manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Control Unit
  8. •
  9. Siemens HOTEL SOLUTION HTC3.1/A User manual

Siemens HOTEL SOLUTION HTC3.1/A User manual

6319
HOTEL SOLUTION™
Room operator unit
Room operator unit with
built-in sensor
HTC3.1/A
HTC3.1S/A
Room unit for operation of the individual room control system in hotel rooms
•Displays room temperature setpoint and setpoint adjustment
•Individual setpoint adjustment with "plus" and "minus" membrane switches
•Individual manual fan-speed selection for fan control (up to 3 speeds)
•Membrane switch for selection of "Auto" mode
•Room temperature detected with connected temperature sensor
•Room temperature detected with built-in temperature sensor (HTC3.1S/A)
Application
The HTC3.1A and HTC3.1S/A room operator units are used in conjunction with a
HRC3.. room controller. The room operator unit detects the temperature and trans-
mits it to the HRC3.. room controller for room temperature control.
The room operator unit indicates the operating mode in the hotel room and can be
used to operate the fan coil unit, either manually or automatically via the connected
room controller.
CM2N6319en
31.07.2008 Building Technologies
Functions
The HTR3.1/A or HTR3.1S/A room operator unit communicates with the HRC3.. room
controller via a serial port, performing the following functions:
•Displays the room temperature setpoint
•Transmits the manual room temperature setpoint adjustment
•Displays the manual room temperature setpoint adjustment
•Transmits the manually set fan speed
•Displays the manual or automatic fan speed
•Transmits the "Auto" operating mode signal for automatic selection of the fan speed
•Detects and transmits the room temperature with an externally connected 10kΩNTC
room temperature sensor (HTC3.1/A only)
•Detects and transmits the room temperature with a built-in 10kΩNTC room
temperature sensor (HTC3.1S/A only)
Types
HTC3.1/A Room operator unit
HTC3.1/SA Room operator unit with built-in sensor
Ordering
When ordering, please specify the quantity, product name and type code:
30 Room operator units HTC3.1/A
Example
Compatibility
See assortment overview, N6301.
Mechanical design
The room operator unit comprises:
•Printed circuit board with the electronic circuit, LCD display, membrane switches for
operation and terminal block
•Front plate
•Operator panel
The components are snap-mounted in the front-plate unit. The operator panel label has
an adhesive strip on the back. After removal of the protective transparent film from the
display window, and of the backing paper from the adhesive operator panel label, the
latter can be affixed to the front plate.
Unlike the HTC3.1/A, the HTC3.1S/A room operator unit has a built-in temperature
sensor.
2/8
Siemens HTC3.1/A, HTC3.1S/A – Room operator units CM2N6319en
Building Technologies 31.07.2008
Operator controls, connectors and display
6319Z01
20.5 °C
1 2 3
1a
1b
1c
8
Auto
7 6 5 4
654321
Front view Rear view
1 LCD panel
Key 1a Setpoint adjustment indicator (bar)
1b Temperature setpoint display (digits)
1c Fan status display
= Off
= Speed 1
= Speed 2
= Speed 3
2 Membrane switch for reducing predefined setpoint in steps of 0.5 or 1.0 K
3 Membrane switch for increasing predefined setpoint in steps of 0.5 or 1.0 K
4 Membrane switch for switching to "Auto" mode
5 Membrane switch for gradually increasing fan speed
6 Membrane switch for gradually decreasing fan speed
7 Membrane switch for switching to "Fan OFF" mode
8 Terminal block
The guest can use the room operator unit to do the following:
•Adjust the preset room temperature setpoint by ±2 or by ±4 K in eight steps. The
step size of 0.5 or 1.0 K can be configured in the room controller. The eight
temperature-change increments are indicated by eight bars across the top of the
LCD display panel.
•Enable fan speeds 1, 2 and 3 manually
•Change from manual to automatic mode ("Auto")
Switching to "Auto" causes the fan speed to be set automatically by the controller
(Speed 1,2 or 3). The fan status is indicated by symbols across the bottom of the LCD
display panel.
The temperature setpoint valid for the room is displayed in digits on the LCD display
panel. Throughout the period for which the guest is checked in, the individual setpoint-
setting remains valid. It cannot be overwritten by the hotel service staff.
When the guest leaves the room (removing the access card from the card holder) the
system switches automatically to "Auto", and the "Pre-comfort" room operating mode
with the energy-saving function (widening of the deadband) comes into effect. When
the guest returns to the room, the "Auto" mode remains active and the "Comfort" room
