rotork YT-3300 Series User manual

SMART POSITIONER PRODUCT MANUAL
YT-3300 / 3350 SERIES (PROFIBUS PA & FOUNDATION FIELDBUS)
VERSION 1.00
YT-3300 (PA/FF)
YT-3350 (PA/FF)
Rotork YTC Limited

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 2
Contents
1Introduction.................................................................................................................................................5
1.1 General Information for the users.........................................................................................................5
1.2 Manufacturer Warranty.........................................................................................................................5
1.3 Explosion Proof Warning (Only for Intrinsic safety type positioners)....................................................6
2Product Description ...................................................................................................................................7
2.1 General.................................................................................................................................................7
2.2 Main Features and Functions ...............................................................................................................7
2.3 Label Description..................................................................................................................................8
2.4 Product Code........................................................................................................................................9
2.4.1 YT-3300 / 3350 (PA/FF) series follows suffix symbols as follows....................................................9
2.5 Product Specification......................................................................................................................... 10
2.6 Certifications...................................................................................................................................... 11
2.7 Parts and Assembly........................................................................................................................... 12
2.8 Product Dimension ............................................................................................................................ 13
2.8.1 YT-3300......................................................................................................................................... 13
2.8.2 YT-3350......................................................................................................................................... 14
3Installation................................................................................................................................................ 15
3.1 Safety................................................................................................................................................. 15
3.2 Tools for installation........................................................................................................................... 15
3.3 Linear positioner Installation.............................................................................................................. 16
3.3.1 Linear positioner Installation of Standard lever type...................................................................... 16
3.3.1.1 Safety..................................................................................................................................... 16
3.3.1.2 Standard lever type positioner Installation Steps .................................................................. 17
3.3.2 Installation of Adapter lever type (on tubeless actuator) ............................................................... 20
3.3.2.1 Safety..................................................................................................................................... 20
3.3.2.2 Adapter lever type positioner Installation Steps .................................................................... 21
3.4 Rotary positioner Installation ............................................................................................................. 23
3.4.1 Components................................................................................................................................... 23
3.4.2 Rotary Bracket Information............................................................................................................ 24
3.4.3 Rotary positioner Installation Steps............................................................................................... 25
4Connection - Air....................................................................................................................................... 27
4.1 Safety................................................................................................................................................. 27
4.2 Supply Pressure Condition................................................................................................................ 27
4.3 Piping Condition................................................................................................................................. 27
4.4 Connection –Piping with actuator..................................................................................................... 28
4.4.1 Single acting actuator .................................................................................................................... 28
4.4.2 Double acting actuator................................................................................................................... 28
5Connection – Power ................................................................................................................................ 29
5.1 Safety................................................................................................................................................. 29

