#: Phase loss1, Phase reversal2, Under voltage3, Over voltage4, Phase unbalance5 NA – Starter is unprotected from incoming power
supply faults,only protection from load side faults. In this mode, amber LED will continously ON if incoming power supply is
healthy and will blink if the incoming power supply is unhealthy – Refer 2.8
1) LMR-A: Manual mode
5A : Check the mode of LMR-A, if it is manual mode, please follow the below steps.
5B : Switches ON the 3-Phase incoming main supply.
5C : Switch ON the rocker switch
5D : Amber LED will start blinking
5E : Amber LED will blink for a duration of min.30sec.
5F : After the ON delay duration, amber LED remains blinking indicating that the 3phase incoming supply is unhealthy.
15G : - Check the rated operational voltage of the starter in incoming terminal block (TB1)between L1- L2 L2-L3, L1-L3
with suitable equipment e.g. multimeter.
- Check for the phase loss in any phase (L1,L2,L3) with suitable equipment e.g. multimeter.
15H: - After resuming incoming main supply to normal condition,
- Repeat the steps from 5A to 5E and then go to step no.5I
If fault still exists, then
25G : - Check the phase sequence of all the phases of incoming main supply.
- Identify the wrong sequence of phase connected in any of the incoming terminal.
25H: - Connect the phase sequence of all the phases correctly (R phase to L1 , Y phase to L2, B phase to L3) to the incoming main
supply terminals of Terminal block TB1.
- Repeat the steps from 5A to 5E and then go to step no.5I
If fault still exists, then
35G : - Check the rated operational voltage of the starter in incoming terminal block (TB1) between L1-L2, L2-L3, L1-L3 with
suitable equipment e.g. multimeter.
- Check whether the 3-phase voltage in the incoming terminals of terminal block TB1 is <minimum required voltage
(Refer table no.13).
35H : - Keep the 3-phase voltage to the incoming terminals of terminal block TB1 to a voltage between min.required voltage
& Max.voltage allowed (Refer table no.13).
- Repeat the steps from 5A to 5E and then go to step no.5I
2.6: Troubleshooting Guidelines in case any incoming
supply fault is present before switching ON the Starter
Starter Fault conditon:
LMR-A
Mode
Manual
Auto
Bypass
3ф
main
supply
ON
ON
ON
Rocker
switch
ON
ON
ON*
On-
Delay
0.5-5min
0.5-5min
0.5-5min
Amber
LED
Blink
(On-delay
duration)
Blink
(On-delay
duration)
Blink
(On-delay
duration)
Amber
LED
Blink
Blink
Blink
#
#
NA
Possible
causes
of fault
1)
2)
NA
ON
ONONON
ON
Corrective
action
Amber
LED
‘ON’ Push
button
Starter
Operation
ONON
NA
ON
ON
ONON
Green
LED
Table: 12 FASD starter operating sequence in fault condition
5A 5B 5C 5D 5E 5F 5G 5H 5L5J 5K5I
Installation, Maintenance & Troubleshooting guide | Version 02
20
ON operation