operating mode, with the guest's personally selected setpoint adjustment, is restored.
In conjunction with the HOTEL SOLUTION system, the room temperature setpoints
preset for a given room are automatically re-instated when the guest checks out.
3/8
Siemens HTC3.1/A, HTC3.1S/A – Room operator units CM2N6319en
Building Technologies 31.07.2008
Engineering notes
Base frame The room operator unit is designed for flush mounting or cavity-wall mounting in
conjunction with base-frames and cover plates from various manufacturers:
−SIEMENS-DELTA futura
−VIMAR idea
−Bticino Classic
−GEWISS Playbus
−AVE Systema 45
Up to 5 room operator units may be connected to one room controller.
The maximum permitted current associated with the supply voltage from the HRC3..
room controller must not be exceeded.
For further information, see data sheets N6313 and N6314.
The room temperature control algorithm is not in the room operator unit itself, but in the
controller application. To enable the room controller to communicate with the room
operator unit, the latter must be assigned with an address.
A
ddressing
The addresses of the room operator units are defined by their ID number, and the
temperature measurement function is enabled by setting the MST flag. The factory
settings are always ID = 1 and MST = 0.
In a control loop with several room operator units, the temperature is measured in one
device only (the master). The MST flag (MST = 0) determines whether the room
operator unit should measure the temperature, or whether it is a slave device
(MST = 1), in which case the temperature sensor is disabled.
−First room operator unit ID=1 MST=0 Master (sensor enabled)
−Second room operator unit ID=2 MST=1 Slave
−Third room operator unit ID=3 MST=1 Slave
−Fourth room operator unit ID=4 MST=1 Slave
−Fifth room operator unit ID=5 MST=1 Slave
Further control loops can also be defined by means of a special application in the room
controller. In such cases, other room operator units measure the temperature on the
same room bus.
Several control loops
Example with two control loops:
−First room operator unit for control loop 1 ID=1 MST=0
−Second room operator unit for control loop 2 ID=2 MST=0
After a power failure, the room operator unit can be set to initialization mode by
operating the keys in the following sequence approximately 6 to 12 seconds after
power has been restored to the room controller or room operator unit:
Changing ID and MST
1. Hold down key 7
2. Hold down key 4
3. Release key 7
4. Release key 4
The current device address will now be displayed, alternating with the letters "Id". The
value can be modified with the "Minus" and "Plus" keys (keys 2 and 3).
After setting the required ID number, the ID number setting is confirmed with key 6.
The current MST number will now be displayed, alternating with the letters "MST". The
value can be modified with the "Minus" and "Plus" keys (keys 2 and 3).
4/8
Siemens HTC3.1/A, HTC3.1S/A – Room operator units CM2N6319en
Building Technologies 31.07.2008
After setting the required MST number, the setting is confirmed with key 6.
After this input, the settings are saved and all LCD segments are illuminated for
approximately 4 seconds. This allows you to check that all the available LCD display
characters are still operating correctly.
The temperature sensor connected to the room operator unit HTC3.1/A, or the
HTC3.1S/A room operator unit with the built-in temperature sensor must be installed in
a suitable location for measurement of the room temperature.
Mounting location
The HTC3.1/A room operator unit, which does not have a built-in temperature sensor,
is not restricted in this way. A suitable temperature sensor for this unit is the HSE1.1
cable temperature sensor. If the VIMAR idea installation system is used, the room
temperature sensor HSE1.2 is also suitable.
STOP Caution •Do not connect an external room sensor to the HTC3.1S/A room operator unit.
•Heat sources result in false temperature measurements. Ensure a minimum distance
of 1.5 m from lamps.
If the sensor is in an unsuitable location, the measured value can be corrected with a
temperature offset. The correction can be undertaken with the SCOPE or HSC (Hotel
Solution Commissioning) tool.
Correcting the
measured value
In the standard application the basic setting for the temperature offset is –4 K. This
applies to the HTC3.1S/A room operator unit with the built-in sensor.
For the HTC3.1/A room operator unit with an external type HSE1.2 sensor, a
temperature offset of –1 K must be set.
Mounting
•The HTC3.1/A or HTC3.1S/A should be mounted at eye level in the living area of the
hotel room.