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 3
5.2 Connection......................................................................................................................................... 29
5.3 Ground............................................................................................................................................... 30
6Adjustments ............................................................................................................................................. 31
6.1 A/M switch adjustment....................................................................................................................... 31
6.2 Orifice Installment.............................................................................................................................. 32
7Maintenance ............................................................................................................................................. 33
7.1 Supply air........................................................................................................................................... 33
7.2 Seals.................................................................................................................................................. 33
8Typical connection of YT-3300 with Profibus PA and Foundation Fieldbus...................................... 34
8.1 Profibus PA........................................................................................................................................ 34
8.2 Configurations for high speed solution & low speed solution............................................................ 35
8.3 Foundation Fieldbus .......................................................................................................................... 35
9Auto Calibration and PCB Operation..................................................................................................... 36
9.1 Warning.............................................................................................................................................. 36
9.2 Button Description ............................................................................................................................. 36
9.3 Run Mode (RUN)............................................................................................................................... 36
9.4 Auto Calibration mode (AUTO CAL).................................................................................................. 37
9.4.1 AUTO1 Calibration (AUTO1)......................................................................................................... 37
9.4.2 AUTO2 Calibration (AUTO2)......................................................................................................... 38
9.4.3 AUTO 3 Calibration (AUTO 3)....................................................................................................... 38
9.4.4 AUTO HF Calibration (AUTO HF).................................................................................................. 38
9.5 Manual Mode (MANUAL)................................................................................................................... 39
9.6 Parameter Mode (PARAM)................................................................................................................ 39
9.6.1 Dead-Zone (dEAdZONE, %) ......................................................................................................... 40
9.6.2P Value (KP).................................................................................................................................. 40
9.6.3 I Value (KI)..................................................................................................................................... 41
9.6.4 D Value (Kd) .................................................................................................................................. 41
9.6.5 P_ (KP_), I_(KI_), D_ (Kd_) Values............................................................................................... 41
9.6.6 KF Up Value (KFUP) ..................................................................................................................... 42
9.6.7 KF Down Value (KFdN) ................................................................................................................. 42
9.6.8 Control mode (CTRL) .................................................................................................................... 43
9.7 Hand Calibration Mode (HAND CAL) ................................................................................................ 44
9.7.1 Zero-Point (PV ZERO) and End-Point (PV END) for Valves......................................................... 44
9.8 Valve Mode (VALVE)......................................................................................................................... 45
9.8.1 Acting Adjustment (ACT RA / dA).................................................................................................. 45
9.8.2 Valve flow Characteristic Adjustment (CHAR)............................................................................... 46
9.8.3 User defining flow Characteristics (USER SET)............................................................................ 47
9.8.4 Tight Shut Open (TSHUT OP)....................................................................................................... 49
9.8.5 Tight Shut Close (TSHUT CL) ....................................................................................................... 49
9.8.6 Interpolation Mode (ITP ON/OFF, ITP USER SET)....................................................................... 50

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 4
9.8.7 Acting Type (SINGLE / dOUBLE).................................................................................................. 50
9.8.8 Lever Type (STd / AdT) ................................................................................................................. 51
9.9 Diagnostic (dIAGNO)......................................................................................................................... 52
9.9.1 Diagnosis Limit Configuration (LIMT CFG).................................................................................... 52
9.9.1.1 Deviation (dEV)...................................................................................................................... 53
9.9.1.2 Deviation Time (dEV TIME) ................................................................................................... 53
9.9.1.3 Travel Accumulator Limit (TVLA LMT) ................................................................................... 54
9.9.1.4 Low Limit Alarm (LO ALRM) and High Limit Alarm (HI ALRM) .............................................. 54
9.9.1.5 Low Low Limit Alarm (LL ALRM) and High High Limit Alarm (HH ALRM) ............................. 55
9.9.2 PST Introduction............................................................................................................................ 56
9.9.3 PST Mode (PST)............................................................................................................................ 57
9.9.4 PST Configuration (PST CFG) ...................................................................................................... 57
9.9.4.1 Start Position (START PO) .................................................................................................... 58
9.9.4.2 Target 1 (TARGET 1) ............................................................................................................. 58
9.9.4.3 Target 2 (TARGET 2) ............................................................................................................. 58
9.9.4.4 Interval (INTERVAL) .............................................................................................................. 59
9.9.4.5 Tolerance (TOL) ..................................................................................................................... 59
9.9.4.6 Limit Time (LIMIT TM)............................................................................................................ 59
9.9.4.7 Latency (LATENCY)............................................................................................................... 60
9.9.5 PST Result (PST RSLT)................................................................................................................ 60
9.10 View Mode (VIEW) ............................................................................................................................ 61
10 Warning / Alarm Code ............................................................................................................................. 63
11 Main Software Map .................................................................................................................................. 66

