S&C TripSaver II Quick guide

June 1, 2021
© S&C Electric Company 2021, all rights reserved Instruction Sheet 461-519
TripSaver®II Cutout-Mounted Recloser
Outdoor Distribution (15.5 kV, 25 kV)
TripSaver®II Communications via Gateway
using the IEC 60870-5-104 Protocol
Installation, Operation, and Conguration
Table of Contents
Section Page Section Page
Introduction
Qualified Persons ........................... 2
Read this Instruction Sheet ................... 2
Retain this Instruction Sheet. . . . . . . . . . . . . . . . . . . 2
Video..................................... 2
Proper Application .......................... 2
Warranty .................................. 2
Safety Information
Understanding Safety-Alert Messages........... 3
Following Safety Instructions .................. 3
Replacement Instructions and Labels ........... 3
Location of Safety Labels ..................... 4
Safety Precautions ......................... 5
Shipping and Handling
Packing ................................... 6
Inspection ................................. 6
Handling .................................. 6
Storage ................................... 6
Returning ................................. 6
Mounting, Powering, and Securing the
Communications Gateway................... 7
Mounting the Communications Gateway to a Pole.. 8
Powering the Communications Gateway ......... 9
Securing the Communications Gateway ......... 9
Installing and Replacing a Radio
Installing a New Radio .......................10
Replacing a Radio ..........................11
Installing and Replacing a Backup Battery
Installing a New Battery ......................12
Replacing a Battery .........................13
Installing Remote Antenna Kits
Installing Remote Antenna Kit 903-002702-02/01 ..14
Installing Remote Antenna Kit 903-002701-01/02 ..15
Installing Remote Antenna Kit 903-002700-02/03 ..15
Installing and Replacing a Local Antenna
Installing Local Antenna 904-002450-02 .........16
Replacing a Local Antenna....................16
Configuring the Communications Gateway
Software User’s Guide .......................17
Enabling IEC 60870-5-104 Communication
Protocol in the Communications Gateway ......19
General Status ............................ 20
Gateway Settings ...........................21
Device Management........................ 37
Tri pSaver ®II Service Center Configuration
Software ................................. 38
Remote Drop Open......................... 40
Gang/Local Operation ...................... 42
User Roles ............................... 46
IEC 104 Setpoints ...........................47
IEC104 Controlling Station ................... 53
IEC104 Controlled Station ................... 53
Security Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Profile ................................... 58
Diagnostics ............................... 58
Commissioning (Pairing) a TripSaver II Recloser
for Use with the Communications Gateway
Service Center Pairing a TripSaver II Recloser
with Firmware Version 1.9 or 1.8 ............ 60
Field Pairing a TripSaver II Recloser with Firmware
Version 1.6 or 1.7 Installed on the Utility Pole
and Powered by Line Current................61
Troubleshooting
Signal Interference ......................... 63
Pairing Process Takes Longer Than Expected ... 63
Quick Installation Checklist ................ 64
Appendix A
Interface Pinouts........................... 65
Power System Diagram ..................... 66
Understanding the Radio Mode ............... 66
Appendix B
Regulatory Information..................... 68