•Lamps and other heat sources in the vicinity of the room temperature sensor must
not be allowed to distort the measured temperature. The room operator unit with the
built-in temperature sensor is not suitable for mounting within reach of the bed, for
example, because items such as bedside lamps cause to0 great an increase in the
measured temperature.
•Conduits must be sealed where they enter wall boxes, so that the temperature is not
falsified by draughts.
•First press the room operator unit into the base frame and remove the protective
transparent film from the display window. There is no access to the protective film on
the display window once the front-plate label is in position. Only then should you
attach the adhesive front-plate label. It is important to follow this sequence, because
if the front-plate label is fitted first, it is then difficult to press the unit into the base
frame.
•To remove the unit, it must be unscrewed from the wall together with the base frame.
•The screw terminals of the room operator unit can accommodate only one wire with
a maximum diameter of 1 mm. When connecting the bus, therefore, we recommend
that the room operator unit should be connected as the last room-bus device.
•The device is designed for fixed installation in a dry, enclosed space.
•For installation in a 4-module mounting box, depth 50 mm
•Mount horizontally only, with the front plate vertical
•Do not install AC 230 V devices in the same mounting box
•Commissioning must be carried out by trained personnel only
•Do not open the unit
•Local safety and installation regulations must be observed
5/8
Siemens HTC3.1/A, HTC3.1S/A – Room operator units CM2N6319en
Building Technologies 31.07.2008
Commissioning
If several devices are operated by the same room controller, an address must be set for
each one (see "Engineering notes"). Only one device will operate with the factory-set
default.
Note In the standard application with only one room operator unit, the defaults are ID = 1
and MST = 0 (sensor active). The room operator units are therefore factory-set to these
defaults.
Depending on the location of the sensors, the measured value may need to be adjusted
with the SCOPE or HSC tool (see "Engineering notes").
Technical data
Power supply (from HRC3..) Working voltage DC 9..15 V
Current 20 mA
Bus interface Bus voltage SELV DC 12 V
Type RS485
Transmission speed 4800 baud
Temperature signal input Voltage DC 0…12 V 10…40 °C
Current 1 mA
Measuring element NTC 10kOhm
Setpoint correction Correction range ±2 or ±4 K
Resolution 0.5 K or 1 K
Parameters Parameters set with internal software and
stored in EEPROM
Environmental conditions Operating temperature: -5...+50 °C
Transport temperature: -25..+65 °C
Humidity <95 % non-condensing
Air pressure during operation: Min. 700hPa (3000m above sea level)
Air pressure during transportation: Min. 700hPa (10, 000m above sea level)
Standards
Product safety Automatic electrical controls for household
and similar use EN 60 730-1 and EN 60 730-2-11
Electromagnetic
compatibility Emitted interference in accordance with
Interference immunity in accordance with EN 61000-6-3
EN 61000-6-2
Housing protection
Protection standard
Protection class IP 20 to EN 60529
III to IEC1140
conformity Meets the requirements of
EMC Directive
89/336/EEC
Low Voltage Directive 73/23/EEC
UL/CUL approval UL/CUL 916
Dimensions Suitable for flush mounting in rectangular
flush-mounting box or cavity-wall box 4 modules
Color Operator panel label Pantone black 7U2Y
Dimensions See also dimension diagrams 103mm x 51mm x 25mm
Weight Excluding packaging
With packaging 0.050 kg
0.068 kg
6/8
Siemens HTC3.1/A, HTC3.1S/A – Room operator units CM2N6319en
Building Technologies 31.07.2008
Connection diagrams
12345
6319G01
6
(GND)
(DC 12 V)
1 Serial port, RS485+
2 Serial port, RS-485−
3 Working voltage DC 0 V
4 Working voltage DC 12 V
5,6 Connection for 10 kΩNTC
temperature sensor
Connection
terminals
12345 S2
X12
6319A01
N1
6
1234
B1
S2 Room operator unit, type HTC3.1/A
B1 Temperature sensor, 10 kΩ, NTC
(e.g. HSE1.1, HSE1.2)
N1 HRC3.. room controller
Wiring diagram
HTC3.1/A
125S2
X12
6319A02
N1
6
1234
34
S2 Room operator unit, type HTC3.1S/A
N1 HRC3.. room controller
Wiring diagram
HTC3.1S/A
STOP Caution Note the cross-over between pins 3 and 4.
7/8
Siemens HTC3.1/A, HTC3.1S/A – Room operator units CM2N6319en
Building Technologies 31.07.2008
Dimensions
51
100
102,5
25 1,5
67
9,5
>25
6319M01
Auto
Dimensions in mm
3
108
140,5
80,5
6319M02
8/8
Siemens HTC3.1/A, HTC3.1S/A – Room operator units CM2N6319en
©2005-2008 Siemens Switzerland Ltd. Sub
j
ect to chan
ge
Building Technologies 31.07.2008