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 5
1 Introduction
1.1 General Information for the users
Thank you for purchasing Rotork YTC Limited products. Each product has been fully inspected after
its production to offer you the highest quality and reliable performance. Please read the product
manual carefully prior to installing and commissioning the product.
➢Installation, commissioning, and maintenance of the product may only be performed by trained
specialist personnel who have been authorized by the plant operator accordingly.
➢The manual should be provided to the end-user.
➢The manual can be altered or revised without any prior notice. Any changes in product’s
specification, design, and/or any components may not be printed immediately but until the
following revision of the manual.
➢When the manual refers to “Valve Zero / Zero” means the final valve position upon pneumatic
pressure has been fully exhausted from positioner’s OUT1 port. For example, the valve zero
position may differ between linear direct and reverse actions. (DA/RA)
➢The manual should not be duplicated or reproduced for any purpose without prior approval from
Rotork YTC Limited, Gimpo-si, South Korea.
➢In case of any other problems that are not stated in this manual, please make immediate contact
to Rotork YTC Limited.
➢Positioner is an accessory of the control valve, so please make sure to read the applicable
instruction manual of the control valve prior to installation and operation.
1.2 Manufacturer Warranty
➢For the safety, it is important to follow the instructions in the manual. Manufacturer will not be
responsible for any damages caused by user’s negligence.
➢Any modifications or repairs to the product may only be performed if expressed in this manual.
Injuries and physical damages caused by customer’s modifying or repairing the product without a
prior consultation with Rotork YTC Limited will not be compensated. If any alterations or
modifications are necessary, please contact Rotork YTC Limited directly.
➢The warranty period of the product is (18) months from the date of shipment unless stated
otherwise. Date of shipment can be checked by providing the LOT NO. or SERIAL NO. to us.
➢Manufacturer warranty will not cover products that have been subjected to abuse, accidents,
alterations, modifications, tampering, negligence, misuse, faulty installation, lack of reasonable
care, repair or service in any way that is not contemplated in the documentation for the product,
or if the model or serial number has been altered, tampered with, defaced or removed; damages
that occurs in shipment, due to act of God, failure due to power surge, or cosmetic damage.
Improper or incorrectly performed maintenance will void this limited warranty.
➢For detailed warranty information, please contact the corresponding local Rotork YTC Limited
office or main office in South Korea.

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 6
1.3 Explosion Proof Warning (Only for Intrinsic safety type positioners)
Please ensure the unit is being used and installed in conformity with local, regional, and national
explosion proof within the proper safety barrier environment.
➢Refer to “2.6 Certifications”
➢Explosion proof type of cables and gaskets should be used, when explosion gases are present at
the installation site.
➢Positioner has 2 ports for power connection. Explosion proof type wires and packing should be
used. Blind plug is required when any port is not being used.
➢Ring terminal with surface area of more than 1.25 mm2 with M4 spring washer should be used to
connect the power.
➢For external ground terminal, ring terminal with surface area of more than 5.5 mm2 should be used.
➢WARNING –EXPLOSION HAZARD –Substitution of components may impair suitability for
Class I, Division 2.
➢“AVERTISSEMENT –RISQUE D'EXPLOSION –Remplacement des composants peut nuire à la
conformité de Classe I, Division 2”
➢EXPLOSION HAZARD. Do not connect or disconnect wiring unless all sources of power have
been removed or the area is known to be non-hazardous.
(French) RISQUE D'EXPLOSION. Ne pas raccorder ou débrancher le câblage à moins Toutes
les sources d'énergie ont été enlevées ou la zone est connue pour être non dangereux.
➢The enclosure of models YT-3300 contains aluminum, which is considered to constitute a
potential risk of ignition when subjected to impact or friction. Care must be used during
installation in locating this equipment to prevent impact or friction
➢Some of the enclosure parts are made of non-metallic materials. To prevent the risk of
Electrostatic sparking, clean the enclosure only with a damp cloth.
➢The product must be installed in such a manner as to minimize the risk of impact or friction with
other metal surfaces.
➢For Intrinsically Safe installations, the product must be connected to suitably rated intrinsically
safe equipment, and must be installed in accordance with applicable intrinsically safe installation
standards.
➢Special conditions for safe use :
The ambient temperature range deviates from the standard temperature range and amounts to:
Equipment must be protected from risk of mechanical impact hazard.
Temperature class T5 / T100 °C: -40 °C to +60 °C
Temperature class T6 / T85 °C: -40 °C to +40 °C

