sprinkler.
Maintenance
The Models N252 EC Pendent and Recessed Pendent
Sprinklers should be inspected and the sprinkler system main-
tained in accordance with NFPA 25, and local jurisdictional
requirements. Do not clean sprinklers with soap and water,
ammonia, or any other cleaning fluids or solvents. Remove
dust by gentle vacuuming. Replace any sprinkler that has
been painted (other than factory-applied) or otherwise altered
after leaving the factory. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated sprinklers. Prior to installation, sprinklers should be
maintained in the original cartons and packaging until used
to minimize the potential for damage to sprinkler that would
cause improper operation or non-operation.
Ordering Information
Specify:
1. Sprinkler: Model N252 EC
2. Temperature Rating: [Ordinary, 165°F (74°C)][Inter-
mediate, 212°F (100°C)]
3. Threads: [1” NPT][ISO 7-1R1]
4. Finish: [Brass*][White Polyester][Black Polyester]
[Custom Color Polyester - Specify]
5. Recessed Escutcheon: [None][Model FP - cULus
Listed only]
6. Sprinkler Wrench: [None][Model N - Pendent and
Recessed Pendent][Model N1 - Pendent only]
*Note: Intermediate temperature rated, 212°F (100°C), sprin-
klers in Brass finish are supplied with non-decorative white
paint on the frame arms for identification of the temperature
rating.