6/10
Siemens Building Technologies CC1N7130en
Landis & Staefa Division 31.07.2000
Function •Burner control is reset
•All contacts in the line are closed
•No undervoltage
•Flame detector is darkened, no extraneous light
•Safety shut-down in the operating position takes place should the mains voltage
drop below about AC 165 V
•Restart is initiated when the mains voltage exceeds about AC 175 V
If the oil pre-heater’s release contact does not close within 10 minutes, the burner control
will initiate lock-out.
After no more than 24 hours of continuous operation, the burner control will initiate an
automatic safety shut-down followed by a restart.
If lock-out occurs, the outputs for the fuel valves and the ignition will immediately be
deactivated (< 1 second).
Cause Response
After a mains failure Restart
After voltage has fallen below the undervoltage threshold Restart
In the event of a premature, faulty flame signal during «t1» Lock-out at the end of «t1»
In the event of a premature, faulty flame signal during «tw» Prevention of start-up, lock-out after no more than
40 seconds
If the burner does not ignite during «TSA» Lock-out at the end of «TSA»
In the event the flame is lost during operation Max. 3 repetitions, followed by lock-out
Oil pre-heater’s release contact does not close within 10 min. Lock-out
In the event of lock-out, the LMO... remains locked (lock-out cannot be changed), and the
red signal lamp will light up. This status is also maintained in the case of a mains failure.
Whenever lock-out occurs, the burner control can immediately be reset. To do this, keep
the lock-out reset button depressed for about 1 second (< 3 seconds).
If the flame is lost during «TSA», the burner will be reignited, but not later than at the
end of «TSAmax.». This means that several ignition attempts can be made during
«TSA» (refer to «Program sequence»).
If the flame is lost during operation, a maximum of 3 repetitions can be made. If the
flame is lost for the 4th time during operation, the burner will initiate lock-out. The repeti-
tion count is restarted each time controlled switching on by «R-W-SB» takes place.
QRB... QRC...
12
11 LMO...
bl
µA DC
+
QRB...
7130v01/0700
sw
1211 LMO...
1
sw
bl br
µA DC
+
QRC1...
7130v02/0700
As an alternative to the detector current measurement, the diagnostic tool OCI400 /
ACS400 can be used. In that case, connection of the DC microammeter is not required.
Legend µA DC DC microammeter with an internal resistance of Ri = max. 5 kΩbl Blue
sw Black
br Brown
Preconditions for start-
up
Undervoltage
Time supervision oil
pre-heater
Controlled intermittent
operation
Control sequence in the
event of fault
Lock-out
Resetting the burner
control
Ignition program with
LMO14.113A2 and
LMO24.113A2
Limitation of repetitions
Measurement circuit for
detector current