D9
Siemens Energy & Automation, Inc. 1000 McKee Street Batavia, Illinois 60510
SFIM-7002A-0901
Section D, September, 2001
Full Voltage Contactor with Fusible Switch (refer to Pg E4): Disconnect Ratings and Space Requirements
Maximum Standard Maximum
Fuse Unit Control Control
Maximum Horsepower Contactor Switch Clip Unit Space Transformer Transformer
200V 230V 460V 575V Size Size Size Height Factor VA VA Relay Timer
6.92 8.0 15.9 19.9 0 30 30 12 1 50 150 1* 1*
10.4 11.90 23.9 29.8 1 30 60 12 1 50 150 1* 1*
24.2 27.8 55.7 69.6 2 60 60 12 1 50 150 1* 1*
31.1 35.8 71.6 89.5 3 100∆100 24 2 50 250 1* 1*
43.3 50.0 99.4 124 3 100 100 24 2 150 250 1* 1*
67.5 77.6 155 194 4 200 200 42 3½ 150 250 2 1
121 139 278 348 5 400 600 72a550
d150d22
162 210 415 515 6 600 600 72s6 150 250 1 1
* Either/or but not both
** Oversized for additional equipment
aFixed mounted unit
sFixed mounted unit - Space behind not available
dStarter supplied with interposing relay(s)
∆200, 230V applications
Available Features - Standard Unit Size
• Control power transformer with fused secondary, and dual
fused primary.
• Pull-apart control terminals.
• Pull-apart load terminals, Sizes 0 - 2.
• 4 pilot devices mounted on unit device panel.
• Control relay.
• Surge suppressor.
• ETM.
• Handle interlocks operate with handle.
• Extra starter auxiliary contacts in addition to NO seal-in
contact.
• Class J fuse clips.
• Refer to tables for maximum size control power trans-
former, relays, and timer addition.
• Communicating devices (ASi, SIMOCODE-DP, SAMMS)
Auxiliary Contacts
Starter Extra Contacts
Size Per Starter Type
0 - 1 4 SPST NO or NC
2 - 4 3 SPST NO or NC
5 - 6 3 SPDT NO & NC
Full Voltage Contactor with ITE Circuit Breaker Disconnect Ratings and Space Requirements
Circuit Standard Maximum
Maximum KW Breaker Unit Control Control
Resistance Heating Leads Contactor Frame Unit Space Transformer Transformer
200V 230V 460V 575V Size Size Height Factor VA VA Relay Timer
6.92 8.0 15.9 19.9 0 125 12 1 50 150 1* 1*
10.4 11.9 23.9 29.8 1 125 12 1 50 150 1* 1*
24.2 27.8 55.7 69.6 2 125 12 1 50 150 1* 1*
43.3 50.0 99.4 124 3 125 18 1½ 150 250 1* 1*
43.3 50.0 99.4 124 3 125 24** 2 150 250 2 1
67.5 77.6 155 194 4 125/250 24 2 150 250 2 1
121 139 278 348 5 400 36 3 50d150d1–
162 210 415 515 6 600 48s4 150 250 2 1