Siemens Building Technologies Group 12.1997
4 User function
Table 5: Notes on parameterization ’Extinguishing’ via SWE11
Function Choice of variants SWE11
Outline description Value Def. 1)
Valve on: confirmation:
Line ’Extinguishing activated’
’Active’ status generates
a) No message (Line unused / Message ’simulated’)
b) Message ’Extinguishing activated’ or signal contact existent
0
11
Key stop/block:
Function line ’Stop /Blocking key’
’Active’ status generates
a) autom.+ man. activation of extinguishing blocked (= ’Stop key’)
b) Autom. activation of extinguishing blocked (= ’Blocking key’) 2) 0
1
0
Activation time:
Duty cycle of activating agent valve
(Activating device 2)
a) Active for 0..240sec (Value 0..240 permissible)
b) Active until reset (value 255 entered)
0..240
255
120
Flooding time:
Flooding time
(Duty cycle of activating device 1)
a) Active for 0..240sec (Value 0..240 permissible)
b) Active until reset (Value 255 entered)
0..240
255
30
Evacuation time:
Evacuation time
(Delay to activating device 1)
a) 0..240sec (Value 0..240 permissible) 0..240 16
Stop –> evacuation time:
Function ’Stop key active’ generates
during ’Evacuation’
a) Evacuation time is reset (New start)
b) Evacuation time is not reset
0
1
0
Horn activation:
Activation and runninng mode of
alarm horn
a) activated upon ’pre-alarm’ and ’evacuation’ and ’actuated’
b) activated upon ’evacuation’ and ’actuated’
c) running mode continuous
d) running mode pulsating upon ’pre-alarm’ 3)
e) running mode pulsating upon ’evacuation’ and ’actuated’ 3)
f) running mode pulsating upon ’pre-alarm’ / ’evac.’ / actuat.’ 3)
a + c
a + d
a + e
a + f
b + c
b + e
0
8
16
24
1
17
0
Silence:
Function ’Switch off alarm horn’
(Blocked during ’Flooding’+ Evacuat. )
a) Can be carried out via CT or extinguishing control panel
b) Can only be carried out via extinguishing control panel
0
22
Warning panel mode:
Deactivating and running mode of
warning panel
a) active until RESET (no switching off via B3Q440)
b) active until switched off via B3Q440
c) running mode continuous
d) running mode pulsating 3)
a + c
a + d
b + c
b + d
1
9
4
12
1
Extinguishing agent LOSS:
Line ’Extinguishing agent loss’
Status ’Active’ generates
b) Fault AND ’Autom. + man. activation of extinguishing blocked’
a) Fault
0
1
0
Stop key FAULT:
Line ’Stop-/blocking key’
Open line / short circuit generates
a) Fault
b) Fault AND ’Autom. + man. activation of extinguishing blocked’
0
1
0
LED ’Operation’:
’Power on’ indicator
Local extinguish. control panel (B3Q440)
a) Inactive upon ’Fault’ / ’Extinguishing blocked’ / ’Alarm’
b) always active
0
11
key switch:
Function ’Key switch’
Local extinguish. control panel (B3Q440)
a) No influence on the ’Switch off sounder’ key
b) Influence on ’Switch off sounder’ key
0
11
supply FAULT:
’Fault power supply’ indicator
Local extinguish. control panel (B3Q440)
a) active upon ’Power supply fault’ control unit
b) Spare indicator
0
11
1) Default values are laid down according to each country
2) Function variant ’Blocking key’ may be used only with software V4.xx
3) Running mode ’pulsating’ only with software V5.xx (EP5) onwards
Note
In order that the combined indicators for ’Extinguishing’
are displayed on the AlgoPilot, the corresponding ’panel
variant’ must be selected at CT or CI level
(for details see HELP AlgoWorks).
ALARM
Extinguishing
blocked
blocked
activated
Evacuation
Combined indicators
’Extinguishing’ common
to all extinguishing
SECTIONS