2 S&C Instruction Sheet 461-519
Introduction
Qualified
Persons WARNING
Only qualified persons who are knowledgeable in the installation, operation, and maintenance
of overhead and underground electric distribution equipment, along with all associated hazards,
may install, operate, and maintain the equipment covered by this publication. A qualified person
is someone trained and competent in:
• The skills and techniques necessary to distinguish exposed live parts from nonlive parts of
electrical equipment
• The skills and techniques necessary to determine the proper approach distances corresponding
to the voltages to which the qualified person will be exposed
• The proper use of special precautionary techniques, personal protective equipment, insulated
and shielding materials, and insulated tools for working on or near exposed energized parts
of electrical equipment
These instructions are intended ONLY for such qualified persons. They are not intended to be a
substitute for adequate training and experience in safety procedures for this type of equipment.
Read this
Instruction
Sheet
NOTICE
Thoroughly and carefully read this instruction sheet before installing, operating, or configuring
your TripSaver II Communications via Gateway system. The latest version is available online in
PDF format at sandc.com/en/support/product-literature/. Familiarize yourself with the Safety
Information and Safety Precautions on pages 3 through 5.
Retain this
Instruction
Sheet
This instruction sheet should be available for reference wherever the TripSaver II Communications
via Gateway system is used. Retain this instruction sheet in a location where you can easily retrieve
and refer to it.
Video A video of the how to pair a communications gateway with a TripSaver II Cutout-Mounted Recloser is
available at sandc.com/GatewayPairing-video. The goal of the video is to provide a clear and simple
visual reference. In no way is the video meant as a complete replacement of these written instructions.
Proper
Application WARNING
The equipment in this publication is only intended for a specific application. The application must
be within the ratings furnished for the equipment. Ratings for the TripSaver® II Communications
Gateway are listed in Specification Bulletin 461-33. The ratings are also on the S&C nameplate
affixed inside the product.
The operating temperature range for the communications gateway is -40° C to +50°C (-40°F to +122°F).
Warranty The warranty and/or obligations described in S&C’s standard conditions of sale, as set forth in Price
Sheet 150, plus any special warranty provisions, as set forth in the applicable product-line specica-
tion bulletin, are exclusive. The remedies provided in the former for breach of these warranties shall
constitute the immediate purchaser’s or end user’s exclusive remedy and a fulllment of all the seller’s
liability. In no event shall the seller’s liability to the immediate purchaser or end user exceed the price
of the specic product that gives rise to the immediate purchaser’s or end user’s claim. All other war-
ranties, whether express or implied or arising by operation of law, course of dealing, usage of trade or
otherwise, are excluded. The only warranties are those stated in Price Sheet 150, and THERE ARE NO
EXPRESS OR IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE. ANY EXPRESS WARRANTY OR OTHER OBLIGATION PROVIDED IN PRICE SHEET 150
IS GRANTED ONLY TO THE IMMEDIATE PURCHASER AND END USER, AS DEFINED THEREIN.
OTHER THAN AN END USER, NO REMOTE PURCHASER MAY RELY ON ANY AFFIRMATION OF
FACT OR PROMISE THAT RELATES TO THE GOODS DESCRIBED HEREIN, ANY DESCRIPTION
THAT RELATES TO THE GOODS, OR ANY REMEDIAL PROMISE INCLUDED IN PRICE SHEET 150.

S&C Instruction Sheet 461-519 3
Safety Information
Understanding
Safety-Alert
Messages
Several types of safety-alert messages may appear throughout this instruction sheet and on labels
and tags attached to your TripSaver II Communications Gateway. Familiarize yourself with these
types of messages and the importance of these various signal words:
DANGER
“DANGER” identifies the most serious and immediate hazards that will likely result in serious
personal injury or death if instructions, including recommended precautions, are not followed.
WARNING
“WARNING” identifies hazards or unsafe practices that can result in serious personal injury or
death if instructions, including recommended precautions, are not followed.
CAUTION
“CAUTION” identifies hazards or unsafe practices that can result in minor personal injury if
instructions, including recommended precautions, are not followed.
NOTICE
“NOTICE” identifies important procedures or requirements that can result in product or property
damage if instructions are not followed.
Following
Safety
Instructions
If you do not understand any portion of this instruction sheet and need assistance, contact your
nearest S&C Sales Ofce or S&C Authorized Distributor. Their telephone numbers are listed on
S&C’s website sandc.com, or call the S&C Global Support and Monitoring Center at 1-888-762-1100.
NOTICE
Read this instruction sheet thoroughly and carefully before
installing your TripSaver II Communications via Gateway system.
Replacement
Instructions
and Labels
If additional copies of this instruction sheet are needed, contact your nearest S&C Sales Ofce,
S&C Authorized Distributor, or S&C Headquarters. This instruction sheet can be downloaded from
S&C’s website sandc.com, or call the S&C Global Support and Monitoring Center at 1-888-762-1100.
It is important that any missing, damaged, or faded labels on the equipment be replaced immedi-
ately. Replacement labels are available by contacting your nearest S&C Sales Office, S&C Authorized
Distributor, or S&C Headquarters.