This manual suits for next models

1

Other Siemens Control Unit manuals

Siemens FDK:085U0321 User manual

Siemens

Siemens FDK:085U0321 User manual

Siemens CUA20 User manual

Siemens

Siemens CUA20 User manual

Siemens Simatic S7-1500 User manual

Siemens

Siemens Simatic S7-1500 User manual

Siemens SINUMERIK 802D Installation guide

Siemens

Siemens SINUMERIK 802D Installation guide

Siemens MXG461B Series Owner's manual

Siemens

Siemens MXG461B Series Owner's manual

Siemens Simatic S7-1500 User manual

Siemens

Siemens Simatic S7-1500 User manual

Siemens SIMATIC ET 200SP User manual

Siemens

Siemens SIMATIC ET 200SP User manual

Siemens SITRANS F M MAGFLO series User manual

Siemens

Siemens SITRANS F M MAGFLO series User manual

Siemens VALVEGYR LDU11.323A17 User manual

Siemens

Siemens VALVEGYR LDU11.323A17 User manual

Siemens LAL1.25 User manual

Siemens

Siemens LAL1.25 User manual

Siemens FDCI223 User manual

Siemens

Siemens FDCI223 User manual

Siemens SINORIX CPY-35 User manual

Siemens

Siemens SINORIX CPY-35 User manual

Siemens SIMATIC ET 200SP Technical Document

Siemens

Siemens SIMATIC ET 200SP Technical Document

Siemens SIRIUS 3RF2330-DA Series User manual

Siemens

Siemens SIRIUS 3RF2330-DA Series User manual

Siemens SITRANS PCS 7 Parts list manual

Siemens

Siemens SITRANS PCS 7 Parts list manual

Siemens SINAMICS G120 Administrator guide

Siemens

Siemens SINAMICS G120 Administrator guide

Siemens P Series User manual

Siemens

Siemens P Series User manual

Siemens SINAMICS G120 Datasheet

Siemens

Siemens SINAMICS G120 Datasheet

Siemens 7KM4211-1BA00-3AA0 User manual

Siemens

Siemens 7KM4211-1BA00-3AA0 User manual

Siemens SIMOTION D410 PN User manual

Siemens

Siemens SIMOTION D410 PN User manual

Siemens SIRIUS 3RA2711 C Series User manual

Siemens

Siemens SIRIUS 3RA2711 C Series User manual

Siemens SINAMICS S120 User manual

Siemens

Siemens SINAMICS S120 User manual

Siemens SINAMICS G120P CU230P-2 Administrator guide

Siemens

Siemens SINAMICS G120P CU230P-2 Administrator guide

Siemens LMO14 Series User manual

Siemens

Siemens LMO14 Series User manual

Popular Control Unit manuals by other brands

Intermec MaxiScan 3010 installation guide

Intermec

Intermec MaxiScan 3010 installation guide

Bardiani BYAW3 Instruction, use and maintenance manual

Bardiani

Bardiani BYAW3 Instruction, use and maintenance manual

EastRising Technology ER-OLED0.91-1 user manual

EastRising Technology

EastRising Technology ER-OLED0.91-1 user manual

MITSUBISHI ELECTRIC ENGINEERING FA Goods FA-TH16YRA20SL user manual

MITSUBISHI ELECTRIC ENGINEERING

MITSUBISHI ELECTRIC ENGINEERING FA Goods FA-TH16YRA20SL user manual

AMX RDA-CKM Wiring diagram

AMX

AMX RDA-CKM Wiring diagram

powersoft DigiMod 3004PFC2 user guide

powersoft

powersoft DigiMod 3004PFC2 user guide

Wellpro WP9038ADAM user manual

Wellpro

Wellpro WP9038ADAM user manual

H3C SR6600 SPE-FWM manual

H3C

H3C SR6600 SPE-FWM manual

Linear Technology Dust Networks Eterna LTP5901 Integration guide

Linear Technology

Linear Technology Dust Networks Eterna LTP5901 Integration guide

fafnir VISY-Input 8 Technical documentation

fafnir

fafnir VISY-Input 8 Technical documentation

Emerson KEYSTONE V30 Series Installation and Operation Manua

Emerson

Emerson KEYSTONE V30 Series Installation and Operation Manua

Ebyte E31-433T30D user manual

Ebyte

Ebyte E31-433T30D user manual

Elektrogas VMM quick start guide

Elektrogas

Elektrogas VMM quick start guide

getAir EASY Installation & user guide

getAir

getAir EASY Installation & user guide

Ditek DTK-DF120S12 user guide

Ditek

Ditek DTK-DF120S12 user guide

Vira SKV 3400 Installation and operating instructions

Vira

Vira SKV 3400 Installation and operating instructions

Beast-Tek Instruments PIXEL DRUM v1.3 Build guide

Beast-Tek Instruments

Beast-Tek Instruments PIXEL DRUM v1.3 Build guide

Toshiba GN-4020 manual

Toshiba

Toshiba GN-4020 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.