manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Security Sensor
  8. •
  9. Siemens FDO421 User manual

Siemens FDO421 User manual

Siemens Industry, Inc.
BuildingTechnologies Division
A6V10323926_a_en_--
These instructions are written in accordance with the installation
guidelines of NFPA 72, National Fire Alarm Code, The Installation
of Fire Alarm Systems.
CAUTION
Detection Device Storage
DO NOT install this detection device until all construction
is completed.
DO NOT store this detection device where it can be
contaminated by dirt, dust, or humidity.
DETECTOR PLACEMENT
Although no specific spacings are set for the detectors used for
a clean air application, use 30 foot center spacing (900 sq ft)
from NFPA Standard 72 initiating devices chapter, if practical,
as a guide or starting point for a detector installation layout.
This spacing, however, is based on ideal conditions–smooth
ceiling, no air movement, and no physical obstructions. In some
applications, therefore, considerably less area is protected
adequately by each smoke detector. This is why it is mandatory
to closely follow the installation drawings. In all installations place
the detector on the ceiling, a minimum of 6 inches from a side
wall, or on a wall, 6 inches from the ceiling.
If you have any questions regarding detector placement, follow
the drawings provided or approved by Siemens Industry, Inc.,
or by its authorized distributors. This is extremely important! The
detector placements shown on these drawings were chosen after
a careful evaluation of the area that is protected. Such factors
as air currents, temperature, humidity, pressure, and the nature
of the fire load were carefully considered. Especially noted were
the room or area configuration and the type of ceiling (sloped or
flat, smooth or beamed). Siemens Industry, Inc.’s extensive
experience in the design of the system assures the best detector
placement by following these drawings.
TO AVOID NUISANCE ALARMS
Do not locate the detectors where excessive smoke
concentrations exist under normal conditions, or in areas of
prolonged high relative humidity where condensation occurs.
Do not locate the detectors next to an oil burner, kitchen, or
garage where exhaust fumes can trigger an alarm. Other causes
of false alarms are dust accumulation, heavy concentrations of
steam, heavy pipe or cigar smoke, and certain aerosol sprays.
AIR CURRENTS
Before a detector can sense a fire, the products of combustion
or smoke must travel from the fire to the detector. This travel is
especially influenced by air currents; therefore, consider air
movement when designing the system. While combustion
products tend to rise, drafts from hallways, air diffusers, fans,
etc., may help or hinder the travel of combustion products to the
detector. When positioning a detector at a particular location,
give consideration to windows and doors, both open and closed,
to ventilating systems, both in and out of operation, and to other
factors influencing air movement. Do not install a detector in the
air stream of a room air supply diffuser. It is better to position a
detector closer to an air return.
The distance that products of combustion or smoke travel from
a fire to the detector is not usually the shortest linear route.
Combustion products or smoke usually rise to the ceiling, then
spread out. Average ceiling heights of 8 to 10 feet do not
abnormally affect detector response. High ceilings, located in
churches, warehouses, auditoriums, etc., do affect detector
response and should be considered.
SPECIAL CEILING CONSTRUCTION FACTORS
Ceiling obstructions change the natural movement of air and
combustion products. Depending on the direction of smoke
travel, joists and beams can slow the movement of heated air
and smoke, while pockets between them can contain a reduced
level of smoke. Take obstructions created by girders, joists,
beams, air conditioning ducts, or architectural design into
consideration when determining area protection. Refer to the
Initiating Devices chapter of NFPA Standard 72 for Location and
Spacing requirements for specific types of construction; e.g.
beam, suspended, level, sloped and peaked ceilings. The
detector is also compatible with the following mechanical
protection guard model: STI-9604 (see www.STI-USA.com for
details).
TEMPERATURE – HUMIDITY – PRESSURE – AIR
VELOCITY
The temperature range for the FDO421 detector is 32°F (0°C)
to 120°F (49°C). Use the detector in environments where the
humidity does not exceed 95% (non-condensing). Normal
changes of atmospheric pressure do not affect detector
sensitivity. The air velocity range is 0-4000 ft/min for open areas