Safety Information
4 S&C Instruction Sheet 461-519
Location of Safety Labels
A
Reorder Information for Safety Labels
Location Safety Alert Message Description Part Number
ACAUTION This control is connected to electrical distribution equipment... 180-000070-00 Rev A
BCAUTION Risk of electric shock... 180-002533-01
CCAUTION Earth Ground 180-002577-01
DCAUTION Enclosure must be grounded... 180-000710-01
B
D
C
C
(Not Shown)

Safety Precautions
S&C Instruction Sheet 461-519 5
DANGER
The TripSaver II Communications via Gateway system connects to a
120/240-Vac source. Failure to observe these precautions will result in serious
personal injury or death.
Some of these precautions may differ from your company’s operating procedures
and rules. Where a discrepancy exists, follow your company’s operating procedures
and rules.
1. QUALIFIED PERSONS. Access to a TripSaver II
Communications via Gateway system must be
restricted only to qualified persons. See the “Qualified
Persons” section on page 2.
2. SAFETY PROCEDURES. Always follow safe
operating procedures and rules.
3. PERSONAL PROTECTIVE EQUIPMENT. Always
use suitable protective equipment, such as rubber
gloves, rubber mats, hard hats, safety glasses, and
flash clothing, in accordance with safe operating
procedures and rules.
4. SAFETY LABELS. Do not remove or obscure any of
the “DANGER,” “WARNING,” “CAUTION,” or
“NOTICE” labels. Remove tags ONLY if instructed to
do so.
5. ENERGIZED COMPONENTS. Always consider all
parts live until de-energized, tested, and grounded.
6. MAINTAINING PROPER CLEARANCE. Always
maintain proper clearance from energized
components.

6 S&C Instruction Sheet 461-519
Shipping and Handling
A complete TripSaver II Communications via Gateway system for a new installation
consists of two shipping containers. They include the following:
• The communications gateway (including radio, if specied “factory-furnished” at
time of order), an optional battery if specied, and mounting hardware for securing
the box to the pole
• (Optional) An ac power cable
Examine the shipment for external evidence of damage as soon after receipt as possible,
preferably before removal from the carrier’s conveyance. Check the bill of lading to make
sure the listed shipping containers are present.
If there is visible loss and/or damage:
1. Notify the delivering carrier immediately.
2. Ask for a carrier inspection.
3. Note the condition of shipment on all copies of the delivery receipt.
4. File a claim with the carrier.
If concealed damage is discovered:
1. Notify the delivering carrier within 15 days of receipt of shipment.
2. Ask for a carrier inspection.
3. File a claim with the carrier.
Also, notify S&C Electric Company in all instances of loss and/or damage.
CAUTION
DO NOT drop the communications gateway or subject any of its parts to undue
stress during installation. Only remove the communications gateway from the
carton when you are ready for installation. The communications gateway weighs
about 20 lbs. (9 kg); follow proper lifting techniques to avoid minor injury.
TripSaver II Communications Gateways are shipped on pallets banded with plastic wrap.
This packaging is designed to protect the communications gateway from freight damage.
This packaging is not suitable for outdoor storage because it can pool water and damage
the communications gateway. After receipt, TripSaver II Communications Gateways
should be stored indoors in their shipping packaging. Storing communications gateways
outdoors in the shipping packaging will void the warranty.
If for any reason the communications gateway is to be returned, place it in the original
shipping carton to prevent damage during shipping. If additional shipping cartons are
required, contact the nearest S&C Sales Ofce, S&C Authorized Distributor, or S&C
Headquarters.
Packing
Inspection
Handling
Storage
Returning

S&C Instruction Sheet 461-519 7
Figure 1. The TripSaverII Communications Gateway.
Gateway
Controller
Module Battery
Module
PS/Battery Board
Antenna
Radio
Ground wire
Ac line fuse
Ac line fuse
Mounting, Powering, and Securing the Communications Gateway

