Instructions for Use - SCHMIDT®Flow Sensor SS 20.515 LED Page 5
Mounting sequence
For the assembly of the SCHMIDT®Flow Sensor SS 20.515 LED, five
different assembly versions optimized for use in cleanrooms are available,
in order to cover all the different applications (see Table 1).
First, the required holes, depending on the assembly version, must be
drilled, and the corresponding fixing socket must be mounted in that hole.
Then the connecting cable is introduced with its open into the fixing socket
from the cleanroom side until the cable bushing protrudes from the fixture
by only about 5 cm. Please note that after assembling the sensor, there
must still be room for this protruding cable length in the void behind the
assembly bushing. Now connect the sensor to the connecting cable (plug
in and screw down spigot nut), insert it into the fixture bushing and tighten
the holding fixture screw by hand. Now the sensor can still be aligned ac-
curately by hand, if required. Finally, the holding fixture screw must be
tightened with a key wrench (wrench size 22) until the sensor is sufficiently
secured against twisting.
Prior to commissioning the sensor, remove the protective cap.
Mounting beneath a ceiling
The angled sensor is designed for mounting beneath a ceiling.
After screwing the sensor into the ceiling sleeve, its tip is automatically in
the correct position to measure a vertical downdraft flow from the filter
outlet. Only the torsional angle of the sensor arm in parallel to the ceiling
must still be aligned. Then tighten assembly screw using the key wrench
until the sensor is secured against twisting (hold sensor, if necessary).
Mounting at a wall
The straight sensor is designed for assembly at a wall.
Insert sensor into the fixture bushing and thoroughly tighten the assembly
screw. No alignment to the flow is required, due to the omnidirectional
measurement characteristic of the sensor head.