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 7
2 Product Description
2.1 General
YT-3300 / 3350 (PA/FF) series Smart Valve Positioner accurately controls valve stroke in response to
an input signal of Communication from the controller. Built-in micro-processor optimizes the
positioner’s performance and provides unique functions such as Auto-Calibration, Profibus PA or
Foundation fieldbus Protocol Communications.
2.2 Main Features and Functions
➢LCD display enables users to monitor the positioner status.
➢User will easily understand the method of using 4 buttons because it work same in all versions of
firmware interfaces.
➢When unexpected situation like momentary blackout happens, our positioner boot-time only take
0.5 second and this can minimize the travel of valve which consequentially increase the safety of
system.
➢Positioner operates normally even there are sudden changes in supply pressure and / or high
vibration environment.
➢The method of Auto Calibration is very simple.
➢As an advantage of having very low air consumption, It could greatly reduce operating costs in
large-scale plants.
➢It is compatible with most of controllers.
➢Orifices can be installed even in the field to minimize the hunting occurrence and optimize
operating conditions.
➢Different valve characteristics can be adjusted – Linear, Quick Open, Equal Percentage, and User
Set which user can make 5 or 11 points characterizations.
➢Tight Shut – Close and Shut - Open can be set.
➢PID parameters can be adjusted in the field without any additional communicator.
➢A/M switch can be used to direct supply air to the actuator or to manually operate the positioner
or valve without any signal.
➢Operating temperature for positioners is -30 ~ 85 °C or -40 ~ 85 °C (Please check certified
explosion proof temperature)
➢It has IP66 protection grade.
➢Polyester powder coating resists the corrosion process. (except YT-3350).
➢Maintenance of the positioner is easy because of modularized inner structure.
➢SIL2 certified.(For more information, see SIL Safety Instruction on homepage)

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 8
2.3 Label Description
•MODEL : Indicates the model number and additional options.
•INTRINSIC SAFETY / NONINCENDIVE : Indicates intrinsic safety explosion proof grade.
•INGRESS PROTECTION : Indicates enclosure protection grade.
•SUPPLY POWER : Indicates input electric power.
•AMBIENT TEMP. : Indicates the allowable ambient temperature for explosion proof.
•SUPPLY PRESSURE : Indicates the supply pressure range.
•Ui, Ii, Pi, Ci, Li : Indicates the allowable electrical data in the certificate.
ATEX: Ui = 28 V, Ii = 93 mA, Pi = 651 mW, Ci = 0.6 nF, Li = 10 μH
FM: Ui = 28 V, Ii = 93 mA, Pi = 651 mW, Ci = 0.55 nF, Li = 12 μH
You can also see the details in the certificate.
•SERIAL NUMBER : Indicates unique serial number.
•MONTH.YEAR. : Indicates manufactured month and year.
Fig. L-1: YT-3300 PA Intrinsic safety type (ATEX, IECEx)
※Precautions
Be careful not to apply volatile solvent (hardener of instant adhesive, acetone, WD-40, etc.) to the
sticker nameplate. Printed contents may be erased.
Fig. L-2: YT-3300 FF Intrinsic safety type (ATEX, IECEx)

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 9
2.4 Product Code
2.4.1 YT-3300 / 3350 (PA/FF) series follows suffix symbols as follows.
YT-3300 / 3350 1 2 3 4 5 6 7 8
1 Motion Type
L :
R :
Linear (Positioner is attached the right yoke of actuator.)
Rotary
2 Acting type
S :
D :
Single
Double
3 Explosion Proof
N :
i :
Non-Explosion
ATEX, IECEx :
Ex ia IIC T5/T6 Gb, Ex iaD IIIC T100°C/T85°C Db, IP66
4 Lever Type
Linear
0 :
1 :
2 :
3 :
4 :
5 :
6 :
10 ~ 40 mm (Standard type)
20 ~ 100 mm (Standard type)
90 ~ 150 mm (Standard type)
16 ~ 30 mm (Adapter type)
16 ~ 60 mm (Adapter type)
16 ~ 100 mm (Adapter type)
90 ~ 150 mm (Adapter type)
Rotary
1 :
2 :
3 :
4 :
5 :
M6 x 34L
M6 x 63L
M8 x 34L
M8 x 63L
Namur
5 Conduit - Air
Connection Type
1 :
2 :
3 :
4 :
5 :
G 1/2 – Rc 1/4
G 1/2 – 1/4 NPT (YT-3350 is available for No. 2 ONLY)
G 1/2 – G 1/4
M20x1.5P – 1/4 NPT
1/2 NPT – 1/4 NPT
6 Communication
3 :
4 :
Profibus PA
Foundation Fieldbus
7 Option
0 :
None
8 Operating Temp.
(Non-explosion proof) 1)
S :
L :
-30 ~ 85 °C (-22 ~ 185 °F)
-40 ~ 85 °C (-40 ~ 185 °F)
1) This option is just the normal operating temperature of the product and is not related to explosion
proof temperature. See “2.6 Certificates” for explosion proof temperature.

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 10
2.5 Product Specification
Model
YT-3300
YT-3350
Housing Material
Aluminum
Stainless Steel 316
Motion Type
Linear
Rotary
Linear
Rotary
Acting Type
Single / Double
Input Voltage
9 ~ 32 VDC for non-intrinsic safe applications
FISCO barrier 17.5 V
Entity barrier 24 V
(Max Voltage: 32 VDC)
Minimum Current
21 mA
Supply Pressure
0.14 ~ 0.7 MPa (1.4 ~ 7 bar)
Stroke
10 ~ 150 mm
55 ~ 110°
10 ~ 150 mm
55 ~ 110°
Air Connection
Rc 1/4 or 1/4 NPT or G 1/4
1/4 NPT
Gauge Connection
Rc 1/8 or 1/8 NPT
1/8 NPT
Conduit Entry
G 1/2 or 1/2 NPT or M20x1.5P
G 1/2
Ingress Protection
IP66, Type 4X(FM)
Explosion Proof
1. None-explosion proof
2. Intrinsic safety : ATEX, IECEx
※See “2.6 Certificates” for details
Operating
Temperature
Standard Type
-30 ~ 85 °C (-22 ~ 185 °F)
Low Temp. Type
-40 ~ 85 °C (-40 ~ 185 °F)
Ambient Temperature
Of Explosion Proof
T5
-40 ~ 60 °C (-40 ~ 140 °F)
T6
-40 ~ 40 °C (-40 ~ 104 °F)
Linearity
± 0.5 % F.S.
Hysteresis
± 0.5 % F.S.
Sensitivity
± 0.2 % F.S.
Repeatability
± 0.3 % F.S.
Flow Capacity
70 LPM (Sup. = 0.14 MPa)
Air Consumption
Below 2 LPM (Sup. = 0.14 MPa @ idle)
Output Characteristic
Linear, Quick Open, EQ%, User Set
Vibration
No Resonance up to 100 Hz @ 6 G
Humidity
5 ~ 95 % RH @ 40 °C
Protocol
Profibus PA / Foundation Fieldbus
Weight
2 kg (4.4 lb)
5.1 kg (11.2 lb)
Painting
Polyester Powder Coating
-
Tested under ambient temperature of 20 °C, absolute pressure of 760 mmHg, and humidity of 65 %.
Please contact Rotork YTC Limited for detailed testing specification.