8 S&C Instruction Sheet 461-519
Follow these steps to mount the communications gateway:
STEP 1. Attach the communications gateway in an upright position, with the S&C logo
facing you, to the pole using the upper and lower mounting bolts provided. See
Figure 1 on page 7 and Figure 2.
STEP 2. Connect a #2 copper (or equivalent) ground wire from the base of the
communications gateway to the ground rod.
Mounting
bolt
Ground wire
Padlock
hasp on
latch
Mounting bolt Power
connector
terminal
Figure 2. Mounting the communications gateway to the utility pole.
The communications gateway antenna is directional. The communications gateway
should be mounted ideally no more than 30 feet (9.1 m) below the TripSaver II reclosers
to which it will be paired. There should be an unobstructed line of sight between the
gateway antenna and the LCD screen of each TripSaver II recloser. S&C recommends
mounting the communications gateway directly beneath and on the same side of the pole
as the reclosers to which it will be paired. Do not mount the gateway perpendicular to
the TripSaver II reclosers or on the opposite side of the pole.
Mounting the
Communications
Gateway to a Pole
Mounting, Powering, and Securing the Communications Gateway

S&C Instruction Sheet 461-519 9
Follow these steps to power up the communications gateway:
STEP 1. Remove the red protection cap attached to the power-connection terminal at
the bottom of the communications gateway.
STEP 2. Open the box.
STEP 3. Run the ac power cable down the pole. The unterminated end of the cable
should be connected to the overhead transformer.
Figure 3. The communications gateway control PS/Battery Board.
STEP 4. Align the ve-pin connector at the terminated end with the notch of the power
connection terminal, make the connection, and tighten the ring. See Figure 2
on page 8.
STEP 5. After a short delay, LEDs on the PS/Battery board and the gateway controller
should light up, indicating the communications gateway is receiving power. See
Figure 1 on page 7 and Figure 3.
To secure the communications gateway, close the door and use the door latches to secure
the enclosure. See Figure 2 on page 8. The door latches accept locks with a maximum
shackle diameter of ⅜ -inches (9.5 mm).
Powering the
Communications
Gateway●
Securing the
Communications
Gateway
LED light
on PS/
Battery
Board
Mounting, Powering, and Securing the Communications Gateway
● A user-supplied disconnect switch may be required for your installation between the ac input and the
PS/ Battery board. Contact your nearest S&C Sales Office for details. See the power system diagram
(Figure 71) on page 66.

10 S&C Instruction Sheet 461-519
Installing and Replacing a Radio
A radio providing eld-area network capability for SCADA applications, if specied, is
furnished factory-installed in the communications gateway. Alternately, the customer
may install a user-furnished radio. See Figure 4.
Follow these steps to install a radio in the communications gateway:
STEP 1. Disconnect the ac power cable connected to the bottom of the gateway and then
disconnect the ac-line fuse located at the lower right corner of the gateway box.
STEP 2. Install the radio on the mounting plate using user-furnished hardware.
STEP 3. The wiring harness on most radios includes a power plug and data-port
connectors (Ethernet or RS-232 serial). Insert the power plug in its receptacle.
As applicable, connect the Ethernet connector to Port 2 of the green gateway
controller or insert the serial connector in its receptacle on the gateway
controller.
Figure 4. Installing a radio.
Installing a New Radio
Radio
mounting
plate
Ethernet
Port 1
Ac line fuse
Antenna connector
Ac power cable

