Reliable GFR VELO–ECOH Manual

The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model GFR VELO–ECOH
Extended Coverage
Ordinary Hazard
Upright Sprinkler
Bulletin 165 Rev. E
Bulletin 165 Rev. E
Model GFR VELO–ECOH Upright
(SIN R6553) Standard Response
Features
1. Provides Extended Coverage Ordinary
Hazard protection to 400 ft2(37.2m2) per
sprinkler.
2. Very Extra Large Orifice of Nominal K=14.0
(200) results in low pressures.
3. 212°F (100°C) and 165°F (74°C) temperature
rating.
4. Available in brass, chrome, black plated and
polyester coated finishes.
5. Can be used for all editions of NFPA 13.
Listings & Approvals
1. Listed by Underwriters Laboratories, and UL certified
for Canada (cULus)
2. NYC MEA 258-93-E
UL Listing Category
Sprinklers, Automatic and Open Extended Coverage
Sprinklers— Ordinary Hazard Occupancy
UL Guide Number
VNIV
Product Description
The Reliable Model VELO-ECOH Extended Coverage Sprin-
kler has a very extra large orifice, Nominal K=14.0 (200). It can
provide Ordinary Hazard protection to 400 ft2(37.2 m2) at lower
pressures than an XLO which has a K=11.2 (160.2).
The Model GFR VELO-ECOH Sprinklers provide protection in
Ordinary Hazard Group 1 and 2 Occupancies to 400 ft2 (37.2m2)
per sprinkler when the system is designed to NFPA 13 hydraulic
density requirements.
Model GFR VELO-ECOH Upright Sprinklers are to be installed
according to the design criteria shown in this bulletin. The use
of ECOH sprinklers can provide opportunities for lower system
installation costs by requiring fewer sprinklers, less piping and
reduced labor.
Model GFR VELO-ECOH Sprinklers use a levered fusible alloy
solder link.
Model GFR VELO-ECOH Upright
Design Criteria
Reliable Model GFR VELO-ECOH sprinklers are to be used
in systems designed and installed in accordance with NFPA 13
and all other local codes and ordinances. The following design
criteria also apply:
• Minimum sprinkler spacing is 12’ (3.6 m).
• Minimum flow requirement is shown in the Flow Re-
quirements Table on the reverse side.
• ECOH sprinklers are only to be used in systems hy-
draulically designed per NFPA 13, and for a minimum
area of 1,500 ft2(139.4 m2) or 5 sprinklers, whichever
is greater.
• Deflector to commodity clearance shall be a minimum
of 18” (457mm).
• ECOH sprinklers shall be installed in unobstructed
constructions as defined in NFPA 13.
• Sprinklers can be installed under a sloping ceiling not
exceeding 2” (50.8mm) of rise in 12” (305mm).
• Maximum working pressure is 175 psi (12 bar) at the
sprinkler.
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 11/13 P/N 9999970181
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Technical Data
Sprinkler Model Thread
Size
Orifice
Size
Temperature
Rating
Max.
Ambient
Temp.
Maximum
Sprinkler
Spacing
Maximum
Coverage
Area
Approvals
Sprinkler
Identification
Number
(SIN)
°F °C °F °C
GFR VELO–ECOH
Upright (1)
¾” NPT
(R¾)
0.70”
(18mm)
165 74 100 38 20 ft.
(6.1 m)
400 ft.2
(37.2 m2)1,2 R6553
212 100 150 66
(1) Minimum Spacing Between GFR VELO-ECOH Upright Sprinklers is 12 feet (3.6m).
Minimum Flow Requirements
Spacing (1) Coverage
Area
NFPA 13 - 1991 & Later NFPA 13 - 1989 & Earlier
Nominal
K
Factor
Ordinary Hazard 1 Ordinary Hazard 2 Ordinary Hazard 1 Ordinary Hazard 2 Ordinary Hazard 3
0.15 gpm/ft2
(6.1L/min/m2)
Density
0.20 gpm/ft2
(8.1 L/min/m2)
Density
0.16 gpm/ft2
(6.5 L/min/m2)
Density
0.19 gpm/ft2
(7.7 L/min/m2)
Density
0.21 gpm/ft2
(8.25 L/min/m2)
Density
Flow Pressure Flow Pressure Flow Pressure Flow Pressure Flow Pressure
US Metric
gpm
(L/min)
psi
(bar)
gpm
(L/min)
psi
(bar)
gpm
(L/min)
psi
(bar)
gpm
(L/min)
psi
(bar)
gpm
(L/min)
psi
(bar)
20 ft. x 20 ft.
(6.1m x 6.1m)
400 ft.2
(37.2m2)
60.0
(227)
18.4
(1,3)
80.0
(302)
32.7
(2,3)
64.0
(242)
20.9
(1,5)
76.0
(287)
29.5
(2,1)
84.0
(318)
36.0
(2,5) 14 200
(1) For spacing and coverage areas less than 20 ft. x 20 ft. (6.1m x 6.1m) and 400 ft2, the flows and
pressures for the 20 ft. x 20 ft. (6.1m x 6.1m) spacing and 400 ft2(37.2m2) area must be used.
Ordering Information
Specify:
1. Sprinkler Model
2. Temperature Rating
3. Sprinkler Finish
Finishes
Standard Finishes
Bronze
Chrome Plated
(1) Other colors and finishes are available
on special order. Consult factory for
details.
Model H Sprinkler Wrench
Use Model H Wrench for Model GFR VELO–ECOH
Upright Sprinkler removal and installation.
Maintenance
Model GFR VELO-ECOH Upright Extended Coverage
Sprinklers should be inspected and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other clean-
ing fluids. Remove dust by using a soft brush or gentle vac-
uuming. Remove any sprinkler that has been painted (other
than factory applied) or damaged in any way. A stock of
spare sprinklers should be maintained to allow quick re-
placement of damaged or operated sprinklers. Prior to
installation, sprinklers should be maintained in the original
cartons and packaging until used to minimize the potential
for damage to sprinklers that would cause improper opera-
tion or non-operation.
Patents: U.S. Patent No. 6,446,732

