
After setting the required MST number, the setting is confirmed with key 6.
After this input, the settings are saved and all LCD segments are illuminated for
approximately 4 seconds. This allows you to check that all the available LCD display
characters are still operating correctly.
The temperature sensor connected to the room operator unit HTC3.1/A, or the
HTC3.1S/A room operator unit with the built-in temperature sensor must be installed in
a suitable location for measurement of the room temperature.
Mounting location
The HTC3.1/A room operator unit, which does not have a built-in temperature sensor,
is not restricted in this way. A suitable temperature sensor for this unit is the HSE1.1
cable temperature sensor. If the VIMAR idea installation system is used, the room
temperature sensor HSE1.2 is also suitable.
STOP Caution •Do not connect an external room sensor to the HTC3.1S/A room operator unit.
•Heat sources result in false temperature measurements. Ensure a minimum distance
of 1.5 m from lamps.
If the sensor is in an unsuitable location, the measured value can be corrected with a
temperature offset. The correction can be undertaken with the SCOPE or HSC (Hotel
Solution Commissioning) tool.
Correcting the
measured value
In the standard application the basic setting for the temperature offset is –4 K. This
applies to the HTC3.1S/A room operator unit with the built-in sensor.
For the HTC3.1/A room operator unit with an external type HSE1.2 sensor, a
temperature offset of –1 K must be set.
Mounting
•The HTC3.1/A or HTC3.1S/A should be mounted at eye level in the living area of the
hotel room.
•Lamps and other heat sources in the vicinity of the room temperature sensor must
not be allowed to distort the measured temperature. The room operator unit with the
built-in temperature sensor is not suitable for mounting within reach of the bed, for
example, because items such as bedside lamps cause to0 great an increase in the
measured temperature.
•Conduits must be sealed where they enter wall boxes, so that the temperature is not
falsified by draughts.
•First press the room operator unit into the base frame and remove the protective
transparent film from the display window. There is no access to the protective film on
the display window once the front-plate label is in position. Only then should you
attach the adhesive front-plate label. It is important to follow this sequence, because
if the front-plate label is fitted first, it is then difficult to press the unit into the base
frame.
•To remove the unit, it must be unscrewed from the wall together with the base frame.
•The screw terminals of the room operator unit can accommodate only one wire with
a maximum diameter of 1 mm. When connecting the bus, therefore, we recommend
that the room operator unit should be connected as the last room-bus device.
•The device is designed for fixed installation in a dry, enclosed space.
•For installation in a 4-module mounting box, depth 50 mm
•Mount horizontally only, with the front plate vertical
•Do not install AC 230 V devices in the same mounting box
•Commissioning must be carried out by trained personnel only
•Do not open the unit
•Local safety and installation regulations must be observed
5/8
Siemens HTC3.1/A, HTC3.1S/A – Room operator units CM2N6319en
Building Technologies 31.07.2008