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 11
2.6 Certifications
※ All certifications below are posted on Rotork YTC Limited homepage(www.ytc.co.kr).
➢ATEX
Type : Intrinsic safety
Rating : II 2G Ex ia IIC T5/T6 Gb, II 2D Ex ia IIIC T100°C/T85°C Db, IP6X
Certification No. : 19 ATEX 14453 X
Ambient temperature : -40 ~ +60°C (T5), -40 ~ +40°C (T6)
➢IECEx
Type : Intrinsic safety
Rating : Ex II 2G Ex ia IIC T5/T6 Gb, Ex II 2D Ex ia IIIC T100°C/T85°C Db, IP6X
Certification No. : IECEx PRE 19.0031X
Ambient temperature : -40 ~ +60°C (T5/T100°C), -40 ~ +40°C (T6/T85°C)
➢SIL2 (in a redundant structure up to SIL 3)
Intended application : Safety function is defined as to move into fail-safe-position, when
signal to positioner is interrupted.
Certification No. : 968/V 1155.00/20
➢Electromagnetic Compatibility (EMC)
- EMC directive 2014/30/EC from April 2016
- EC Directive for CE conformity marking

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 12
2.7 Parts and Assembly
Fig. 2-1: exploded view
1. Base Cover 8. Pilot Block
2. PCB Cover 9. Base body
3. Main PCB 10. Feedback Lever
4. Torque Motor 11. Auto Manual Switch
5. Main Shaft 12. Gauge Block
6. Potentiometer
7. Pilot

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 13
2.8 Product Dimension
2.8.1 YT-3300
Fig. 2-2: YT-3300L (Standard Lever Type) Fig. 2-3: YT-3300L (Adapter Lever Type)
Fig. 2-4: YT-3300R (Fork lever Type) Fig. 2-5: YT-3300 (Namur Type)

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 14
2.8.2 YT-3350
Fig. 2-6: YT-3350L (Standard Lever Type) Fig. 2-7: YT-3350L (Adapter Lever Type)
Fig. 2-8: YT-3350R (Fork lever Type) Fig. 2-9: YT-3350R (Namur Type)

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 15
3 Installation
3.1 Safety
When installing a positioner, please ensure to read and follow safety instructions.
➢Any input or supply pressures to valve, actuator, and / or to other related devices must be turned
off.
➢Use bypass valve or other supportive equipment to avoid entire system “shut down”.
➢Ensure there is no remaining pressure in the actuator.
➢The positioner has a vent cover to exhaust internal air and drain internal condensation water.
When installing the positioner, make sure the vent cover must be facing downward. Otherwise,
the condensation water could cause damages to PCB.
Fig. 3-1: The correct positions of a vent cover
※Installed in accordance with the National Electrical Code(NEC), ANSI/NFPA 70, or
CEC Part 1 as applicable.(FM approved product)
3.2 Tools for installation
➢Hex key set for hex socket cap bolts
➢(+) & (-) Screw drivers
➢Spanners for hexagonal-head bolts

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 16
3.3 Linear positioner Installation
Linear positioner should be installed on linear motion valves such as globe or gate type which uses
spring return type diaphragm or piston actuators.
3.3.1 Linear positioner Installation of Standard lever type
Fig. 3-2: Installation of standard lever type example
Before proceeding with the installation, ensure following components are available.
➢Positioner
➢Feedback lever and lever spring
➢M6 nut and spring washer (fastening feedback lever to a main shaft)
➢Bracket, bolts and washers for positioner or sensor – not supplied with the positioner
➢Connection bar – not supplied with the positioner
3.3.1.1 Safety
Proper bracket must be made in order to adapt the positioner on the actuator yoke.
Please consider following important points when a bracket is being designed.
➢Positioner’s feedback lever must be vertical to the valve stem at 50 % of the valve stroke.
➢The connection bar of the actuator clamp for the feedback lever should be installed in such a way
that the valve stroke length coincides with the corresponding figure in “mm” marked on the
feedback lever. Improper setting may cause poor linearity