S&C Instruction Sheet 461-519 11
Installing and Replacing a Radio
STEP 4. Attach the antenna connector to the user-furnished radio. If using the standard
S&C-provided antenna, the applicable leads are LTE 1 (890- to 960-MHz/1710-
to 2700-MHz bands) and LTE 2 (diversity). If using a remote antenna, use the
leads from the surge-suppressor connector. Refer to the “Installing Remote
Antenna Kits” section on page 14 for further information.
Note: Radios may be pre-programmed or may need to be programmed via a
physical cable or over the air. When programming via a physical cable, if the
radio is already installed in the gateway box, remove the radio-tray assembly
so the cable connection to the radio becomes easier. When programming is
complete, reinstall the radio-tray assembly and replace and securely tighten
the four 8/32-inch bolts.
STEP 5. Replace the ac line fuse located at the lower right corner of the gateway box.
Reconnect the ac cable connector.
Follow these steps to replace a radio in the gateway:
STEP 1. Disconnect the ac power cable connected to the bottom of the gateway and
then disconnect the ac line fuse located at the lower right corner of the gateway
box. See Figure 4 on page 10.
STEP 2. Remove the existing eld-area network radio. See Figure 4 on page 10.
(a) Disconnect the power plug from its receptacle.
(b) As applicable, disconnect the Ethernet connector or the serial connector
from the receptacles on the radio.
(c) Disconnect the antenna connector.
(d) Remove the radio from the mounting plate.
STEP 3. Install the new radio. Follow the procedure outlined in the “Installing a New
Radio” section on page 10.
Note: S&C recommends the new radio be programmed before installation to
match the configuration of the previous radio.
STEP 4. Replace the ac line fuse located at the lower right corner of the gateway box.
Reconnect the ac cable connector.
Replacing a Radio

12 S&C Instruction Sheet 461-519
Installing and Replacing a Backup Battery
A backup battery to support the loss of control power and the Gang Operation
feature, if specied, is furnished factory-installed in the communications gateway. For
customers who initially choose not to have a backup battery, a backup battery system kit
(903-002460-01) can be retrotted to the communications gateway. See Figure 5 and
Figure 6 on page 13.
Follow these steps to install the battery in the communications gateway:
STEP 1. Disconnect the ac power cable connected to the bottom of the gateway and then
disconnect the ac line fuse located at the lower right corner of the gateway box.
STEP 2. Install the battery. The battery kit includes a battery, a top bracket, and
hardware.
(a) The battery should be installed in the lower-middle section of the gateway.
(b) Install the battery using the two spring-loaded screws, with the connector
facing outward on top.
(c) Install the top bracket using the four cap nuts.
2-pin connector
Ac line
fuse
LED
light
on PS/
Battery
board
Spring-
loaded
screw
Figure 5. Disconnect the Ac line fuse and install the battery.
STEP 3. Connect the battery. With the ac line fuse still removed, connect the red and
black battery leads to the white 2-pin connector on the PS/Battery board. The
acrylic safety cover over the PS/Battery board does not need to be removed to
make this connection.
STEP 4. Replace the ac line fuse located at the lower right corner of the gateway box and
leave the ac cable connector disconnected.
STEP 5. Check the LEDs on the green gateway controller. After a short delay, LEDs on
the gateway controller should light up. This conrms the battery is functioning.
STEP 6. Reconnect the ac-cable connector.
Installing a New
Battery

S&C Instruction Sheet 461-519 13
Installing and Replacing a Backup Battery
Follow these steps to replace a battery in the communications gateway:
STEP 1. Disconnect the ac power cable connected to the bottom of the gateway
(See Figure 2 on page 8) and then disconnect the ac line fuse located at the
lower right corner of the gateway box. See Figure 5 on page 12.
STEP 2. Remove the pre-installed battery located in the bottom-middle section of the
enclosure. See Figure 6.
(a) Disconnect the red and black battery leads from white 2-pin connector on
the PS/Battery board. See Figure 5 on page 12.
(b) Unscrew the four cap nuts that hold the battery pack and top bracket in
place.
(c) Loosen the two spring-loaded screws and remove the battery pack from
the enclosure.
STEP 3. Install a new battery. Follow the procedure as outlined in the “Installing a
New Battery” section on page 12.
Figure 6. Battery installation.
Spring-
loaded
screw
Top bracket
Cap nuts (4)
Spring-loaded
screw
Replacing a Battery

