The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model RFS42
Residential Flat Concealed
Horizontal Sidewall
Sprinkler (SIN RA4835)
Coverage to 16 ft. x
20 ft. (4.9 mx6.1 m)
Features
1. Flat cover plate (Solid or Perforated) for a flush, concealed
wall finish.
2. 4.2 (60 metric) K-Factor.
3. Sized to fit in a 3
1/2” or larger stud space even when
installed directly in a TorqueSafeTM 90° Sprinkler Head
Elbow** and several other common 1/2” and 3/4” by 1/2”
sprinkler fittings.
4. Push-on/pull-off flat cover plate.
5. Sprinkler shipped complete with factory installed protective
cap.
6. Sprinkler assembly and cover plate packaged separately.
7. 1/8” (3.2 mm) cover plate adjustment.
8. Cover plate available, either solid or perforated, in a wide
variety of colors and finishes.
Listings and Approvals
1. Listed by Underwriters Laboratories Inc. and UL certified for
Canada (cULus).
UL Listing Category
Residential Automatic Sprinklers
UL Guide Number
VKKW
Patents:
U.S. Patent No. 7,353,882, other Patents pending
Product Description
The Reliable Model RFS42 Concealed Residential Extended
Coverage Horizontal Sidewall Sprinkler is an attractive,
concealed sprinkler assembly specially sized to fit within a 3
1/2”
or larger stud space. The sprinkler uses a push-on/pull-off flat
cover plate assembly. The sprinkler assembly is shipped with a
protective cap.
The flat cover plate is attached to the skirt using 135 °F
(57 °C) ordinary temperature classification solder. The sprinkler
is installed into the sprinkler fitting using the Model G6 Sprinkler
Wrench.
When the ambient temperature rises, the solder holding the
cover plate melts, allowing the release of this part and thus
exposing the sprinkler inside to the rising ambient temperature.
This sprinkler is listed for a maximum service pressure of
175 psi (12.0 bar).
Application and Installation
The Model RFS42 sprinkler is intended for installation in
the residential portions of any occupancy in accordance with
NFPA 13, 13R and 13D. The sprinkler is listed as a Concealed
Residential Horizontal Sidewall Sprinkler using a smooth, flat,
horizontal ceiling. System design and installation requirements
for other ceiling configurations are described in NFPA 13, 13R
or 13D, as applicable.
The minimum listed spacing between Model RFS42 sprinklers
is 8 ft (2.4 m).
The low flow RFS42RES sprinklers are specifically engineered
to meet the latest residential sprinkler listing standards (UL 1626
Standard).*
The sprinkler must be installed and properly oriented with the
Model G6 Wrench, as follows:
Do not remove the factory installed plastic protective cap
since it is sized to fit inside the G6 wrench. Note that the
sprinkler can only mate when the sprinkler’s deflector orientation
tab (Fig. 1) is aligned with wrench’s key-way. The G6 wrench
is provided with bubble level pad and TOP marking, to allow
the proper orientation of the horizontal sidewall deflector. Final
leveling can be done after leak proof joint is obtained with a
minimum to maximum torque of 8 to 18 ft-lb (11 to 24 N-m).
Leave the protective cap on to protect the sprinkler while the
wall is plastered, wallpapered or painted. The protective cap
must be removed and the listed cover plate installed prior to
the sprinkler system being placed in service. A 2
5/8” (67 mm)
diameter hole must be cut in the wall for the sprinkler assembly
to extend through.
Concealed cover plate/cup assemblies are listed only for use
with specific sprinklers. The use of any other concealed cover
plate/cup assembly with the Model RFS42 Horizontal Sidewall
Sprinkler or the use of this dedicated concealed cover plate
assembly on any sprinkler with which it is not specifically listed
will void all guarantees, warranties, listings and approvals.
* Effective date 3/14/2008 **Spears Manufacturing Company