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 17
3.3.1.2 Standard lever type positioner Installation Steps
1) Assemble the positioner or remote sensor with the bracket made in previous step by fastening the
bolts.
Fig. 3-3: Standard Lever Type
2) Attach the positioner (or remote sensor) with the bracket to the actuator yoke
– DO NOT TIGHTEN THE BRACKET COMPLETELY.
3) Connect connection bar to the actuator clamp. The hole gap on the feedback lever is 6.5 mm so
the connection bar’s outer diameter should be less than 6 mm.
4) Connect an air-filter regulator to the actuator temporarily. (Use the auto manual switch to make it
easier to set up. For more information, see 6.1) Supply enough air pressure to the actuator in order
to position the valve stroke at 50 % of the total stroke.
Fig. 3-4: Standard Lever Type

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 18
5) Insert the connection bar between the feedback lever and lever spring. The connection bar must
be located upward from the lever spring as shown below left figure. If it is located downward from
the lever spring as shown below right figure, the connection bar or the lever spring will be worn out
quickly because of excessive strong tension.
Fig. 3-5: Proper way to insert connection bar between feedback lever and lever spring
6) Check if feedback lever is vertical to the valve stem at 50 % of the valve stroke. If it is not vertical,
adjust the bracket or the connection bar to make vertical. Improper installation may cause poor
linearity.
Fig. 3-6: Feedback lever and valve stem

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 19
7) Check the valve stroke. The stroke numbers are engraved on the feedback lever of the positioner.
Position the connection bar at the number on the feedback lever which corresponds with the
desired valve stroke. To adjust, move the bracket, the connection bar or both.
※ The effective linear lever angle of positioner is 60 degree
Stroke : 75 mm
Stroke : 45 mm
Fig. 3-7: Feedback lever and location of the connection bar
8) After installing the positioner, operate the valve from 0 % to 100 % stroke by using direct air to the
actuator. On both 0 % and 100 %, the feedback lever should not touch the lever stopper, which is
located on the backside of the positioner. If the feedback lever touches the stopper, the positioner
should be installed further away from center of the actuator.
Fig. 3-8: Feedback lever should not touch lever stopper on 0 % ~ 100 % valve stroke.
9) After the installation, tighten all of the bolts on the bracket and the connection bar.

Smart Positioner
YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual
Ver. 1.00 20
3.3.2 Installation of Adapter lever type (on tubeless actuator)
Fig. 3-9: Installation of adapter lever type example
Before proceeding with the installation, ensure following components are available.
➢Positioner
➢Feedback lever
➢M6 nut and spring washer (fastening feedback lever to a main shaft of positioner)
➢O-ring(Connect out1 port of positioner and actuator) – not supplied with the unit
➢1/4 plug – not supplied with the unit
➢Adapter holder – not supplied with the unit
➢2 pcs x bolts (M8 x 1.25P) – not supplied with the unit
※When using adapter lever, generally tubeless actuator which doesn’t requires pipe between
actuator and positioner is used. Therefore, in this section, installation method of tubeless actuator
and positioner will be introduced like below.
3.3.2.1 Safety
➢Positioner’s feedback lever must be vertical to the valve stem at 50 % of the valve stroke.
➢Adapter of feedback lever should be installed in such a way that the valve stroke length coincides
with the corresponding figure in “mm” marked on the feedback lever.
Other manuals for YT-3300 Series
2
This manual suits for next models
1
Table of contents
Other rotork Valve Positioner manuals

rotork
rotork YT-2600 Series User manual

rotork
rotork YT-3300 Series User manual

rotork
rotork YT-3302 Series User manual

rotork
rotork YT-1200 Series User manual

rotork
rotork YT-2500 Series User manual

rotork
rotork YT-2700 User manual

rotork
rotork YT-3700 User manual

rotork
rotork TMP-3000 User manual

rotork
rotork YT-3700 User manual

rotork
rotork YT-1000 Series User manual