14 S&C Instruction Sheet 461-519
Installing Remote Antenna Kits
The 403- to 470-MHz, 2-dBi antenna kit includes an omnidirectional antenna with an
N-male connector, pole mounting and bracket BM-1009, two pieces of shrink tubing,
grounding kits for the LMR-400, and a weather-resistant cable tie. Also available are
40-foot (12.2-m) or 60-foot (18.3-m) coaxial cable-length options.
Follow these steps to install Remote Antenna Kit 903-002702-02/01:
STEP 1. Install the antenna on the antenna bracket with one U-bolt. The white antenna
mast should be above the bracket, with only the brass base clamped in the
bracket.
STEP 2. Attach the antenna bracket to the pole. The pole should not block the line of
sight to other antennas.
STEP 3. Slip the supplied cold-shrink tube over the antenna cable and connect the
end where the shrink tube was applied to the antenna. Tighten nger-tight.
STEP 4. Wrap the cable connector inside the antenna with one piece of vinyl mastic
tape. Don’t stretch excessively, and do not block the antenna drain holes.
See Figure 7.
STEP 5. Apply the second piece of tape overlapping the end of the rst piece and tightly
cover the cable end of the connector.
STEP 6. Align the end of the cold-shrink tube ush with the bottom of the antenna and
shrink it over the tape and cable.
STEP 7. Tie-wrap the cable to the antenna bracket. Loop and secure any excess antenna
cable near the pole. Use of a U-guard is recommended to protect the cables.
Do not use staples. See Figure 8.
STEP 8. Slip a cold-shrink tube over the control end of the antenna cable and connect
the cable to the surge suppressor at the bottom of communications gateway
box. Waterproof this connector to industry standards.
Installing Remote
Antenna Kit
903-002702-02/01
Figure 7. Do not block antenna drain holes.
Antenna
U-guard
Figure 8. The remote antenna.
Waterproof antenna connector

S&C Instruction Sheet 461-519 15
Installing Remote Antenna Kits
The 890- to 960-MHz, 10-dBi antenna includes an omnidirectional Yagi antenna, a
pole-mounted single antenna arm with 30-foot (9.1-m) or 50-foot (15.2-m) coaxial cable,
and N-type male connectors on both ends. The customer must provide 1.375-inch (35-mm)
OD pipe for the antenna.
Follow these steps to install Remote Antenna Kit 903-002701-01/02:
STEP 1. Install the antenna on the antenna bracket.
STEP 2. Attach the antenna bracket to the pole to the specied azimuth, per the network
design. The pole should not block the line of sight to other antennas.
STEP 3. Slip the supplied cold-shrink tube over the antenna cable and connect the
end where the shrink tube was applied to the antenna. Tighten nger-tight.
STEP 4. Wrap the cable connector inside the antenna with one piece of vinyl mastic
tape. Don’t stretch excessively, and do not block the antenna drain holes.
STEP 5. Apply the second piece of tape overlapping the end of the rst piece and tightly
cover the cable end of the connector.
STEP 6. Align the end of the cold-shrink tube ush with the bottom of the antenna and
shrink it over the tape and cable.
STEP 7. Tie-wrap the cable to the antenna bracket. Loop and secure any excess antenna
cable near the pole. Use of a U-guard is recommended to protect the cables.
Do not use staples.
STEP 8. Slip a cold-shrink tube over the control end of the antenna cable and connect
the cable to the surge suppressor at the bottom of communications gateway
box. Waterproof this connector to industry standards.
The 902- to 928-MHz, 3-dBi antenna includes an omnidirectional berglass antenna, a
pole-mounted single antenna arm with 30-foot (9.1-m) or 50-foot (15.2-m) coaxial cable
and N-type male connectors on both ends.
Follow these steps to install Remote Antenna Kit 903-002700-02/03:
STEP 1. Install the antenna on the antenna bracket with one U-bolt.
STEP 2. Attach the antenna bracket to the pole. The pole should not block the line of
sight to other antennas.
STEP 3. Slip the supplied cold-shrink tube over the antenna cable and connect the
end where the shrink tube was applied to the antenna. Tighten nger-tight.
STEP 4. Wrap the cable connector inside the antenna with one piece of vinyl mastic
tape. Don’t stretch excessively, and do not block the antenna drain holes.
STEP 5. Apply the second piece of tape overlapping the end of the rst piece and tightly
cover the cable end of the connector.
STEP 6. Align the end of the cold-shrink tube ush with the bottom of the antenna and
shrink it over the tape and cable.
STEP 7. Tie-wrap the cable to the antenna bracket. Loop and secure any excess antenna
cable near the pole. Use of a U-guard is recommended to protect the cables.
Do not use staples.
STEP 8. Slip a cold-shrink tube over the control end of the antenna cable and connect
the cable to the surge suppressor at the bottom of communications gateway
box. Waterproof this connector to industry standards.
Installing Remote
Antenna Kit
903-002701-01/02
Installing Remote
Antenna Kit
903-002700-02/03

