Hardware Installation and Reference Guide Preparing for Installation
8
the case of accidents.
Make sure that the switch is powered off when you cut off the power supply.
Equip the power supply system with a leakage protector (also referred to as “leakage current switch” or
“leakage current breaker”) to automate the power cut-off in the case of power leakage or shock. When
selecting the leakage protector, observe the following rule:
○The rated leakage action current of each leakage protector is greater than twice of the theoretical
maximum leakage current of all the power supplies in the system.
For example, if a system is equipped with 16 identical power supplies, the leakage current of each power
supply is at most 3.5 mA, and the leakage current of the system totals 56 mA (maximum theoretical
value). A leakage protector with 30 mA rated action current supports less than nine power supplies (that
is, Action current of the leakage protector/2/Maximum leakage current of each power supply = 30/2/3.5
≈ 4.28). In other words, the leakage protector with a rated action current of 30 mA supports up to four
power supplies. In this case, the 16 power supplies in the system require at least four leakage protectors
with a rated action current of 30 mAand each leakage protector supports four power supplies.
If power supplies in a system differ in models, the rated leakage action current of each leakage protector
divided by two is greater than the sum of maximum leakage currents of all the power supplies.
○The rated leakage non-action current of a leakage protector shall be 50% of the leakage action current.
If the non-action current value is too small, the high sensitivity level may cause the circuit to break,
causing power cut-off and service interruption even if the leakage current value is normal.
Take a leakage protector with a rated action current of 30 mA as an example. The rated leakage non-
action current shall be 15 mA. When the leakage current is less than 15mA, the protector shall not act.
Caution
●To guarantee personal safety, the rated leakage action current of each leakage protector in the system
must be equal to or less than 30 mA (human body safety current is 30 mA). When twice of the total
leakage current of the system is greater than 30 mA, the system must be equipped with two or more
leakage protectors.
●The leakage current values vary with products. For the leakage current value of each product model, see
the technical specifications in Section 1.4 Technical Specifications.
2.1.4 Static Electricity
Ensure that the grounding screw on the rear panel of the device is tightened. Ensure that the AC power
socket is a single-phase three-core power socket with protective earthing conductors (PE).
Keep the indoor installation environment clean and free of dust.
Maintain appropriate humidity conditions.
Before installing the various pluggable modules, please wear an anti-static wrist strap and make sure that it is
well grounded.
2.1.5 Laser Safety
The RG-NBS5200 switch supports various types of optical transceivers available in the market, and these
optical transceiver are Class I laser products. Improper use of an optical transceiver may cause damage.
Therefore, pay attention to the following: