
0
IHO
I2 * IHO
1.5 * IHO
3 s 57 s 240 s
300 s
t[s]
Load cycle 300 s based on
High Overload
t[s]
Load cycle 300 s based on
Low Overload
0
ILO
I1.5 * ILO
1.1 * ILO
3 s 57 s 240 s
300 s
*A5E35088648-AE*
Lifting
1
2
3
Mounting lower shielding plate
Compact Operating Instructions SINAMICS G120
Power Module, PM240-2, FSD, FSE, FSF
Siemens AG,
Frauenauracher Str. 80,
DE-91056 Erlangen Issue 09/2015
FSD
FSE
FSF
Contents of delivery
Compact Operating Instructions
CSA Warning labels for Canadian plants
EMC connection lug (separating plate)
Contact protection for Power connection
– if power connection not used
1) Increasing the pulse frequencies leads to an output current reduction. For more details refer to the Hardware Installation Manual.
2) The maximum surrounding air temperature is determined by the component (Power Module, Control Unit or Operator panel) with the
lowest maximum temperature
0 Hz … 550 Hz, depending on the control mode
Less than rated input current
(Increasable in 2 kHz steps 1))
200 V Units, factory setting: 4 kHz
setting range: < 37 kW: 4 kHz … 16 kHz
≥37 kW 4 kHz … 8 kHz
400 V Units, factory setting: < 75 kW 4 kHz
≥75 kW 2 kHz
setting range: < 55 kW: 2 kHz … 16 kHz
≥55 kW 2 kHz … 8 kHz
690 V Units, factory setting: 2 kHz
setting range: 2 kHz … 4 kHz
Electromagnetic compatibility
Filtered devices comply with EN 61800-3: 2012 and are suitable for Category C2 / C3. For more
details refer to the Hardware Installation Manual.
DC braking, Compound braking, Resistor braking
IP20 according to EN60529 (IEC) / open type (UL)
Motor overload protection
This equipment is capable of providing internal motor overload protection according to UL61800-5-1.
The protection level is 115 % of full load current of the equipment. This is adjusted via parameter
p0640 and assumes the equipment has had basic motor commissioning for the motor used as
described in the documentation.
2)
-20 °C … 40 °C (-4 °F … 104 °F) without derating / up to 60 °C (140 °F) with derating
- 40 °C … +70 °C (- 40 °F … 158 °F)
Installation altitude above sea level
Up to 1000 m (3300 ft) without derating / Up to 4000 m (13000 ft) with derating
< 95 % RH - non-condensing
Suitable for environmental class 3C3 according to IEC 60721-3-3 against damaging chemical
substances
Protected against pollution according to pollution degree level 2.
If protection against conductive pollution is required, the unit must be installed in an IP54 cabinet.
Long-term storage in the transport packaging according to Class 1M2 to EN 60721-3-1. Transport in
the transport packaging according to Class 2M3 to EN 60721-3-2. Vibration during operation
according to Class 3M2 to EN 60721-3-3
values
(LO)
input
current
Size
Line fuses, fuses for branch
circuit protection
Power
(IEC)
Output
current
Power
(IEC)
Output
current
acc. IEC/UL
Siemens 2)
class J
acc. UL
600 V ac
in
3 AC 200 … 240 V ± 10 %, U
out
in
* 0.95, brake output volt. 410 V
in
3 AC 380 … 480 V – 20 %, + 10 %, U
out
in
* 0.95, brake output volt. 820 V
in
3 AC 500 … 690 V – 20 %, + 10 %,
3)
out
in
* 0.95, brake output volt. 1210 V
1) _: A = filtered unit, U = unfiltered unit
2) must be installed in the same overall assembly
3) for UL applications 3 AC 500 V ... 600 V only
SCCR: The Short Circuit Current Rating of the supply circuit
shall not exceed 65 kA rms (Symmetrical Amperes),
240/480/600/690 Vac*) maximum, when protected by Listed
Class J Fuses or Semiconductor Fuses as referred in this
instruction manual.
*) value according to the voltage rating of the device; 690 V
are not applicable to Class J fuses)
The brake chopper is rated for 100 % inverter nominal
output power. Maximum load cycle will be 12 s nominal
power in a 240 s period. The brake chopper is protected by
a short circuit protection.
WARNING - The opening of the branch-circuit
protective device may be an indication that a fault current
has been interrupted. To reduce the risk of fire or electrical
shock, current-carrying parts and other components of the
controller should be examined and replaced if damaged. If
burnout of the current element of an overload relay occurs,
the complete overload relay must be replaced.
Applicable motors
Using 200 V or 400 V Power Modules, motors with a rated
current from 25 % … 150 % of the rated converter output
current can be used at full performance.
Using 600 V Power Modules, motors with a rated current
from 50 % … 150 % of the rated converter output current
can be used at full performance.
For United States / Canadian installations (UL/cUL):
The products are cULus listed under E192450.
Integral solid state short circuit protection does not provide
branch circuit protection. Branch circuit protection must be
provided in accordance with the NEC or CEC, Part I,
respectively, and any additional local codes. You find fuses
for branch circuit protection in the table on the right top of
this page.
Install power conductors sufficiently separated or isolated
against any low voltage circuits or other power circuits.
Use 60/75 °C copper conductors only.
On the brake resistor terminal of FSE use 75 °C rated
conductors only.
FSF line and motor terminals shall be connected with UL-
Listed (ZMVV) ring lugs with suitable voltage and current
rating (min. 125 % of input/output current).
For connecting the safety related function "Safe Torque
Off" (STO) or Brake Relay use 600 V insulated wire only.
Additional requirements for CSA compliance:
Overvoltage Category OVC III must be ensured for all
primary circuit connections of the equipment. This may
require Transient Surge Supression (SPD) to be installed
on the line side of the equipment. The voltage rating of the
SPD shall not be smaller than the supply voltage. It shall
provide protection for a rated impulse withstand voltage
peak of not more than the VPR shown in the table below.
For detailed information refer to Hardware Installation Manual PM240-2, Issue 08/2015 or younger under:
http://support.automation.siemens.com/WW/view/de/30563173/133300
For connecting the safety related function "Safe Torque
Off" (STO) or Brake Relay use 600 V insulated wire only.
Additional requirements for CSA compliance:
Overvoltage Category OVC III must be ensured for all
primary circuit connections of the equipment. This may
require Transient Surge Supression (SPD) to be installed
on the line side of the equipment. The voltage rating of the
SPD shall not be smaller than the supply voltage. It shall
provide protection for a rated impulse withstand voltage
peak of not more than the VPR shown in the table below.
For detailed information refer to Hardware Installation Manual PM240-2, Issue 08/2015 or younger under:
http://support.automation.siemens.com/WW/view/de/30563173/133300
Declaration of Conformity:
The Declaration of Conformity can be found at the following link:
http://support.automation.siemens.com/WW/view/en/30563514/134200
For connecting the safety related function "Safe Torque
Off" (STO) or Brake Relay use 600 V insulated wire only.
Additional requirements for CSA compliance:
Overvoltage Category OVC III must be ensured for all
primary circuit connections of the equipment. This may
require Transient Surge Supression (SPD) to be installed
on the line side of the equipment. The voltage rating of the
SPD shall not be smaller than the supply voltage. It shall
provide protection for a rated impulse withstand voltage
peak of not more than the VPR shown in the table below.
voltage
voltage
3 AC
200 … 240 V
3 AC
380 … 480 V
3 AC
500 … 600 V
For detailed information refer to Hardware Installation Manual PM240
http://support.automation.siemens.com/WW/view/de/30563173/133300