16 S&C Instruction Sheet 461-519
Installing and Replacing a Local Antenna
The 403- to 470-MHz, 2-dBi antenna includes an omnidirectional antenna with an N-type
male connector.
STEP 1. Remove the protection cap attached to the antenna connector terminal at the
bottom of the communications gateway box.
STEP 2. Screw in the antenna to the N-type female connector.
STEP 3. Waterproof the connector to industry standards.
STEP 1. Visually inspect the antenna for damage (bent, not vertical).
STEP 2. If it needs to be replaced, remove any waterproong material around the
connector.
STEP 3. Unscrew the antenna.
STEP 4. Check to ensure the connector channel is clear.
STEP 5. Follow the procedure outlined in the previous “Installing Local Antenna”
section.
Installing Local
Antenna
904-002450-02
Replacing a Local
Antenna

S&C Instruction Sheet 461-519 17
Conguring the Communications Gateway
Logging on to the Communications Gateway
The communications gateway is accessed via a Web browser interface. Connect a personal
computer (PC) with a CAT5 Ethernet cable to the communications gateway’s Ethernet Port
1. See Figure 4 on page 10. The default conguration of the communications gateway’s IP
gateway is 192.168.1.1 with DHCP set as “On.” To join the communications gateway network,
set the PC’s network address to “Obtain an IP Address Automatically” and “Obtain DNS
Server Address Automatically” under the PC’s LAN address settings to enable a network
connection to the communications gateway. Alternately, a static IP address within the
192.168.1.x network may be used. See Figure 9.
Note: To remove Windows routing conflicts, S&C recommends turning the PC’s Wi-Fi
radio off.
Figure 9. Setting a static IP address on the PC to connect to the communications gateway.
After allowing approximately 3 minutes for the gateway to boot, a confirmation the PC
has successfully joined the communications gateway network may be observed by launching
an MSDOS command window and running ‘ipconfig /all’ at the command prompt. An output
showing all the IP interfaces for the host system will be displayed. Identify the Ethernet
interface that has the cabled connection to communications gateway Ethernet Port 1 and
examine the output for that interface. Screen information for the interface supporting a
successful connection when using DHCP will resemble what’s shown in Figure 10.
Figure 10. A successful ipconfig/all reply from the Command prompt.
Software User’s
Guide

18 S&C Instruction Sheet 461-519
Conguring the Communications Gateway
Note: If the interface indicates “media disconnected,” this is an indication the Ethernet
connection between the host PC and the communications gateway is not functional,
and it should be investigated.
NOTICE
Because the end user can change the IP address range, or even disable DHCP
completely and change the communications gateway to a static IP, it is important
to make a note of any IP settings changes. When relocating or setting up a
communications gateway that has had its IP settings changed, look for the IP setting
configured by your service or IT department when running ipconfig/all from the
MSDOS command line.
With the CAT5 Ethernet cable attached to communications gateway’s Ethernet
Port 1, launch a Web browser on the PC. Type 192.168.1.1 in the browser’s address line.
(Browsers supported include Google Chrome, Internet Explorer, and Microsoft Edge.)
The Communications Gateway Login screen will open with a username and password
challenge. See Figure 11.
Note: The default username and password can be requested from S&C by calling the
Global Support and Monitoring Center at 888-762-1100 or by contacting S&C through
the S&C Customer Portal at sandc.com/en/support/sc-customer-portal/.
Figure 11. The Communications Gateway Login screen.
NOTICE
With communications gateway firmware version 3.1 and later, the default password
for the Admin user must be changed before proceeding. See Figure 12 on page 18.
The new non-default password must be at least eight characters with at least one
uppercase and one lowercase character. Numbers and special characters are also
allowed but not required. <Space>, <Tab>, and <&> characters are not allowed.
Do not lose this password. There is no way to recover a lost password in the field.
A lost password will require returning the gateway controller module to S&C for
re-initialization.

S&C Instruction Sheet 461-519 19
Conguring the Communications Gateway
Figure 12. The Profile screen for changing the default password.
After a successful login, the browser will open to the communications gateway
General Status screen with an application Navigation menu on the left side of the screen.
The Navigation menu will remain visible for all subordinate menu interface screens.
See Figure 14 on page 20.
The communications gateway is shipped congured to use the DNP3 communication
protocol by default. Before starting to congure the communications gateway, S&C
recommends rst switching to the IEC 60870-5-104 or “IEC104” protocol. To switch to
the IEC104 protocol:
STEP 1. Select “Gateway Settings” from the Navigation menu.
STEP 2. Scroll down to the SCADA Protocol panel. Click on the IEC104 radio button.
See Figure 13.
STEP 3. Scroll up to the top of the screen and click the Save button.
Figure 13. The IEC104 Protocol panel and Save button.
Enabling IEC
60870-5-104
Communication
Protocol in the
Communications
Gateway

20 S&C Instruction Sheet 461-519
Conguring the Communications Gateway
A success message will display, and the IEC104 Setpoints, IEC104 Controlling
Station, and IEC104 Controlled Station menu items will show on the menu bar.
See Figure 14.
Figure 14. IEC104 Enabled.
NOTICE
Simultaneous access to the Web-user interface by multiple users is not officially
supported. If it is desired to have multiple users logged in simultaneously, S&C strongly
recommends only one of those users be assigned the Admin role. S&C also strongly
recommends only one of those users modify settings on the gateway. The other
users should be performing read-only activities. Also, if two users are sharing a single
username and the users attempt to log in at the same time, the older session will be
silently logged out.
The purpose of the General Status screen is informational and for display only. No edits are
allowed. Field edits will be permissible under respective menu sections where each eld’s
purpose is dened.
The General Status screen is comprised of the “Gateway Identity,” “GPS,” “Gateway LAN,”
“Gateway WAN,” “Gateway Hardware,” and “SCADA Communication” panels. The “Gateway
Identity” panel contains five fields: Gateway Name, Gateway Serial #, Gateway Software
Version, Gateway App Version, and Gateway Platform Version. The “GPS” panel contains
five fields: Status, Time Since Last GPS Fix, Location, Satellites (In Use), and System
Time. The “Gateway LAN” and “Gateway WAN” panels contain three fields each: Link
Status, IP Address, and Netmask. The “Gateway Hardware” panel contains four fields:
Battery Present, Battery Health, Battery Voltage (Volts), and Door Status. The “SCADA
Communication” panel contains the IEC 104 Communication Status field. See Figure 15.
Figure 15. The General Status screen.
General Status
Other manuals for TripSaver II
12
Table of contents
Other S&C Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Bend-Tech
Bend-Tech Dragon A400 Start-Up and Training Manual

HARVEY
HARVEY Eagle E-305S instruction manual

schmersal
schmersal AZM300B-I1-ST-1P2P-T Instructions for operation

Index
Index G220 Operating instructions and Maintenance instructions

LEGRAND
LEGRAND DMX3 Maintenance Guide

PASCO
PASCO PS-2978 Product guide