Other Reliable Irrigation System manuals

Reliable G4-300 User manual

Reliable

Reliable G4-300 User manual

Reliable DDX PrePaK D Maintenance manual

Reliable

Reliable DDX PrePaK D Maintenance manual

Reliable F3QR80 Series User manual

Reliable

Reliable F3QR80 Series User manual

Reliable F1FR40 Manual

Reliable

Reliable F1FR40 Manual

Reliable HL22 User manual

Reliable

Reliable HL22 User manual

Reliable Sidewall Concealer SWC User manual

Reliable

Reliable Sidewall Concealer SWC User manual

Reliable F1-300 User manual

Reliable

Reliable F1-300 User manual

Reliable H PrePak Maintenance manual

Reliable

Reliable H PrePak Maintenance manual

Reliable A4 User manual

Reliable

Reliable A4 User manual

Reliable N252 User manual

Reliable

Reliable N252 User manual

Reliable F1FR56-300 QREC Series Manual

Reliable

Reliable F1FR56-300 QREC Series Manual

Reliable N25 User manual

Reliable

Reliable N25 User manual

Reliable F1FR Series Manual

Reliable

Reliable F1FR Series Manual

Reliable F1-300 User manual

Reliable

Reliable F1-300 User manual

Reliable G6-56 User manual

Reliable

Reliable G6-56 User manual

Reliable RFS42 Manual

Reliable

Reliable RFS42 Manual

Reliable J112 Pendent Manual

Reliable

Reliable J112 Pendent Manual

Reliable F3QR56 Dry Manual

Reliable

Reliable F3QR56 Dry Manual

Reliable F1FR – 300 User manual

Reliable

Reliable F1FR – 300 User manual

Reliable G5-56 Manual

Reliable

Reliable G5-56 Manual

Reliable JL-14 User manual

Reliable

Reliable JL-14 User manual

Reliable GFR Series User manual

Reliable

Reliable GFR Series User manual

Reliable F3QR80 Dry Pendent Operator's manual

Reliable

Reliable F3QR80 Dry Pendent Operator's manual

Reliable DH56 Dry User manual

Reliable

Reliable DH56 Dry User manual

Popular Irrigation System manuals by other brands

Sime SMART quick start guide

Sime

Sime SMART quick start guide

Tyco Fire Product CENTRAL DS-2 instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL DS-2 instruction manual

Westfalia 92 32 73 Original instructions

Westfalia

Westfalia 92 32 73 Original instructions

Tyco G2 manual

Tyco

Tyco G2 manual

Perrot Hydra M VAC operating manual

Perrot

Perrot Hydra M VAC operating manual

claber 8053 instruction manual

claber

claber 8053 instruction manual

Toro T5 Series quick start guide

Toro

Toro T5 Series quick start guide

ARABLE MARK quick start guide

ARABLE

ARABLE MARK quick start guide

Elgo READY 2 DRIP installation guide

Elgo

Elgo READY 2 DRIP installation guide

Senju Sprinkler RC-QR manual

Senju Sprinkler

Senju Sprinkler RC-QR manual

Tyco TY-B Series quick guide

Tyco

Tyco TY-B Series quick guide

TrimmerPlus LD720 Operator's manual

TrimmerPlus

TrimmerPlus LD720 Operator's manual

Senninger i-Wob UP3 Recommended installation

Senninger

Senninger i-Wob UP3 Recommended installation

Tyco CC2 quick start guide

Tyco

Tyco CC2 quick start guide

General Air Products Vapor Pipe Shield VPS-500A Installation, operation and maintenance manual

General Air Products

General Air Products Vapor Pipe Shield VPS-500A Installation, operation and maintenance manual

Task Force Tips FM Series INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

Task Force Tips

Task Force Tips FM Series INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

Johnson Controls tyco TFP700 manual

Johnson Controls

Johnson Controls tyco TFP700 manual

Cellfast SZ IDEAL 52-061 user manual

Cellfast

Cellfast SZ IDEAL 52-061 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.