applications and direct in air duct applications. Follow detector
spacing and location requirements in NFPA 72 Chapter for High
Air Movement Areas and Control of Smoke Spread.
LED INDICATOR OPERATION
The Model FDO421 contains an LED indicator capable of
flashing either one of three distinct colors: green, yellow, or red.
During each flash interval, the microprocessor-based detector
monitors the following:
• Smoke in its sensing chamber
• Smoke sensitivity is within the range indicated on the
nameplate label
• Internal sensors and electronics
Photoelectric Detector
Installation Instructions
Model FDO421
Figure 1
FDO421
Based on the results of the monitoring, the LED indicator flashes
the following:
hsalF
roloCnoitidnoC
lavretnIhsalF
)sdnoceS(
*neerG ekomS.noitarepoyrosivrepuslamroN
.stimildetarnihtiwsiyti
vitisnes 01
wolleY sdeendnaelbuortnisirotceteD
.tnemecalper 4
deRmralA1
oN
sehsalF
ro,derewoptonsirotceteD
.dedee
nsitnemecalper -
fonoitpircsedgnidnopserrocehtwollofesaelP.ffodenrutebnacDEL*
.desulenaPeht
DETECTOR PROGRAMMING
Each detector must be programmed to respond to a unique
system address between 001 - 252.
• To program the detector address, use the Model DPU
Device Programming Unit. Refer to the DPU Manual, P/N
315-033260.
• Record the loop and device number (system address) for
the detector on the detector label and on the base to
prevent installing the detector in the wrong base. The
optional DPU label printer can be used for this purpose.
Each detector provides pre-programmed parameter sets which
can be selected by the panel. Please follow the corresponding
descriptions of the panel used.
• Sensitive
• Standard
• Robust
• Air Duct
When using this detector direct in air duct
applications, be sure the detector is set to the
parameter “Air Duct.”
WIRING
Detector bases for Model FDO421 should be connected as
shown in Figure 2.
DETECTOR MOUNTING
To ensure proper installation of the detector head into the base,
be sure the wires are properly dressed at installation:
• Position all wires flat against the base.
• Take up all slack in the outlet box
• Route wires away from connector terminals.
TO INSTALL DETECTOR HEAD:
• Rotate detector counterclockwise while gently pressing on
it until the detector seats fully into base.
• Then rotate the detector clockwise until it stops and locks in
place. Insert optional locking screw (Order Model LK-11).
TO REMOVE DETECTOR HEAD:
• Loosen locking screw, if installed. Then rotate the detector
counterclockwise until stop is reached.
• Pull detector out of base.
DETECTOR TESTING
Only qualified service personnel should test. To assure proper
operation of the detector, both the Sensitivity and Functional
Test should be conducted. The minimum test schedule may be
found in the current edition of NFPA 72.
SENSITIVITY MEASUREMENT
The sensitivity of FDO421 detectors can be tested individually
using the DPU. Refer to the DPU Manual, P/N 315-033260. The
sensitivity can also be measured by the panel. Follow the
instructions of the panel used.
FUNCTIONAL TEST
Perform a functional (Go, No-Go) test by activating the detector
using Test Gas, P/N 500-649750, following the instruction on
the gas canister label. This test is simply used to ensure that
smoke can enter the sensing chamber and alarm the control
panel when the detector reaches the programmed obscuration
(concentration) level.
The FDO421 detectors can also be tested individually using the
DPU. Refer to the DPU Manual, P/N 315-033260.
DETECTOR MAINTENANCE
The control unit automatically indicates the trouble message for
the FDO421 detector whose smoke chamber changes to the
level where the set sensitivity cannot be maintained. In such
circumstances, the detector may require replacement.
CAUTION: UNDER NO CIRCUMSTANCES IS THE
DETECTOR HEAD TO BE DISASSEMBLED. NO REPAIRS
SHOULD BE ATTEMPTED.
DO NOT PAINT
The detector/base plastic is marked DO NOT PAINT. This is
intended to prohibit painting during routine maintenance of the
occupancy which can affect proper operation of the detector.
TO INITIATING
CIRCUIT OF
SIEMENS
INDUSTRY, INC.
COMPATIBLE
CONTROL UNIT
OPTIONAL
REMOTE
ALARM
INDICATOR
MODELS
RL-HW/RL-HC
TO NEXT BASE
TO NEXT BASE
DO NO
T
USE AN
END OF
LINE
DEVICE
DETECTOR BASE
MODEL DB-11/DB-11E
LINE 1**
LINE 2**
5
6
1a
TB1
TB3
TB2
1b
5
6
1a
1b
RELAY*
CONTACTS
3A, 120 VAC
3A, 30 VDC
REMOTE RELAY
BASE MODEL DB2-HR
*The relay contacts are shown after System reset, which represents the non-alarm condition.
**FDO421 is a polarity insensitive detector. Line 1 and Line 2 can be either line of the loop.
5+
NO
C
NC
6–
5+
NO
C
NC
6–
DO NO
T
USE AN
END OF
LINE
DEVICE
Figure 2
Installation and Wiring Diagram
A6V10323926_a_en_--Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada

Other manuals for FDO421

2

Other Siemens Security Sensor manuals

Siemens DB721 User manual

Siemens

Siemens DB721 User manual

Siemens AS Series User manual

Siemens

Siemens AS Series User manual

Siemens SICAM V01.00 User manual

Siemens

Siemens SICAM V01.00 User manual

Siemens DB-HR User manual

Siemens

Siemens DB-HR User manual

Siemens FDT421 User manual

Siemens

Siemens FDT421 User manual

Siemens FDOOT441 User manual

Siemens

Siemens FDOOT441 User manual

Siemens UP 255D21 5WG1 255-2DB21 Service manual

Siemens

Siemens UP 255D21 5WG1 255-2DB21 Service manual

Siemens DELTA iris 5TG5930-2 Series User manual

Siemens

Siemens DELTA iris 5TG5930-2 Series User manual

Siemens Cerberus CS1140 Guide

Siemens

Siemens Cerberus CS1140 Guide

Siemens HI921 User manual

Siemens

Siemens HI921 User manual

Siemens FDL241-9 Guide

Siemens

Siemens FDL241-9 Guide

Siemens 5TC1585 User manual

Siemens

Siemens 5TC1585 User manual

Siemens 5SM6 01 2 Series User manual

Siemens

Siemens 5SM6 01 2 Series User manual

Siemens AlgoRex CS1140 Operating instructions

Siemens

Siemens AlgoRex CS1140 Operating instructions

Siemens Synco QFP910 User manual

Siemens

Siemens Synco QFP910 User manual

Siemens 5SM6011-1 User manual

Siemens

Siemens 5SM6011-1 User manual

Siemens DELTA i-system 1,1 Komfort 5TC1 505 User manual

Siemens

Siemens DELTA i-system 1,1 Komfort 5TC1 505 User manual

Siemens DB110 User manual

Siemens

Siemens DB110 User manual

Siemens ADM-Q12 User manual

Siemens

Siemens ADM-Q12 User manual

Siemens ADB-11 User manual

Siemens

Siemens ADB-11 User manual

Siemens FDOOTC241 User manual

Siemens

Siemens FDOOTC241 User manual

Siemens FDOOT241-9 User manual

Siemens

Siemens FDOOT241-9 User manual

Siemens Cerberus CS1140 Technical manual

Siemens

Siemens Cerberus CS1140 Technical manual

Siemens FDB181C User manual

Siemens

Siemens FDB181C User manual

Popular Security Sensor manuals by other brands

Protekt CRW 300  Series instruction manual

Protekt

Protekt CRW 300 Series instruction manual

SharpEye 40M user guide

SharpEye

SharpEye 40M user guide

Banner LTF instruction manual

Banner

Banner LTF instruction manual

Fluke TNT 12000 DoseMate Quick reference guide

Fluke

Fluke TNT 12000 DoseMate Quick reference guide

Levenhuk ERMENRICH PING SA30 user manual

Levenhuk

Levenhuk ERMENRICH PING SA30 user manual

Assa Abloy Yale SR-A100-0EIR Installation

Assa Abloy

Assa Abloy Yale SR-A100-0EIR Installation

RAB Lighting STL12LV installation manual

RAB Lighting

RAB Lighting STL12LV installation manual

ControlByWeb XW-112 user manual

ControlByWeb

ControlByWeb XW-112 user manual

Helite B'SAFE user guide

Helite

Helite B'SAFE user guide

GJD MX25 user guide

GJD

GJD MX25 user guide

Vernier Go Direct PAR manual

Vernier

Vernier Go Direct PAR manual

Schonstedt SPOT instruction manual

Schonstedt

Schonstedt SPOT instruction manual

Bentel FireClass FC400H manual

Bentel

Bentel FireClass FC400H manual

Fiessler RAZL-2 CO Setup guide

Fiessler

Fiessler RAZL-2 CO Setup guide

Banner LS2e30-300Q8 instruction manual

Banner

Banner LS2e30-300Q8 instruction manual

IFM Electronic efector150 operating instructions

IFM Electronic

IFM Electronic efector150 operating instructions

MEDC BGE Technical manual

MEDC

MEDC BGE Technical manual

Evenlite Aperion LED installation instructions

Evenlite

Evenlite Aperion LED installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.